Setting the MM420 Parameters with the BOP

If the PROFIBUS

address was set from the

hardware side,

P0918 can only display

Parameter number Value

P0003 2

P0700 6

P0918

9

P1000

2

P1120

2.00

P1121

2.00

Comment

Expanded parameter access

Control signals from PROFIBUS

PROFIBUS address of the MM420

Frequency setpoint from Potentiometer

Ramp-up time 2 seconds

Ramp-down time 2 seconds

Setpoint before ramp-function generator:

Setpoint after ramp-function generator:

50 Hz

Setpoint frequency

50 Hz

Setpoint frequency

Internally generated

ramp-function

t

P1120

P1121

t