<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
cable/busway connections. Therefore, each vertical section of the switchboard is<br />
anchored to the floor. Some manufacturers provide formed base channels that<br />
run the entire length of the switchboard, mounting holes in the structure base, or<br />
both (see Figure 4).<br />
Anchor each section using the hardware recommended (but not usually supplied<br />
by) the switchboard manufacturer and torque the bolts to their recommended<br />
value.<br />
3.6.1 Seismic considerations<br />
Carefully follow the plans and specification when anchoring a switchboard for<br />
seismic conditions since the top of the switchboard structure can move as much<br />
as 3 inches (76 mm) in any direction.<br />
NOTE: Local building codes may have seismic requirements that affect<br />
switchboard installation. Installers should consult these codes or coordinate with<br />
the general contractor prior to installing switchboards.<br />
3.7 Installing Cables<br />
Install the incoming services conductors and load side cables after all<br />
switchboard sections are properly joined together and the entire switchboard<br />
structure is anchored to the floor. If the switchboard is in a seismic environment<br />
and cables or busway enter at the top of the switchboard, it is necessary to take<br />
into account the motion of the top of the switchboard during a seismic<br />
occurrence.<br />
NOTE: If the switchboard consists of only one shipping section, proceed to<br />
Section 3.10.<br />