COOLING LOAD VS. WATER FLOW AND REFRIGERATION CAPACITY<br />

Water Required (gpm) Refrigeration<br />

Capacity<br />

Total Load Water Temperature Change* (any refrigerant)<br />

Btuh 2° 4° 6° 8° 10° Tons<br />

100 .1 .008<br />

200 .2 .1 .017<br />

500 .5 .25 .17 .042<br />

750 .75 .38 .25 .063<br />

1,000 1 .5 .3 .25 .083<br />

1,500 1.5 .75 .5 .4 .3 .125<br />

2,000 2 1 .7 .5 .4 .166<br />

2,500 2.5 1.3 .8 .63 .5 .208<br />

3,000 3 1.5 1 .75 .6 .250<br />

4,000 4 2 1.4 1 .8 .333<br />

5,000 5 2.5 1.7 1.3 1 .416<br />

6,000 6 3 2 1.5 1.2 .500<br />

7,000 7 3.5 2.4 1.8 1.4 .583<br />

8,000 8 4 2.7 2 1.6 .667<br />

9,000 9 4.5 3 2.3 1.8 .750<br />

10,000 10 5 3.4 2.5 2 .833<br />

15,000 15 7.5 5 3.8 3 1.250<br />

20,000 20 10 6.7 5 4 1.667<br />

25,000 25 12.5 8.4 6.3 5 2.083<br />

30,000 30 15 10 7.5 6 2.500<br />

40,000 40 20 13.3 10 8 3.333<br />

50,000 50 25 16.7 12.5 10 4.167<br />

75,000 75 37.5 25 18.8 15 6.250<br />

100,000 100 50 33.4 25 20 8.333<br />

250,000 250 125 83.4 62.5 50 20.833<br />

500,000 500 250 166.7 125 100 41.667<br />

750,000 750 375 250 188 160 62.500<br />

1,000,000 1,000 500 333.3 250 200 83.333<br />

1,250,000 1,250 625 416 313 250 104.167<br />

1,500,000 1,500 750 500 375 300 125.000<br />

1,750,000 1,750 875 583 438 350 145.833<br />

2,000,000 2,000 1,000 666.6 500 400 166.667<br />

Water in gpm = total load Tons = Btuh<br />

60 x 8.34 x T.R.* 12,000<br />

*Difference in temperature between water entering and leaving Temp-Plate passageways.<br />