Technical information<br />
Technische Information<br />
Correcting Factors for Laying B<strong>und</strong>led Undergro<strong>und</strong><br />
Cables<br />
Laying conditions:<br />
1. Gro<strong>und</strong> temperature 20°C<br />
2. Thermal resistivity 1,0 К*m/W<br />
3. Space between cables or systems<br />
4. Cable laying form is triangle<br />
7 cm<br />
Load factor 0,7 (70% load)<br />
Lastfaktor 0,7 (70% Last)<br />
<strong>Kabel</strong> <strong>und</strong> <strong>Leiter</strong><br />
Insulation Cable type and nominal voltage Number of cables / cable systems<br />
Isolierung <strong>Kabel</strong>typ <strong>und</strong> Nennspannung Anzahl der <strong>Kabel</strong> / <strong>Kabel</strong>systeme<br />
XLPE Insulation/<br />
XLPE- Isolierung<br />
Load factor 1,0 (100% load)<br />
Lastfaktor 1,0 (100% Last)<br />
three-core cable 6-35 kV<br />
dreileiterkabel 6-35 kV<br />
single-core cable 6-35 kV<br />
einleiterkabel 6-35 kV<br />
2 4 6 8 10<br />
0,85 0,70 0,63 0,59 0,56<br />
0,85 0,70 0,63 0,59 0,56<br />
Insulation Cable type and nominal Voltage Number of cables / cable systems<br />
Isolierung <strong>Kabel</strong>typ <strong>und</strong> Nennspannung Anzahl der <strong>Kabel</strong> / <strong>Kabel</strong>systeme<br />
XLPE Insulation/<br />
XLPE- Isolierung<br />
three-core cable 6-10 kV/<br />
dreileiterkabel 6-10 kV<br />
single-core cable 6-35 kV/<br />
einleiterkabel 6-35 kV<br />
1 2 4 6 8 10<br />
0,83 0,67 0,53 0,47 0,44 0,41<br />
0,81 0,66 0,52 0,47 0,43 0,41<br />
Correction factors for ambient air temperatures other than 30 °C<br />
Korrekturfaktoren fuer Freilufttemperaturen ausser 30 °C<br />
Maximum conductor temperature °C Ambient air temperature °C<br />
Max. <strong>Leiter</strong>temperatur, °C Freilufttemperatur °C<br />
90<br />
20 25 35 40 45 50 55 60<br />
1,08 1,04 0,96 0,91 0,87 0,82 0,76 0,71<br />
Correction factors for ambient gro<strong>und</strong> temperatures other than 20 °C<br />
Korrekturfaktoren fuer Bodentemperaturen ausser 20 °C<br />
Maximum conductor temperature °C Ambient gro<strong>und</strong> temperature °C<br />
Max. <strong>Leiter</strong>temperatur, °C Bodentemperatur, °C<br />
90<br />
Korrekturfaktoren für Gr<strong>und</strong>verlegung von <strong>Kabel</strong>gruppen<br />
Verlegungsbedingungen:<br />
1. Bodentemperatur 20°С<br />
2. Wärmedurchgangswiderstand des Bodens 1,0 К*m/W<br />
3. <strong>Kabel</strong>abstand oder System<br />
4. Verlegungsform: Dreieck<br />
7 сm<br />
10 15 25 30 35 40 45 50<br />
1,07 1,04 0,96 0,93 0,89 0,85 0,8 0,76<br />
105