Case Study<br />

Riverside Resource Recovery Facility<br />

Location: South Bank of River Thames, Belvedere<br />

The RRR Facility is an energy recovery plant planned as an alternative to a<br />

landfill site. The facility is a river-served recovery plant with waste delivered<br />

by barges and tugs. The plant generates its own power and exports power to<br />

the National Grid.<br />

Specification: A bespoke feeder pillar, with a footprint of<br />

2800mm x 900mm, consisting of two standard feeder cubicles in a ‘back to<br />

back’ arrangement to service the following:<br />

General Power<br />

Sub Mains Circuit<br />

Low voltage 110V centre tapped earth socket outlets/connection units<br />

General area lighting and floodlighting<br />

Jetty Navigational Lighting and Emergency Lighting<br />

The pillar was to be sited on a jetty. Therefore it was recommended that<br />

it be fabricated in 5mm 316 grade stainless steel to suit the marine<br />

environment. Electrical distribution panels to be in modular polycarbonate,<br />

IP65 enclosures, with the following general specification:<br />

Material: Thermoplastic<br />

Application Areas: Harsh Environments/Outdoor Use<br />

Ambient Conditions: -5o C to +40o C<br />

Insulation: Protection Class II<br />

Impact Strength: IK 08 (5 Joule) to DIN EN 50 102<br />

Ingress Protection: IP65 – Dust Proof & Water Jets<br />

Electrical Parameters: Rated Current 630A Insulation Voltage AC/DC 690<br />

Burning Behaviour: Glow Wire Test 960o C to IEC 60 695-2-1<br />

Temperature Resistance: -40°C up to +120°C<br />

UV Resistance: Direct Sun Radiation<br />

Chemical Resistance: Acid & Lye 10%, Petrol & Mineral Oil<br />

Toxic Behaviour: Silicon & Halogen Free<br />

Design: After much discussion between <strong>CEL</strong> Designer and Consultant, a<br />

design was agreed, a unique product reference, PQ2909, allocated and<br />

outline drawings prepared and submitted to the client. The job subsequently<br />

went out to tender and prices were submitted by contractors.<br />

Manufacture: Once the formal order was received, detailed circuit<br />

diagrams were prepared and submitted for approval. Several design<br />

changes occurred as the project progressed and once final design was<br />

approved, fabrication of the pillar and assembly of the electrical equipment<br />

began.<br />

Testing: Carried out to BSEN 60439-1. Because of the very special<br />

requirements for this project the customer sent a representative to witness<br />

the test.<br />

Delivery: Due to the nature of the site and the product, a specific delivery<br />

date and time was arranged.<br />

For further information please contact<br />

our Customer Services Team<br />

Riverside Resource Facility<br />

Product Ref: PQ2909<br />

| 15 |