Table 1 gives an overview of the different versions that were considered in the FMEDA’s and<br />

assessment of the Fisher Controls DVC6000 SIS Digital Valve Controller - DETT.<br />

Table 1 Version overview<br />

Application <strong>Safety</strong> Function<br />

1 4-20 mA Operation, Double-Acting (Relay<br />

A), De-Energize to Trip<br />

2 4-20 mA Operation, Single-Acting (Relay<br />

C), De-Energize to Trip<br />

3 4-20 mA Operation, Single-Acting (Relay<br />

A), De-Energize to Trip<br />

4 0-20 mA or 0-24 VDC Operation, Double-<br />

Acting (Relay A), De-Energize to Trip<br />

5 0-20 mA or 0-24 VDC Operation, Single-<br />

Acting (Relay C), De-Energize to Trip<br />

6 0-20 mA or 0-24 VDC Operation, Single-<br />

Acting (Relay A), De-Energize to Trip<br />

Output A ≤ Output B (with 4 mA input signal)<br />

Output A ≤ 1 psi (with 4 mA input signal)<br />

Output A ≤ 1 psi (with 4 mA input signal)<br />

Output A ≤ Output B (with < 1 mA input<br />

signal)<br />

Output A ≤ 1 psi (with < 1 mA input signal)<br />

Output A ≤ 1 psi (with < 1 mA input signal)<br />

For the 4 – 20 mA operating mode, the fail-safe state is defined as the input signal being 4 mA. The<br />

DVC6000 SIS Digital Valve Controller is classified as a Type B 1 device for these applications<br />

according to <strong>IEC</strong> <strong>61508</strong>, having a hardware fault tolerance of 0.<br />

For the 0 – 20 mA operating mode, the fail-safe state is defined as the input signal being < 1mA.<br />

This will ensure that the electronics are no longer capable of driving the I/P module. Therefore the<br />

DVC6000 SIS Digital Valve Controller is classified as a Type A 1 device for both applications<br />

according to <strong>IEC</strong> <strong>61508</strong>, having a hardware fault tolerance of 0.<br />

© exida Certification SA. EFC 07-07-41 R002 V1R2 <strong>IEC</strong> <strong>61508</strong><strong>Assessment</strong>.doc, March 13, 2008<br />

Iwan van Beurden Page 10 of 19