Assembly - panel wiring<br />

3<br />

To mo<strong>to</strong>rs,<br />

other loads, etc.<br />

Organization<br />

of cable entries<br />

Group the cables by type<br />

of current:<br />

> high power: power<br />

supply, PEN conduc<strong>to</strong>rs,<br />

etc., actua<strong>to</strong>rs;<br />

> low power (< 100 mA):<br />

analogue communication.<br />

Create specific entries in<br />

the panel, one for each<br />

type of current.<br />

Communication<br />

cables<br />

Power<br />

4<br />

Separating partition<br />

LOW level<br />

Actua<strong>to</strong>rs Sensors<br />

Probes<br />

Detec<strong>to</strong>rs<br />

Shielded cable entries<br />

The use of metal cable glands tightened <strong>to</strong> 360°<br />

ideally <strong>protect</strong>s EMC. The cable shielding is<br />

connected <strong>to</strong> the panel's frame earth over its<br />

entire perimeter without being interrupted.<br />

It extends over the cable's entire internal route<br />

up <strong>to</strong> the terminal block, the filter or the variable<br />

speed drive where it is again connected <strong>to</strong><br />

frame earth.<br />

The earthing gaskets clamping the shielding<br />

at the point of entry are an alternative solution<br />

<strong>to</strong> cable glands.<br />

15