Assembly - panel wiring<br />
5<br />
1<br />
6<br />
Earth connection of shielding<br />
Connection of shielding<br />
terminations<br />
The shieldings are s<strong>to</strong>pped as close as possible<br />
<strong>to</strong> the equipment <strong>to</strong> which the cables are connected.<br />
Connection is performed carefully, clamping<br />
the shielding with a clamp which will be:<br />
> fastened <strong>to</strong> an earth terminal strip or<br />
> fastened <strong>to</strong> the panel's earthing plate.<br />
2<br />
Connection of cables<br />
"on standby"<br />
Wires not connected <strong>to</strong> a potential difference constitute antennas collecting<br />
and radiating high-frequency disturbance. This phenomenon can be cancelled<br />
by connecting them <strong>to</strong> the closest frame earth.<br />
Earth connection of metal raceways<br />
The raceway is bolted<br />
on<strong>to</strong> the wall<br />
17