Oil Analysis<br />
Ref. Products Comments<br />
789 Viscosity at 40°C Measures kinematic viscosity.<br />
785 Acidity rate Measures the acidity of the lubricant.<br />
787 Element contents Identifies and quantifies the following elements : B-P-Zn-Fe-Cr-Si-Ba-<br />
Mg-Cu-Mo-Sn-Pb-Cd-Al-Ni-Ca-Sb-Ag-Na.<br />
786 Water content Measures the water content of the lubricant.<br />
788 Dielectric rigidity Measures the electrical isolation qualities of the lubricant.<br />
4962 Ferrography oil Identifies and quantifies the particles present in the lubricant.<br />
6083 Particle counting Determines the number of particles by size. Allows the correct size<br />
filter to be selected.<br />
6084 Infrared spectrum Identifies the nature of an unmixed lubricant.<br />
6548 Kit gravimetric pollution Measures the particle mass of the lubricant.<br />
880 Acitest Box of 6. Acidity test for all types of oils that do not contain additives<br />
(mineral, alkylbenzene, ester…).<br />
6096 Universal acitest Box of 6. Acidity test for all types of oils, whether or not they contain<br />
additives (mineral, alkylbenzene, ester…).<br />
• DPH : Periodic diagnostic test on the refrigerant oil in a circuit<br />
Periodic diagnostic test on the refrigerant oil in a circuit. The values obtained are compared with both standard<br />
values and Climalife recommendations.<br />
875 DPH A Appearance + viscosity + acid index + water content + elements<br />
indicating wear + additives + contaminants. 1 x 60 ml bottle.<br />
876 DPH B Idem DPH A + dielectric rigidity. 1 x 500 ml bottle.<br />
877 DPH E Used to determine the percentage of oil remaining after a retrofit.<br />
Physico-chemical state is compared with a control sample. 3 x 60 ml<br />
bottles.<br />
3978 DPH R After a DPH E, determines the percentage of the original oil remaining<br />
after the subsequent operations to change the oil. 1 x 60 ml bottle.<br />
6035 Kit for specific analysis 4 tests to analyse viscosity, water content, acidity and the presence<br />
of the 5 elements which indicate wear (Fe, Zn, Cu, Al, Si).<br />
6035<br />
875<br />
6096<br />
66<br />
ANALYSiS