ACTOM <strong>OUTDOOR</strong> <strong>DOGBOX</strong> CIRCUIT BREAKER TYPE GDX<br />
T echnical details<br />
The type GDX outdoor "Dog Box"<br />
At atmospheric pressure, the circuit<br />
circuit breaker is available in the<br />
breaker maintains sufficient dielec-<br />
following ratings:<br />
tric characteristics and ensures safe<br />
• 11 kV 2500 A 25 kA 95 kV BIL<br />
load switching.<br />
• 22 kV 1600 A 25 kA 150 kV BIL<br />
• 36 kV 1600 A 25 kA 200 kV BIL<br />
The rapid gas recombination and<br />
• Mild steel or 3CR12 option<br />
the injection of fresh gas into the<br />
• Protection relays, metering<br />
inter-electrode space ensures<br />
instruments; current and voltage<br />
perfect breaking at TRV values<br />
transformers can be housed in<br />
higher than those recommended by<br />
the cubicle<br />
the applicable IEC standard.<br />
• Circuit breakers and cubicles<br />
type tested to IEC 60056 at KEMA<br />
and by the SABS<br />
Easy installation<br />
• Developed and manufactured in The design of the separate pole<br />
the Republic of South Africa circuit breaker and the various<br />
• Used extensively by Eskom possible arrangements make for<br />
fast and easy adaptation to many<br />
Introduction<br />
configurations of open units or in<br />
The Areva ORTHOFLUOR SF6 FP<br />
circuit breaker is the ideal circuit<br />
prefabricated cubicles.<br />
breaker for outdoor dog box<br />
conductor and earth are determined<br />
applications.<br />
by the enclosure. The dielectric<br />
properties between phases depend<br />
ORTHOFLUOR circuit breakers are<br />
only on the pole spacing.<br />
of the separate pole type. The pole<br />
Fast reclosing<br />
The complete range of circuit<br />
breakers is fitted with the same<br />
operating mechanism. This device<br />
covers all the standardised cycles<br />
units are supported on a common<br />
rigid frame which also supports the<br />
operating mechanism.<br />
Endurance<br />
The very high endurance originates<br />
in the minimum wear of the SF6 gas<br />
viz: o - 0.3 sec. - CO - 15 sec. - CO fast<br />
cycle.<br />
The separate pole unit structure<br />
and of the contacts which are lightly<br />
enables the use of different frames<br />
stressed due to the low energy of<br />
and for different pole spacing. Each<br />
the arc; this is due to:<br />
pole unit consists of an interrupting<br />
• the intrinsic qualities of the SF6<br />
element housed in an epoxy resin<br />
gas,<br />
enclosure.<br />
• the limited arcing-time,<br />
• smaller arc length,<br />
The complete range is produced by<br />
•<br />
combining different frames,<br />
enclosures and interrupting ele-<br />
ments.<br />
•<br />
the instability of the arc roots<br />
thanks to the use of hollow<br />
tungsten alloy arcing contacts,<br />
full separation of arcing contacts<br />
and current carrying contacts<br />
The interrupting element determines<br />
the performance in respect Safety<br />
of:<br />
The circuit breakers operate under<br />
• interruption over a given voltage low pressure. The internal pressure<br />
range<br />
rise, due to the SF6 gas compres-<br />
• overcurrent withstand<br />
sion and heating due to switching,<br />
• rated current carrying capacity remains low.<br />
A safety membrane vents any<br />
The dielectric performance between excessive pressure that might arise,<br />
input and output and between however improbable.<br />
2
Capacitive switching Maintenance Standards<br />
The SF6 technique, particularly well Each pole is designed into a ORTHOFLUOR circuit breakers<br />
suited to capacitor bank switching gastight, sealed for life unit, which is meet the full requirements of all<br />
and protection and precludes any not to be opened during the service international standards such as UTE<br />
overvoltages on breaking which life of the breaker. Maintenance is C64100, VDE 0670, BS 5311, IEC 56.<br />
would jeopardise the durability of therefore limited to simple lubricathe<br />
capacitor bank. tion of the operating mechanism<br />
and to pole replacement on completion<br />
of their endurance limit.<br />
3