<strong>HART</strong> Periodic Data<br />

1<br />

16<br />

Ch-0<br />

Ch-15<br />

<strong>HART</strong><br />

AI<br />

Analog PV: (250 ms update)<br />

1<br />

16<br />

Ch-0<br />

Ch-15<br />

Analog OP: (25 ms update)<br />

<strong>HART</strong><br />

AO<br />

<strong>HART</strong> device variable scanning:<br />

Dynamic variables: (Cmd-3, PV, SV, TV, FV)<br />

Scanning configurable for every <strong>HART</strong> enabled channel!<br />

Update is configurable between 1 to 16 seconds for all<br />

sixteen channels exclusive of <strong>HART</strong> device induced delays.<br />

Device standard status: is collected every time cmd-3 is<br />

issued to a device.<br />

Device variables: (Cmd- 33, Slot-0 through Slot-3)<br />

Scanning configurable for every <strong>HART</strong> enabled channel!<br />

Update is configurable between 1 to 16 seconds for all<br />

sixteen channels exclusive of <strong>HART</strong> device induced delays.<br />

Note!<br />

Channels that are not enabled for <strong>HART</strong> and those<br />

that do not use command 3 or 33 (or at a low<br />

frequency) will allow other channels on the same<br />

IOM to scan Dynamic and Device variables<br />

proportionally faster.<br />

28 HONEYWELL September 19, 2012<br />