Technical Specification of Roof Top Tower of 12, 15, 18 & 21m height
Technical Specification of Roof Top Tower of 12, 15, 18 & 21m height
Technical Specification of Roof Top Tower of 12, 15, 18 & 21m height
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
To Plate Earth<br />
e. Earth conductor should not be encircled with metal clamps while taking it along the wall.<br />
This is essential to eliminate the high inductive reactance that will impede the flow <strong>of</strong><br />
surge current along the conductor in case <strong>of</strong> lightning.<br />
f. Earthing conductor shall not pass through any metallic conduit or pipe as this will<br />
increase surge impedance.<br />
OUTDOOR<br />
GROUNDING<br />
BUS BAR<br />
To Plate Earth<br />
TOWER PLATEFORM<br />
FEEDER GROUNDING CARD<br />
FEEDER<br />
LIGHTENING<br />
ARRESTER<br />
MOUNT<br />
GROUNDING<br />
WIRE<br />
Figure – 2<br />
LIGHTENING<br />
ARRESTER<br />
MOUNT<br />
INDOOR<br />
GROUNDING<br />
BUS BAR<br />
GROUNDING STRIP 50 mmX3 mm<br />
Earthing arrangement using outdoor grounding<br />
Bus bar and indoor grounding bus bar<br />
GROUNDING WIRE<br />
UTL/RTT/02-01 OCT 2011 Page 28 <strong>of</strong> 31<br />
BTS<br />
SMPS