11.01.2013 Views

CEL | Feeder Pillars | Distribution Pillars - Charles Endirect Ltd

CEL | Feeder Pillars | Distribution Pillars - Charles Endirect Ltd

CEL | Feeder Pillars | Distribution Pillars - Charles Endirect Ltd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>CEL</strong> | <strong>Feeder</strong> <strong>Pillars</strong> | <strong>Distribution</strong> <strong>Pillars</strong><br />

www.charlesendirect.com


| 2 |<br />

INTRODUCTION<br />

The <strong>CEL</strong> range of feeder pillars has been tried and tested in an extensive variety of applications<br />

and conditions to prove their durability against the elements and the rigours of all urban and rural<br />

environments. <strong>CEL</strong> provides one of the most comprehensive ranges of feeder pillars, both shells<br />

and pre-wired with distribution equipment, in the UK market, with a range of sizes and options to<br />

suit a wide variety of applications.<br />

The range includes Mini pillars manufactured from 3mm mild steel to Maxi double door pillars<br />

manufactured from 5mm mild steel. <strong>Pillars</strong> are also manufactured in Grade 304 or 316 stainless<br />

steel and GRP. Standard finish is hot dipped galvanised to BSEN ISO 1461, but<br />

all pillars can be powder coated to RAL or BS colours with options of anti-graffiti<br />

and HA specifications.<br />

<strong>CEL</strong> are committed to providing excellent quality and service and have made a<br />

deliberate investment in finished stock to ensure the promptest delivery times.<br />

All products are designed, manufactured and inspected under stringent Quality<br />

Control Systems resulting in products and service levels which comply with, or<br />

exceed, the requirements of current legislation and regulations.<br />

COMPLIANCE<br />

OPERATING STANDARDS<br />

Quality Management System ISO 9001:2008<br />

3mm & 5mm Mild Steel HR4<br />

Stainless Steel CR304 & CR316<br />

Hot Dip Galvanising BSEN ISO 1461<br />

Pre-wired design, build and test BSEN 60439-1<br />

Electrical Installation BS7671 IEE Wiring Regs 17th Edition<br />

Welding BS4872<br />

Hazard Warning Labels BS5378<br />

MCB BS 60898<br />

Switch Fuse BSEN 60947-3<br />

Cables BS 6364


Mini Range FMP SMP RMP<br />

The advantages for you<br />

Manufactured for Quality:<br />

3 Constructed from 3mm steel plate hot dipped galvanised to<br />

BSEN ISO 1461<br />

3 Powder Coated finish also available – please specify colour<br />

3 12mm external grade plywood fully treated backboard<br />

Anti-Vandal Features:<br />

3 Fitted with tri-head locks<br />

3 Alternative locks available<br />

Ease of Installation:<br />

3 Detachable door<br />

3 Ground level clearly marked<br />

3 6mm brass earth stud on pillar and door with 500mm earth strap<br />

3 Hazard warning labels to BS5378<br />

FMP unique features<br />

3 Folded door with cut away side – improved access<br />

SMP unique features<br />

3 Flat fitting door – improved ingress protection<br />

RMP unique features<br />

3 Recessed door with integral door handle – easy to open<br />

3 Supplied complete with painted root<br />

3 8mm screw thread lock for added security<br />

3 Standard approved unit in Southern Ireland to ESB specification<br />

Optional Extras<br />

Description Order Code (add to ref)<br />

One louvre at the top and bottom of door LP<br />

Painted Root PR<br />

Powder Coat Paint Colour<br />

Security Hex Lock HEX<br />

Highways Agency Paint Finish G2<br />

EXTERNAL DIMENSIONS (mm) BACKBOARD<br />

WORKING<br />

DEPTH DOOR APERTURE WEIGHT<br />

Ref H W D R O/AH H W H W Kg<br />

FMP15 460 300 150 150 610 290 285 130 280 285 17<br />

FMP20 700 160 125 300 1000 600 145 105 570 150 14<br />

FMP30 700 160 150 300 1000 600 145 130 570 150 17<br />

FMP40 700 210 150 300 1000 600 200 130 570 195 20<br />

SMP30 700 160 150 300 1000 600 150 150 580 142 16<br />

SMP40 700 210 150 300 1000 600 200 200 580 192 19<br />

SMP50 700 210 210 300 1000 600 200 200 580 192 23<br />

SMP60 950 360 150 300 1250 800 350 350 780 342 33<br />

RMP30 680 285 160 320 1000 550 235 118 550 222 28<br />

RMP40 673 400 225 360 1033 545 335 183 545 335 40<br />

|3 |


Midi Range BDP<br />

The advantages for you<br />

Manufactured for Quality:<br />

3 Constructed from 3mm steel plate hot dipped galvanised to<br />

BSEN ISO 1461<br />

3 Powder coated finish also available – please specify colour<br />

3 12mm external grade plywood fully treated backboard<br />

3 Fitted with cast stainless steel block hinges<br />

3 Hinged door with IP55 seal for improved ingress protection<br />

Anti-Vandal Features:<br />

3 Recessed Door<br />

3 Fitted with twin tri-head locks<br />

3 Alternative locks available<br />

BDP unique features<br />

3 Detachable root<br />

3 Heritage option available<br />

BDP03 unique features<br />

3 To DRD NI Specification<br />

3 Painted green<br />

BDP<br />

3 Fitted with CLL anti-vandal locks<br />

3 Fitted with hasp & staple for added security<br />

3 Enclosed root section with removable front plate for easy access<br />

3 Document holder fitted<br />

BDP/FP2 unique features<br />

3 Fitted with hasp & staple for added security<br />

3 Fitted with CLL anti-vandal locks as standard<br />

3 Louvres fitted on both sides for ventilation<br />

Optional Extras<br />

| 4 |<br />

Description Order Code (add to ref)<br />

One louvre at the top and bottom of door LP<br />

Anti-vandal locks CLL<br />

Yale Lock Yale<br />

Hasp & Staple HS<br />

Powder Coat Paint Colour<br />

Highways Agency Paint Finish G2<br />

Ease of Installation:<br />

3 Ground level clearly marked<br />

3 Painted root as standard<br />

3 6mm brass earth stud on pillar and door with 500mm earth strap<br />

3 Will accept <strong>CEL</strong> stainless steel distribution boards<br />

3 Hazard warning labels to BS5378<br />

<strong>CEL</strong> cast stainless steel hinge as<br />

fitted in BDP and CFP ranges<br />

EXTERNAL DIMENSIONS (mm) BACKBOARD<br />

WORKING<br />

DEPTH DOOR APERTURE WEIGHT<br />

Ref H W D R O/AH H W H W Kg<br />

BDP50 750 250 150 300 1050 650 230 130 550 144 24<br />

BDP60 850 350 225 300 1150 750 330 205 650 244 26<br />

BDP70 950 450 250 300 1250 850 430 230 750 344 47<br />

BDP80 1050 550 275 300 1350 950 530 255 850 444 60<br />

BDP90 1150 650 300 300 1450 1050 630 280 950 544 75<br />

BDP100 1250 800 325 300 1550 1150 780 305 1050 694 102<br />

BDP03 770 700 210 250 1020 685 685 190 600 594 61<br />

FP2 710 450 250 300 1010 590 430 230 490 345 45<br />

BDP03<br />

FP2


Maxi Range CFP<br />

The advantages for you<br />

Manufactured for Quality:<br />

3 Constructed from 3mm steel plate hot dipped galvanised to<br />

BSEN ISO 1461<br />

3 Powder coated finish also available – please specify colour<br />

3 Hinged door(s) with IP55 seal for improved ingress protection<br />

3 18mm external grade plywood fully treated backboard<br />

3 Door stay locks door at 90° (5mm pillars)<br />

3 3mm pillars fitted with cast stainless steel block hinges<br />

3 5mm pillars fitted with cast stainless steel hinges with integral<br />

door stay<br />

Anti-Vandal Features:<br />

3 Fitted with anti-vandal locks<br />

3 3mm pillars have recessed door(s)<br />

Optional Extras<br />

Description Order Code (add to ref)<br />

Louvre panel with three slats on each side LP<br />

Yale Lock Yale<br />

Hasp & Staple HS<br />

Powder Coat Paint Colour<br />

Highways Agency Paint Finish G2<br />

Ease of Installation:<br />

3 Detachable painted root as standard<br />

3 6mm brass earth stud on pillar and door(s) with 500mm<br />

earth strap<br />

3 Will accept <strong>CEL</strong> stainless steel distribution boards<br />

3 Complete with lifting eyes<br />

3 Hazard warning labels to BS5378<br />

EXTERNAL DIMENSIONS (mm) BACKBOARD<br />

WORKING<br />

DEPTH DOOR APERTURE WEIGHT<br />

Ref H W D R O/AH H W H W Kg<br />

3mm SINGLE DOOR MAXI<br />

CFP320 1350 800 350 400 1750 1170 780 300 1050 695 87<br />

3mm DOUBLE DOOR MAXI<br />

CFP350 1350 1200 450 400 1750 1170 1180 400 1050 1095 165<br />

5mm SINGLE DOOR MAXI*<br />

CFP510 1350 600 450 400 1750 1170 580 410 1050 520 144<br />

CFP520 1350 800 450 400 1750 1170 780 410 1050 720 158<br />

CFP540 1350 1000 450 400 1750 1170 980 410 1050 920 207<br />

5mm DOUBLE DOOR MAXI*<br />

CFP550 1350 1200 450 400 1750 1170 1180 410 1050 1120 226<br />

CFP572 1600 1500 450 400 2000 1420 1480 410 1300 1420 320<br />

CFP580 1600 2000 450 400 2000 1420 1980 410 1300 1920 405<br />

CFP590 1600 2500 450 400 2000 1420 2480 410 1300 2420 436<br />

*5mm CFP Pillar Stainless Steel Hinge<br />

3 Precision cast stainless steel hinge assembly with integral door stay feature<br />

3 Locks door at 90 degrees<br />

3 The hinge is robustly constructed using a structural geometry that optimises stiffness<br />

3 Stay locking is simple, reliable and elminates risk from ‘wind slamming’ doors<br />

<strong>CEL</strong> stainless steel hinge and<br />

door stay as fitted to 5mm CFP<br />

pillars.<br />

| 5 |


Stainless Steel <strong>Feeder</strong> <strong>Pillars</strong><br />

With a design life of some 50 years the <strong>CEL</strong> range of Stainless Steel<br />

<strong>Feeder</strong> <strong>Pillars</strong> offer the ultimate fit and forget durability and long<br />

service. Available empty or pre-wired across the range, the BDP<br />

series will accept <strong>CEL</strong>’s range of stainless steel distribution boards.<br />

The advantages for you<br />

Manufactured for Quality:<br />

3 Constructed from 3mm Grade 304 stainless steel<br />

3 Powder coated finish also available – please specify colour<br />

3 12mm external grade plywood fully treated backboard<br />

Anti-Vandal Features:<br />

3 Fitted with twin tri-head locks – Anti-vandal locks available<br />

Ease of Installation:<br />

3 Ground level clearly marked<br />

3 6mm brass earth stud on pillar and door with 500mm<br />

earth strap<br />

3 Hazard warning labels to BS5378<br />

FMP/S unique features<br />

3 Folded door with cutaway side - improved access<br />

SMP/S unique features<br />

3 Flat fitting door - improved ingress protection<br />

BDP/S unique features<br />

3 Hinged door with IP55 seal for improved ingress protection<br />

3 Fitted with cast stainless steel block hinges<br />

3 Will accept <strong>CEL</strong> stainless steel distribution boards<br />

EXTERNAL DIMENSIONS (mm) BACKBOARD<br />

WORKING<br />

DEPTH DOOR APERTURE WEIGHT<br />

Ref H W D R O/AH H W H W Kg<br />

FMP30/S 700 160 150 300 1000 570 145 130 570 145 17<br />

FMP40/S 700 210 150 300 1000 570 195 130 570 195 20<br />

SMP30/S 700 160 150 300 1000 600 150 130 570 145 16<br />

SMP40/S 700 210 150 300 1000 600 200 130 580 195 19<br />

BDP60/S 850 350 225 300 1150 750 330 205 650 245 36<br />

BDP70/S 950 450 250 300 1250 850 430 230 750 345 47<br />

BDP80/S 1050 550 275 300 1350 950 530 245 850 445 60<br />

BDP90/S 1150 650 300 300 1450 1050 630 280 950 545 75<br />

Bespoke Stainless Steel <strong>Feeder</strong> <strong>Pillars</strong><br />

In addition to holding stocks of the standard range of stainless<br />

steel pillars, <strong>CEL</strong> design and build bespoke stainless steel pillars<br />

to meet specific requirements including grade 316.<br />

| 6 |


City Range Of Specialised Architectural <strong>Feeder</strong> <strong>Pillars</strong><br />

A selection of pillars manufactured in either stainless steel or galvanised steel for temporary<br />

supply applications. This range offers solutions combining performance, quality and style.<br />

Standard <strong>CEL</strong> Market Trader advantages for you<br />

3 Manufactured for Quality<br />

3 Anti-Vandal Features<br />

3 Ease of Installation<br />

The Smithfield<br />

Unique Features<br />

3 Constructed from 3mm steel plate<br />

3 Standard finish to BSEN ISO 1461 hot dipped galvanised<br />

3 Available in stainless steel<br />

3 Double doors which can be independently locked<br />

3 Can be supplied empty or pre-wired with up to 6 230V sockets,<br />

RCBO protected or to customer’s specifications<br />

3 Space for DNO supply<br />

The Dome<br />

Unique Features<br />

3 Constructed from Grade 304 stainless steel<br />

3 Double doors which can be independently locked<br />

3 Pre-wired with up to six 230V sockets, RCBO protected<br />

3 Sockets mounted in powder coated stainless steel<br />

modular panel (removable for maintenance)<br />

3 Space for DNO supply<br />

3 Flange mounting or root options available<br />

The Tower<br />

(Suitable for private supply only)<br />

Unique Features<br />

3 Constructed from Grade 304 stainless steel<br />

3 Pre-wired with up to four 230V sockets, RCBO<br />

protected<br />

3 Sockets mounted in brushed stainless steel<br />

modular panel<br />

3 Flange mounting or root options available<br />

The Barbican<br />

Unique Features<br />

3 Constructed from 3mm steel plate<br />

3 Standard finish to BSEN ISO 1461 hot dipped<br />

galvanised<br />

3 Available in stainless steel<br />

3 Double doors which can be independently locked<br />

3 Can be supplied empty or pre-wired with up to 4<br />

230V sockets, RCBO protected<br />

3 Space for DNO supply<br />

EXTERNAL DIMENSIONS (mm) BACKBOARD<br />

WORKING<br />

DEPTH DOOR APERTURE<br />

Ref H W D R O/AH H W H W<br />

Smithfield BDP/MT 1270 800 325 300 1570 1150 780 275 500<br />

500<br />

Dome DMT400 1250 Dia 406 300 1550<br />

N/A 540<br />

Lower 450 x 250<br />

450<br />

Tower TMT300 1000 Dia 273 300 1300 N/A N/A 780 260<br />

Barbican GEM1000 1056 376 326 300 1356 598<br />

350<br />

250<br />

250<br />

276 500<br />

250<br />

695<br />

695<br />

260<br />

260<br />

268<br />

268<br />

| 7 |


Specialist <strong>Feeder</strong> <strong>Pillars</strong><br />

<strong>CEL</strong> have built their success on listening to customers, and have designed pillars to suit specific<br />

applications.<br />

Folding Pillar (FFP)<br />

Folding supply pillar providing unobtrusive temporary power supplies (two RCBO protected sockets)<br />

which only operate in the vertical position offering safe operation in open spaces. When not in use<br />

the pillar folds away discreetly.<br />

3 Strong design to withstand foot and vehicle traffic<br />

3 Options of manufacture in galvanised steel or stainless steel<br />

3 Pillar is raised, locked upright and opening covered in one smooth operation<br />

3 Easy to raise and lower, due to maintenance free gas strut - max 20 kilo lift<br />

3 All electrical parts sealed to IP67<br />

3 Pillar is isolated in closed (lowered) position<br />

3 Maximum 300mm planting depth to avoid underground services<br />

3 Trough for surface dressing allows matching of surrounding area<br />

Fibre Glass Range (GRP)<br />

3 Single (GRP320) and Double Door (GRP350) versions<br />

3 GRP composite to provide max ‘U’ value of 3.0W/m2 Deg C (thermal insulation)<br />

3 30 minute fire resistance to BS476 Part 22<br />

3 Self-extinguishing laminate to BS476 Part 7 Class 2<br />

3 Designed Ingress Protection IP54<br />

3 2No internal stainless steel, bonded in, hinges per door<br />

3 2No tri-head locks fitted as standard - other lock options available<br />

3 Fitted with 10mm external grade and treated ply backboard<br />

3 Standard external finish smooth gel-coat colour green or grey<br />

(other RAL or BS colour options available)<br />

3 Base flange for fixing to prepared concrete base (we strongly recommend a<br />

‘stepped’ base to ensure integrity of weatherproof seal)<br />

EXTERNAL DIMENSIONS (mm) BACKBOARD<br />

WORKING<br />

DEPTH DOOR APERTURE<br />

Ref H W D H W H W<br />

GRP320 1290 775 400 740 915 350 960 640<br />

GRP350 1290 1420 400 1350 915 350 960 1230<br />

Heritage <strong>Pillars</strong><br />

Any pillar from the BDP and CFP range can be manufactured in the Heritage style, providing a classic<br />

design for town centre situations. <strong>Pillars</strong> painted black with gold filigree as standard, but other options<br />

are available.<br />

Example Ref: BDP60 in Heritage style = BDP60 Heritage Pillar.<br />

| 8 |


<strong>Feeder</strong> Pillar Accessories<br />

Alternative locks and accessories are available for most pillars in our range:<br />

Anti-Vandal Locks:<br />

CLL Lock complete with anti-vandal cap<br />

CLL Key<br />

Manufactured from precision die cast components<br />

Lock insert precision CNC machined using 316 stainless steel<br />

Can be fitted to BDP pillars as an optional extra<br />

Yale Lock Can be fitted to Midi and Maxi pillars for added security<br />

Yale Padlock Can be fitted to Midi and Maxi pillars for added security<br />

Crown Locks Can be fitted to Mini and Midi pillars as an optional extra<br />

Hex Locks in place of standard tri-head lock<br />

Keys:<br />

Tri-head Key<br />

Hex Head Key<br />

CLL Key<br />

Hasp & Staple Can be fitted to Midi and Maxi pillars for added security to allow fitment of padlock<br />

Endure Range of Stainless Steel <strong>Distribution</strong> Boards<br />

Manufactured from high quality stainless steel – corrosion proof and impact resistant.<br />

The advantages for you<br />

3 Manufactured from high quality brushed stainless steel<br />

3 Designed for use in harsh environments<br />

3 Available in 8, 12 or 18 module widths<br />

3 Designed to maximum cabling space<br />

3 Tested to IP44<br />

3 Fitted with tri-head lock<br />

3 Brass removable gland plate<br />

3 Ideal for use in pre-wired distribution pillars<br />

Dimensions (mm):<br />

Ref Height Width Depth<br />

SSDB-08 360 180 145<br />

SSDB-12 360 250 145<br />

SSDB-18 366 360 145<br />

Door depth = 37.5<br />

C-Lock AV body fitted with<br />

stainless steel insert<br />

C-Lock cap<br />

C-Lock key<br />

| 9 |


<strong>Distribution</strong> <strong>Feeder</strong> <strong>Pillars</strong> to BSEN 60439-1<br />

<strong>CEL</strong> pride themselves on the manufacture of quality, safe products which are fit for purpose, and as part of this<br />

commitment have a dedicated in-house team to design, build and test pre-wired distribution equipment to BSEN<br />

60439-1, Low Voltage Switchgear and Controlgear Assemblies. The pre-wiring of <strong>CEL</strong> distribution pillars ensures that<br />

on-site installation time by the contractor is kept to the absolute minimum.<br />

It is the responsibility of this team to work very closely both with our own Sales Managers and the end customer, to<br />

ensure that the final product will meet both the customer’s requirement and be successfully tested and certified to<br />

BSEN 60439-1. Hence:<br />

3 Design works together with Fabrication and Assembly<br />

3 Clear design ensures compliance with standards<br />

3 Construction must comply with the design<br />

3 Ensures best assembly methods are used<br />

3 Manufactured to ISO standards<br />

The advantages for you<br />

3 Free technical support and design service<br />

3 Certification to BSEN 60439 -1 (peace of mind)<br />

3 Range of single phase and three phase standard types<br />

3 Project specific bespoke solutions<br />

3 Parametric 3D modelling and AutoCAD software<br />

3 Range of stainless steel distribution boards<br />

3 Variety of control and protection options available<br />

3 Experience in designing with variety of OEM equipment, i.e. MEM, Hager<br />

3 O&M manual issued<br />

3 Light, heater, thermostat and 13A RCCB socket can be factory fitted<br />

Electrical Standards of Components<br />

Fuse switch disconnectors BS EN 60947-3:1999<br />

Switch disconnectors BS EN 60947-3:1999<br />

<strong>Distribution</strong> boards BS EN 60439-3:1991<br />

Fuse holders BS88-2.2:1988<br />

Fuse links BS88-2.2:1988<br />

Miniature circuit breakers BS EN 60898 or BS EN 60947-2:2003<br />

Contactors BS EN 60947-4-1:2001<br />

RCCBs BS EN 61008-1:1995<br />

RCBOs BS EN 61009-1:1995<br />

Operation & Maintenance Manual<br />

All pre-wired distribution equipment is supplied with an O&M manual, which consists of:<br />

Test certificate to BSEN 60439-1<br />

Instructions including information concerning:<br />

Installation<br />

Connection<br />

Electrical specification<br />

Incoming fuse data<br />

Earthing system<br />

Service condition<br />

| 10 |


<strong>Distribution</strong> <strong>Feeder</strong> <strong>Pillars</strong> Typical Designs<br />

<strong>CEL</strong> are able to design pre-wired equipment using a selection of OEM<br />

equipment, dependent on client preference and/or suitability for application –<br />

here are some typical designs using different equipment.<br />

M11 Junction 11 Pre-wired Lighting Supply Pillar<br />

Unique Product Reference: PQ4026<br />

CFP350 <strong>Feeder</strong> Pillar fitted with modular polycarbonate IP65 enclosures<br />

SP& N <strong>Distribution</strong> panel with 14 BS88 fuseways<br />

Incoming Supply Connection: DNO=< 100A<br />

Operating Voltage Uo: 230V AC<br />

Design Current Ib: 100A<br />

Greenwich Peninsula Riverside South Supply Pillar<br />

Unique Product Reference PQ2809/FP13<br />

SP355 Bespoke Pillar fitted with Hager Equipment<br />

Panel board 8 TP&N Way with 100A 4P switch and<br />

protection devices<br />

Incoming Supply Connection: DNO=< 100A<br />

Operating Voltage Uo: 400V AC<br />

Design Current Ib: 100A<br />

West Derry Road A287 Crossing<br />

Unique Product Reference: PQ3063<br />

BDP60 <strong>Feeder</strong> Pillar fitted with <strong>CEL</strong> 12 way s/steel dist board<br />

Pre-wired with double insulated tails<br />

DNO supply<br />

Operating Voltage Uo: 230V AC<br />

Design Current Ib: 100A<br />

High Heavens Recycling Centre, High Wycombe<br />

Unique Product Reference: PQ4019<br />

CFP590 <strong>Feeder</strong> Pillar fitted with MEM equipment<br />

TP&N Fuse Switch Disconnector<br />

2 x TP&N <strong>Distribution</strong> Boards<br />

95A AC3 3P Group Switch Contactor<br />

Incoming Supply Connection: 120/4C XLPE/PVC/SWA<br />

Operating Voltage Uo: 400V AC 50 Hz<br />

Design Current Ib: 125A<br />

| 11 |


Standard <strong>Distribution</strong> <strong>Feeder</strong> <strong>Pillars</strong><br />

<strong>CEL</strong> have developed a range of single and three phase standard <strong>Distribution</strong> <strong>Pillars</strong> – these designs have proved to meet the<br />

requirements of a number of applications in the street lighting industry.<br />

Single Phase <strong>Distribution</strong> <strong>Pillars</strong><br />

| 12 |<br />

Product Code <strong>Feeder</strong> Pillar<br />

Standard SP&N pre-wired supply feeder pillars - 2 to 12 outgoing BS88 fuse ways<br />

External<br />

dimensions<br />

H x W x D (mm)<br />

All have 300mm<br />

planted root<br />

Outgoing<br />

Ways<br />

Protection devices<br />

Maximum cable<br />

terminations<br />

(mm 2 )<br />

Available gland<br />

plate space X/Y<br />

(mm)<br />

<strong>CEL</strong>/TYPE/R602 BDP70 950 x 450 x 250 2 Fuses BS88 =< 32A 16/3C - 25/2C 110 x 70<br />

<strong>CEL</strong>/TYPE/R604 BDP80 1050 x 550 x 275 4 Fuses BS88 =< 32A 16/3C - 25/2C 180 x 70<br />

<strong>CEL</strong>/TYPE/R606 BDP80 1050 x 550 x 275 6 Fuses BS88 =< 32A 16/3C - 25/2C 180 x 70<br />

<strong>CEL</strong>/TYPE/R608 BDP80 1050 x 550 x 275 8 Fuses BS88 =< 32A 16/3C - 25/2C 180 x 70<br />

<strong>CEL</strong>/TYPE/R610 BDP90 1150 x 650 x 300 10 Fuses BS88 =< 32A 16/3C - 25/2C 270 x 70<br />

<strong>CEL</strong>/TYPE/R612<br />

Common Features<br />

BDP90 1150 x 650 x 300 12 Fuses BS88 =< 32A 16/3C - 25/2C 270 x 70<br />

Incoming supply Uo 230V AC 50Hz<br />

Design current Ib 100A<br />

Space for DNO cut-out & meter SP&N =< 100A Yes<br />

Pre-wired tails L/N 25mm2 Main earth CPC E 16mm2 Fully earth bonded Yes<br />

<strong>Distribution</strong> panel <strong>Charles</strong> <strong>Endirect</strong> SSDB range in stainless steel<br />

Main switch 100A 2P switch disconnector<br />

Outgoing circuits 24 hour supplies (not group switched)<br />

Wiring standard BS 7671<br />

Test and certified BSEN 60439-1<br />

O&M pack with test certificate Supplied in plastic document holder fitted within the pillar<br />

Alternative incoming supply connection Private cable = < 25mm2 2 or 3 core SWA (by others)<br />

Option kit Thermostat and compact 60 watt heater (sub assembly item SA/66)


Standard <strong>Distribution</strong> <strong>Feeder</strong> <strong>Pillars</strong><br />

Three Phase <strong>Distribution</strong> <strong>Pillars</strong><br />

Product Code <strong>Feeder</strong> Pillar<br />

Standard TP&N pre-wired supply feeder pillars - 6 to 8 outgoing BS88 fuse ways<br />

External<br />

dimensions<br />

H x W x D (mm)<br />

All have 300mm<br />

planted root<br />

Outgoing<br />

Ways<br />

Protection devices<br />

Maximum cable<br />

terminations (mm 2 )<br />

<strong>CEL</strong>/TYPE/R600GS CFP572 1600 x 1500 x 450 6 Fuses BS88 =< 32A 35/4C<br />

<strong>CEL</strong>/TYPE/R60024 CFP572 1600 x 1500 x 450 6 Fuses BS88 =< 32A 35/4C<br />

<strong>CEL</strong>/TYPE/R800GS CFP572 1600 x 1500 x 450 8 Fuses BS88 =< 32A 35/4C<br />

<strong>CEL</strong>/TYPE/R80024 CFP572 1600 x 1500 x 450 8 Fuses BS88 =< 32A 35/4C<br />

Common Features<br />

Incoming supply Uo 400V AC 3PH 50Hz<br />

Design current Ib 100A<br />

Space for DNO cut-out & meter SP&N =< 100A Yes<br />

Pre-wired tails L/N 25mm2 Main earth CPC E 16mm2 Fully earth bonded Yes<br />

<strong>Distribution</strong> panel Industrial grade metal clad<br />

Main switch 100A 2P switch disconnector<br />

Outgoing circuits 24 = 24 hour supplies GS = Group Switched<br />

Wiring standard BS 7671<br />

Test and certified BSEN 60439-1<br />

O&M pack with test certificate Supplied in plastic document holder fitted within the pillar<br />

Alternative incoming supply connection Private cable = < 25mm2 2 or 3 core SWA (by others)<br />

Option kit Thermostat and compact 60 watt heater (sub assembly item SA/66)<br />

| 13 |


Project Specific Bespoke Solutions<br />

<strong>CEL</strong> also offer a design service, working with the client from the conception of a project to<br />

delivery.<br />

Everybody in the Supply Chain has a responsibility to ensure that the product is safe, from the<br />

specifier, to <strong>CEL</strong> as the manufacturer, to the installer.<br />

All <strong>CEL</strong> distribution equipment is designed, manufactured and tested to BSEN 60439-1. A<br />

design is prepared under instruction from the Specifier who receives a CAD drawing giving<br />

details of layout, together with a unique reference which can be used in the<br />

specification documentation.<br />

When a project comes to construction phase, Design and Assembly work closely together to<br />

ensure build complies with the design. Quality systems under ISO 9001:2008 are followed<br />

throughout the manufacture.<br />

On completion, all distribution equipment is tested using calibrated instruments, with the<br />

results being recorded. All assemblies are inspected both mechanically and electrically.<br />

Electrical continuity of the protective circuits is checked.<br />

A Certificate of Type Test is produced and included in the O&M Manual supplied with the<br />

product.<br />

To provide full traceability, all completed distribution<br />

pillars are supplied complete with a name plate<br />

affixed showing:<br />

3 Identity number<br />

3 Standard<br />

3 Rated Operational Voltage Ue<br />

3 Rated Insulation Voltage Ui<br />

3 Degree of Protection<br />

3 Date of Manufacture<br />

|14 |


Case Study<br />

Riverside Resource Recovery Facility<br />

Location: South Bank of River Thames, Belvedere<br />

The RRR Facility is an energy recovery plant planned as an alternative to a<br />

landfill site. The facility is a river-served recovery plant with waste delivered<br />

by barges and tugs. The plant generates its own power and exports power to<br />

the National Grid.<br />

Specification: A bespoke feeder pillar, with a footprint of<br />

2800mm x 900mm, consisting of two standard feeder cubicles in a ‘back to<br />

back’ arrangement to service the following:<br />

General Power<br />

Sub Mains Circuit<br />

Low voltage 110V centre tapped earth socket outlets/connection units<br />

General area lighting and floodlighting<br />

Jetty Navigational Lighting and Emergency Lighting<br />

The pillar was to be sited on a jetty. Therefore it was recommended that<br />

it be fabricated in 5mm 316 grade stainless steel to suit the marine<br />

environment. Electrical distribution panels to be in modular polycarbonate,<br />

IP65 enclosures, with the following general specification:<br />

Material: Thermoplastic<br />

Application Areas: Harsh Environments/Outdoor Use<br />

Ambient Conditions: -5o C to +40o C<br />

Insulation: Protection Class II<br />

Impact Strength: IK 08 (5 Joule) to DIN EN 50 102<br />

Ingress Protection: IP65 – Dust Proof & Water Jets<br />

Electrical Parameters: Rated Current 630A Insulation Voltage AC/DC 690<br />

Burning Behaviour: Glow Wire Test 960o C to IEC 60 695-2-1<br />

Temperature Resistance: -40°C up to +120°C<br />

UV Resistance: Direct Sun Radiation<br />

Chemical Resistance: Acid & Lye 10%, Petrol & Mineral Oil<br />

Toxic Behaviour: Silicon & Halogen Free<br />

Design: After much discussion between <strong>CEL</strong> Designer and Consultant, a<br />

design was agreed, a unique product reference, PQ2909, allocated and<br />

outline drawings prepared and submitted to the client. The job subsequently<br />

went out to tender and prices were submitted by contractors.<br />

Manufacture: Once the formal order was received, detailed circuit<br />

diagrams were prepared and submitted for approval. Several design<br />

changes occurred as the project progressed and once final design was<br />

approved, fabrication of the pillar and assembly of the electrical equipment<br />

began.<br />

Testing: Carried out to BSEN 60439-1. Because of the very special<br />

requirements for this project the customer sent a representative to witness<br />

the test.<br />

Delivery: Due to the nature of the site and the product, a specific delivery<br />

date and time was arranged.<br />

For further information please contact<br />

our Customer Services Team<br />

Riverside Resource Facility<br />

Product Ref: PQ2909<br />

| 15 |


<strong>Charles</strong> <strong>Endirect</strong> <strong>Ltd</strong> is a market<br />

leader in the street lighting industry.<br />

The company’s innovative product<br />

range includes:<br />

ISOLATORS & CUT-OUTS<br />

LSI Range<br />

Festive Lighting<br />

Helix Range<br />

Extension Boxes & Gland Plates<br />

FEEDER & DISTRIBUTION PILLARS<br />

Mini <strong>Pillars</strong><br />

Midi <strong>Pillars</strong><br />

Maxi <strong>Pillars</strong><br />

Stainless Steel <strong>Pillars</strong><br />

Specialised Architectural <strong>Pillars</strong><br />

Pre-wired <strong>Distribution</strong><br />

BELISHA EQUIPMENT<br />

Gallery<br />

Light Sources<br />

Globes<br />

Accessories<br />

ENERGY SAVING<br />

Power Switches<br />

Gear Trays<br />

Electronic Ballasts<br />

Control Gear<br />

Energy Management System<br />

LEDs<br />

EARTHING<br />

Cable Glands<br />

CETs<br />

Accessories<br />

MIS<strong>CEL</strong>LANEOUS<br />

Passive Safety<br />

Fuses<br />

Surge Protection<br />

Emergency Doors<br />

Strimmex<br />

4090<br />

T +44 (0)1963 828400<br />

F +44 (0)1963 828401<br />

E info@charlesendirect.com<br />

www.charlesendirect.com<br />

Wessex Way<br />

Wincanton Business Park<br />

Wincanton<br />

Somerset BA9 9RR<br />

<strong>Charles</strong> <strong>Endirect</strong> <strong>Ltd</strong> operates a policy of continuous product development and improvement.<br />

The facts and information offered in this document are correct at the time of going to press.<br />

©2010 <strong>Charles</strong> <strong>Endirect</strong> <strong>Ltd</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!