GLYCOL COOLED: Performance data at OPTIONAL airfl ow<br />
MODEL NUMBER DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-<strong>30</strong><br />
ELECTRICAL SECTION Next size motor<br />
Electrical data based on STANDARD unit, electric reheat - YES, steam generator humidifi er - YES, and NEXT SIZE MOTOR.<br />
208-2<strong>30</strong>/3/60 FLA/MCA/MOP 69/83/90 78/90/100 92/105/110 101/115/125 116/139/150 125/149/150 151/171/200 164/199/225<br />
460/3/60 FLA/MCA/MOP 32/38/40 39/44/50 43/46/50 49/56/60 56/67/70 60/72/80 69/78/90 77/93/110<br />
575/3/60 FLA/MCA/MOP 25/<strong>30</strong>/35 28/32/35 34/39/40 38/43/50 43/52/60 45/54/60 59/66/80 64/77/90<br />
Electrical data based on, electric reheat - NO, steam generator humidifi er - YES, and NEXT SIZE MOTOR.<br />
208-2<strong>30</strong>/3/60 FLA/MCA/MOP 69/80/90 78/90/100 92/105/110 101/115/125 112/126/150 124/139/150 151/171/200 165/186/225<br />
460/3/60 FLA/MCA/MOP 32/38/40 39/44/50 43/49/50 49/56/60 57/65/70 46/52/60 69/78/90 79/89/110<br />
575/3/60 FLA/MCA/MOP 24/28/<strong>30</strong> 28/32/35 34/39/40 38/43/50 43/49/50 45/50/60 59/66/80 68/76/90<br />
Electrical data based on, electric reheat - YES, steam generator humidifi er - NO, and NEXT SIZE MOTOR.<br />
208-2<strong>30</strong>/3/60 FLA/MCA/MOP 69/83/90 74/89/90 85/101/110 90/106/110 116/139/150 125/149/150 134/162/175 164/199/225<br />
460/3/60 FLA/MCA/MOP 32/38/40 35/42/50 39/47/50 43/51/60 56/67/70 60/72/80 62/74/90 77/93/110<br />
575/3/60 FLA/MCA/MOP 25/<strong>30</strong>/35 27/32/35 31/37/40 33/39/45 43/52/60 45/54/60 51/62/70 64/77/90<br />
Electrical data based on, electric reheat - NO, steam generator humidifi er - NO, and NEXT SIZE MOTOR.<br />
208-2<strong>30</strong>/3/60 FLA/MCA/MOP 41/44/50 50/54/70 61/69/90 73/79/100 83/91/110 96/104/125 123/135/175 137/151/200<br />
460/3/60 FLA/MCA/MOP 19/20/25 26/28/35 <strong>30</strong>/33/40 37/40/50 44/49/60 50/54/70 56/62/80 66/73/100<br />
575/3/60 FLA/MCA/MOP 14/15/20 18/19/25 24/26/<strong>30</strong> 28/<strong>30</strong>/40 33/36/45 36/39/50 48/53/70 57/63/80<br />
FLA - Full load amps MCA - Minimum circuit amps (wire sizing amps) MOP - Maximum rating of the overcurrent protective device<br />
COMPRESSOR FLA - full load amps<br />
208-2<strong>30</strong>/3/60 13.1 17.6 20.5 25.0 <strong>30</strong>.1 33.3 51.3 55.8<br />
460/3/60 6.1 9.6 9.6 12.8 16.7 17.9 23.1 26.9<br />
575/3/60 4.4 6.1 7.6 9.6 12.2 12.8 19.9 23.7<br />
OUTDOOR FLUID COOLER<br />
Standard selection at 95° F ambient at sea level<br />
Evaporator model DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-<strong>30</strong><br />
Fluid cooler model DAFC-11 DAFC-17 DAFC-17 DAFC-21 DAFC-24 DAFC-37 DAFC-40 DAFC-50<br />
Selection at 100° F ambient at sea level<br />
Evaporator model DAGD/U-06 DAGD/U-08 DAGD/U-10 DAGD/U-13 DAGD/U-16 DAGD/U-20 DAGD/U-26 DAGD/U-<strong>30</strong><br />
Fluid cooler model DAFC-17 DAFC-21 DAFC-21 DAFC-<strong>30</strong> DAFC-<strong>30</strong> DAFC-40 DAFC-50 DAFC-61<br />
(NOTE: Refer to pages 59 and 62 for electrical data on fl uid coolers.)<br />
* * * The following section has no reference to column headings * * *<br />
EVAPORATOR Fan motor FLA - full load amps<br />
Horsepower 1.0 1.5 2.0 3.0 5.0 7.5 10.0<br />
208-2<strong>30</strong>/3/60 3.6 4.8 6.2 9.0 14.6 23.0 29.0<br />
460/3/60 1.8 2.4 3.1 4.4 6.6 11.0 14.0<br />
575/3/60 1.4 2.0 2.5 3.3 5.3 8.6 10.0<br />
* Units with Energy Saver or Auxiliary Chilled <strong>Water</strong> Coils have different fi lter quantities as those listed in this section. Refer to dimensional data sheets.<br />
31 R-410A