TO: NECA 400-200X ANSI Canvass Participants FROM: Billie Zidek ...
TO: NECA 400-200X ANSI Canvass Participants FROM: Billie Zidek ...
TO: NECA 400-200X ANSI Canvass Participants FROM: Billie Zidek ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>TO</strong>: <strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> <strong>ANSI</strong> <strong>Canvass</strong> <strong>Participants</strong><br />
<strong>FROM</strong>: <strong>Billie</strong> <strong>Zidek</strong><br />
Director of Standards<br />
DATE: December 12, 2006<br />
RE: Revision of <strong>NECA</strong> <strong>400</strong>, Standard for Installing and Maintaining<br />
Switchboards, as an American National Standard<br />
As a result of comments received on the first ballot, the proposed standard has<br />
been revised. Section 6 has been completely rewritten for your review and<br />
comment.<br />
<strong>NECA</strong> <strong>400</strong>-200x reballot is attached for your review. Please note that the<br />
Foreword and Annexes are not a part of the proposed American National<br />
Standard.<br />
Also enclosed is a copy of the canvass list for this standard indicating the various<br />
interests represented and a comment response form.<br />
Action Request:<br />
After completing your review, please email or fax your <strong>ANSI</strong> canvass ballot to<br />
301-215-4500. We would appreciate receiving your response on or before<br />
Monday, January 29, 2007.<br />
NATIONAL ELECTRICAL CONTRAC<strong>TO</strong>RS ASSOCIATION<br />
3 Bethesda Metro Center, Suite 1100, Bethesda, MD 20814<br />
301-657-3110 x546 ℡; 301-215-4500 �; billie.zidek@necanet.org �
Date: March 30, 2006<br />
<strong>ANSI</strong> CANVASS REAFFIRMATION<br />
LETTER BALLOT<br />
Ballot Due Date: January 29, 2007<br />
<strong>TO</strong>PIC: Revision of <strong>NECA</strong> <strong>400</strong>-<strong>200X</strong>, Standard for Installing and<br />
Maintaining Switchboards, as an American National Standard.<br />
QUESTION: Should this standard, developed by the National Electrical<br />
Contractors Association (<strong>NECA</strong>), be approved as an American<br />
National Standard?<br />
_____ Yes No technical changes required.<br />
_____ Yes With Editorial Comments<br />
_____ No Technical changes required (see attached file).<br />
_____ Abstain If you find you cannot vote “yes” or “no” and<br />
want to be recorded as abstaining, please explain<br />
the reasons for your abstention on the reverse<br />
side.<br />
Signature: ___________________________________________<br />
Name: ___________________________________________<br />
Email Address:<br />
Organization<br />
______________________________________<br />
Represented: ______________________________________<br />
Phone No.: ______________________________________<br />
Fax No.: ______________________________________<br />
Date: ______________________________________<br />
Return to:<br />
<strong>Billie</strong> <strong>Zidek</strong><br />
Standards & Safety<br />
National Electrical Contractors Association<br />
3 Bethesda Metro Center, Suite 1100<br />
Bethesda, MD 20814<br />
301/215-4546 ℡<br />
301/215-4500 �<br />
billie.<strong>Zidek</strong>@necanet.org
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
13<br />
14<br />
15<br />
16<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
TABLE OF CONTENTS<br />
Foreword..........................................................................................................................ii<br />
1. Scope .......................................................................................................................1<br />
2. Switchboard Receiving, Handling and Storing ....................................................2<br />
3. Installation ...............................................................................................................5<br />
4. Pre-Energizing Checkout Procedure...................................................................15<br />
5. Energizing the Switchboard.................................................................................18<br />
6. Switchboard Maintenance ................................................................................19<br />
7. Adverse Circumstances .......................................................................................27<br />
8. Recommended Torque Values.............................................................................30<br />
9. Switchboard Insulation Resistance Chart ..........................................................32<br />
10. Operations and Maintenance Documents.......................................................33<br />
Appendix A: Reference Standards .............................................................................34<br />
i
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
25<br />
26<br />
27<br />
28<br />
29<br />
30<br />
31<br />
32<br />
33<br />
34<br />
35<br />
36<br />
37<br />
38<br />
39<br />
40<br />
41<br />
42<br />
43<br />
44<br />
45<br />
46<br />
47<br />
48<br />
49<br />
50<br />
51<br />
52<br />
53<br />
54<br />
55<br />
56<br />
57<br />
58<br />
59<br />
60<br />
61<br />
62<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
(This foreword is not part of the standard)<br />
Foreword<br />
National Electrical Installation Standards (NEIS ® ) are designed to improve<br />
communication among specifiers, purchasers, and suppliers of electrical<br />
construction services. They define a minimum baseline of quality and<br />
workmanship for installing electrical products and systems. NEIS are intended to<br />
be referenced in contract documents for electrical construction projects. The<br />
following language is recommended:<br />
Deadfront distribution switchboards rated 600 volts or less shall be<br />
installed and maintained in accordance with <strong>NECA</strong> <strong>400</strong>, Standard for<br />
Installing and Maintaining Switchboards.<br />
Use of NEIS is voluntary, and the National Electrical Contractors Association<br />
(<strong>NECA</strong>) assumes no obligation or liability to users of this publication. Existence<br />
of a standard shall not preclude any member or non-member of <strong>NECA</strong> from<br />
specifying or using alternate construction methods permitted by applicable<br />
regulations.<br />
This publication is intended to comply with the edition of the National Electrical<br />
Code (NEC) in effect at the time of publication. Because they are quality<br />
standards, NEIS may in some instances go beyond the minimum safety<br />
requirements of the NEC. It is the responsibility of users of this publication to<br />
comply with state and local electrical codes when installing electrical products<br />
and systems.<br />
Suggestions for revisions and improvements to this standard are welcome. They<br />
should be addressed to:<br />
<strong>NECA</strong> Standards & Safety<br />
3 Bethesda Metro Center, Suite 1100<br />
Bethesda, MD 20814<br />
(301) 657-3110 telephone<br />
(301) 215-4500 fax<br />
neis@necanet.org<br />
www.neca-neis.org<br />
To purchase NEIS, contact the <strong>NECA</strong> Order Desk at (301) 215-4504 tel, (301)<br />
215-4500 fax, or orderdesk@necanet.org. NEIS can also be purchased in .pdf<br />
download format at www.neca-neis.org/standards.<br />
Copyright © 200x, National Electrical Contractors Association. All rights reserved. Unauthorized<br />
reproduction prohibited.<br />
National Electrical Installation Standards and NEIS are trademarks of <strong>NECA</strong>, National Electrical<br />
Code and NEC are registered trademarks of the National Fire Protection Association.<br />
ii
63<br />
64<br />
65<br />
66<br />
67<br />
68<br />
69<br />
70<br />
71<br />
72<br />
73<br />
74<br />
75<br />
76<br />
77<br />
78<br />
79<br />
80<br />
81<br />
82<br />
83<br />
84<br />
85<br />
86<br />
87<br />
88<br />
89<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
1. Scope<br />
This standard describes installation procedures for deadfront distribution<br />
switchboards rated 600 volts or less.<br />
1.1 Products and Applications Included:<br />
It also covers periodic routine maintenance procedures for switchboards, and<br />
special procedures to be used after adverse circumstances such as a shortcircuit,<br />
ground-fault, or immersion in water.<br />
1.2 Regulatory and Other Requirements:<br />
a) All information in this publication is intended to conform to the National<br />
Electrical Code (<strong>ANSI</strong>/NFPA 70). Installers should always follow the NEC,<br />
applicable state and local codes, manufacturer’s instructions, and contract<br />
documents when installing switchboards.<br />
b) Only qualified persons familiar with the construction and installation of<br />
switchboards should perform the work described in this publication. It is<br />
recommended that all work be performed in accordance with NFPA 70E,<br />
Standard for Electrical Safety in the Workplace.<br />
c) General requirements for installing electrical products and systems are<br />
described in <strong>NECA</strong> 1, Standard Practices for Good Workmanship in<br />
Electrical Contracting (<strong>ANSI</strong>). Other NEIS provide additional guidance for<br />
installing particular types of electrical products and systems. A complete<br />
list of NEIS is provided in Annex A.<br />
1
90<br />
91<br />
92<br />
93<br />
94<br />
95<br />
96<br />
97<br />
98<br />
99<br />
100<br />
101<br />
102<br />
103<br />
104<br />
105<br />
106<br />
107<br />
108<br />
109<br />
110<br />
111<br />
112<br />
113<br />
114<br />
115<br />
116<br />
117<br />
118<br />
119<br />
120<br />
121<br />
122<br />
123<br />
124<br />
125<br />
126<br />
127<br />
128<br />
129<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
2. Switchboard Receiving, Handling and Storing<br />
2.1 Receiving the Switchboard<br />
a) Unload carefully, observing all packing label warnings.<br />
b) Use forklifts or other loading equipment only for palletized<br />
shipments.<br />
c) Leaving protective coverings in place as much as possible, open<br />
and inspect the switchboard completely for shipping damage.<br />
Undamaged material should be carefully repacked unless intended<br />
for immediate installation.<br />
NOTE: Depending on company policy or project circumstances, it may be<br />
necessary to receive, unpack and check all material at the company shop<br />
or other staging area, in which case, careful repacking is essential.<br />
2.2 Handling the Switchboard<br />
Switchboards are typically large, bulky pieces of equipment weighing several<br />
hundred pounds or more. The packing list will provide the actual weight of each<br />
item. Handle the switchboard properly in order to avoid injury to personnel and<br />
damage to equipment. Verify that the lifting capacity of the handling equipment<br />
is more than the shipping weight and type of truck making the delivery prior to<br />
receiving the shipment. Delivery on an open truck at the job-site is<br />
recommended.<br />
Suitable protection against the weather must be provided if the equipment is<br />
designed only for indoor installation (NEMA Type 1).<br />
There are two primary ways of lifting the equipment: with lifting straps and with<br />
lifting straps, using a sling instead. Using the manufacturer’s lifting straps is the<br />
preferable method when these are supplied.<br />
2.2.1 Handling with lifting straps<br />
Switchboard manufacturers provide lifting straps as standard equipment when<br />
the weight of the switchboard section(s) does not exceed the recommended<br />
capacity of the lifting straps. Use a rigid spreader or a spanner beam to provide<br />
vertical lift on the lifting straps (see Figure 1), and avoid damage to the frame or<br />
finish. Follow lifting warning labels on the switchboard.<br />
2
130<br />
131<br />
132<br />
133<br />
134<br />
135<br />
136<br />
137<br />
138<br />
139<br />
140<br />
141<br />
142<br />
143<br />
144<br />
145<br />
146<br />
147<br />
148<br />
149<br />
150<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
2.2.2 Handling without lifting straps<br />
Lifting straps are not furnished on switchboards when the weight of the section(s)<br />
exceeds their capacity, or when the lifting straps would cause stress to the<br />
switchboards. They also are not provided when the design does not permit, such<br />
as NEMA Type 3R outdoor equipment with overhangs. These switchboards can<br />
be handled by either slings, forklifts, rollers or a combination of these means.<br />
Typically, a handling warning is provided on those switchboard sections for which<br />
lifting straps are not provided.<br />
a) Sling: A crane or suitably rigged equipment with a chain arranged<br />
in a sling, or wire cable with safety hooks and shackles, should be<br />
used to lift a switchboard shipping section not equipped with lifting<br />
straps. Rig the sling completely around the switchboard and<br />
shipping stringers (see Figure 2), and use a forklift or jacks to lift<br />
the switchboard vertically off the floor to attach the sling.<br />
3
151<br />
152<br />
153<br />
154<br />
155<br />
156<br />
157<br />
158<br />
159<br />
160<br />
161<br />
162<br />
163<br />
164<br />
165<br />
166<br />
167<br />
168<br />
169<br />
170<br />
171<br />
172<br />
173<br />
174<br />
175<br />
176<br />
177<br />
178<br />
179<br />
180<br />
181<br />
182<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
b) Forklifts: Forklifts are an alternate method of handling<br />
switchboards. Verify that the capacity of the forklift is more than the<br />
weight of the load to be lifted. Always insure that the form lengths<br />
extend under the entire switchboard and extend beyond the<br />
opposite side (see Figure 3).<br />
c) Rollers: If equipment is not available for lifting the switchboard, or<br />
the ceiling is not high enough, rollers suitable for the application<br />
may be used to move the switchboard into position. A forklift or<br />
jacks can be used to initially lift the switchboard and position it on<br />
the rollers. Rollers should be positioned approximately every 18<br />
inches (457 mm), and be at least the width of the switchboard for<br />
stability. Extreme care should be taken when using rollers due to<br />
switchboard height and weight. Rollers are most suitable for<br />
moving switchboards on a level surface; use a winch or chainfall<br />
where inclines must be traveled over to prevent “runaway.”<br />
2.2 Storing the Switchboard<br />
a) Cover the switchboard with a tarp or plastic to keep the equipment<br />
from getting wet and accumulating dust or debris (cement dust can be<br />
corrosive and cause insulation breakdown when it accumulate across<br />
insulators). The cover should be heavy enough to keep from tearing<br />
during wind gusts at the storage location.<br />
b) To reduce condensation within the switchboard, store the switchboard<br />
indoors whenever possible to keep harmful condensation from<br />
accumulating inside the enclosure.<br />
c) Install a minimum of 250 watts of heat per vertical section, even for<br />
outdoor enclosures. Remove all loose packing or materials that could<br />
catch fire prior to applying the heat.<br />
4
183<br />
184<br />
185<br />
186<br />
187<br />
188<br />
189<br />
190<br />
191<br />
192<br />
193<br />
194<br />
195<br />
196<br />
197<br />
198<br />
199<br />
200<br />
201<br />
202<br />
203<br />
204<br />
205<br />
206<br />
207<br />
208<br />
209<br />
210<br />
211<br />
212<br />
213<br />
214<br />
215<br />
216<br />
217<br />
218<br />
219<br />
220<br />
221<br />
222<br />
223<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
3. Installation<br />
Proper installation is essential to the proper operation of all switchboard<br />
components. Thoroughly study associated instruction manuals, literature and<br />
drawings before attempting to install the switchboard. In most cases, this<br />
information will already have been requested prior to the shipment of the<br />
switchboard to enable advanced planning.<br />
3.1 Location<br />
a) The floor plan of the structure for an inside switchboard, or the site<br />
plan for an outdoor switchboard will show the area where the<br />
switchboard is to be installed. The location of the switchboard should<br />
comply with all building codes and at a minimum should meet the<br />
working space requirements of the NEC, Section 110.26.<br />
NOTE: Provisions for temporary ramps or installation hoists may require<br />
working clearances greater than NEC minimums.<br />
b) Consult the switchboard drawings to determine where accessibility is<br />
required for the switchboard (e.g., a rear access switchboard cannot<br />
be placed against a wall).<br />
c) Indoor switchboards in damp locations require shielding to prevent<br />
moisture and water from entering and accumulating. If the room<br />
temperature around the indoor switchboard is not between 77° – 104°F<br />
(25 – 40°C), use a minimum of 250 watts of heating per vertical section<br />
until the suitable environment can be provided.<br />
d) In locations where a sump pump is required, the pump should be<br />
properly working before the switchboard is installed to prevent<br />
accumulation of water that may seriously damage the switchboard and<br />
its internal components (see Section 7, Adverse Circumstances). The<br />
sump pump should be connected to a standby power source.<br />
3.2 Foundation Preparation<br />
a) The floor or foundation on which the switchboard will be installed needs to<br />
be strong enough to support the weight of the switchboard without bowing<br />
or sagging. A concrete surface is preferred.<br />
b) In special instances where earthquakes may occur, <strong>400</strong>0 psi concrete<br />
should be used along with specific anchoring means such as stud<br />
anchors, sleeves anchors or concrete anchor bolts (anchoring hardware is<br />
not supplied as a standard item with most switchboards). Performance of<br />
the switchboard under earthquake conditions is directly related to the<br />
foundation preparation.<br />
5
224<br />
225<br />
226<br />
227<br />
228<br />
229<br />
230<br />
231<br />
232<br />
233<br />
234<br />
235<br />
236<br />
237<br />
238<br />
239<br />
240<br />
241<br />
242<br />
243<br />
244<br />
245<br />
246<br />
247<br />
248<br />
249<br />
250<br />
251<br />
252<br />
253<br />
254<br />
255<br />
256<br />
257<br />
258<br />
259<br />
260<br />
261<br />
262<br />
263<br />
264<br />
265<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
NOTE: Local building codes may have seismic requirements that affect<br />
switchboard installation. Installers should consult these codes or<br />
coordinate with the general contractor prior to installing switchboards.<br />
c) A level mounting pad raised four inches (100 mm) above the general floor<br />
level is typical with the surrounding floor area gently sloping toward a<br />
drain. To ensure correct bus bar alignment within the switchboard and to<br />
enable bolting vertical sections together it is critical that the mounting pad<br />
or floor be smooth and level.<br />
NOTE: Provisions for temporary ramps or installation hoists may require<br />
working clearances greater than NEC minimums.<br />
d) If floor channels are embedded in the concrete pad, they should be level<br />
over the entire length of the switchboard in order to avoid distortion of the<br />
switchboard structure.<br />
e) Before pouring the concrete for the pad, install all conduits including future<br />
conduits required for bottom entry into the switchboard. Consult the<br />
switchboard drawing bottom view during this process to verify that the<br />
conduit layout matches the available conduit entry area into the<br />
switchboard. The manufacturer will already have taken into account the<br />
NEC and product listing requirements for conduit entry.<br />
f) Embedded conduits typically project above the finished pad approximately<br />
2 inches (50.8 mm). If embedded conduits project more than 2 inches<br />
(50.8 mm) above the concrete pad, it may be necessary to lift each<br />
shipping section vertically into place using a crane, timbers, jacks, or<br />
forklift. After the sections are installed, and approximate extension<br />
sleeves added to the conduits, the maximum projection should be 3<br />
inches (76 mm); NEC Section 408.5 prohibits projections greater than 3<br />
inches (76 mm).<br />
3.3 General Installation Instructions<br />
a) Clean dirt and debris from the pad and surrounding area where the<br />
switchboard will be located before moving the switchboard into its final<br />
position.<br />
b) Remove the shipping skids before installing the switchboard on the<br />
pad.<br />
c) If the switchboard is equipped with bottom closure plates, temporarily<br />
remove these plates and set them aside. Cut holes for the conduits<br />
entering the bottom of each enclosure in the bottom plates (if supplied)<br />
6
266<br />
267<br />
268<br />
269<br />
270<br />
271<br />
272<br />
273<br />
274<br />
275<br />
276<br />
277<br />
278<br />
279<br />
280<br />
281<br />
282<br />
283<br />
284<br />
285<br />
286<br />
287<br />
288<br />
289<br />
290<br />
291<br />
292<br />
293<br />
294<br />
295<br />
296<br />
297<br />
298<br />
299<br />
300<br />
301<br />
302<br />
303<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
based on that section’s conduits. Once the vertical sections have been<br />
installed, reinstall the bottom closure plates.<br />
d) Block the opening of each conduit with material that rodents will not be<br />
able to gnaw through, squeeze through, or push out of the way.<br />
Bottom closure plates will not keep out rodents that come in through<br />
the conduits.<br />
3.4 Installing Vertical Sections<br />
3.4.1 Initial placement<br />
a) If the switchboard has incoming cables or busway near or in its center,<br />
start with that vertical section first and work outward on each side.<br />
b) If the switchboard is left-feed, start from the left. If right-fee, start from<br />
the right.<br />
c) If the switchboard is close-coupled to a transformer, start at the<br />
transformer and work away from the transformer.<br />
3.4.2 Positioning<br />
Position each shipping section carefully, following the instructions in 2.2 Handling<br />
the Switchboard. Level with shims if necessary, and align each section with the<br />
previous section. Proper alignment will make joining the structures and throughbus<br />
easier.<br />
NOTE: Improper alignment of the through-bus may result in property loss, death,<br />
or serious injury.<br />
3.4.3 Lifting straps<br />
Remove lifting straps or slings so that vertical sections can be joined flush.<br />
Leave lifting straps or hardware on the switchboard if their removal is not<br />
required to join adjacent sections flush together.<br />
3.5 Joining Switchboard Sections<br />
a) Open or remove the front and, if necessary, the rear door or panels<br />
that provide access for bolting adjacent shipping sections together.<br />
b) Torque the bolts based on the manufacturer’s instructions.<br />
NOTE: The authority having jurisdiction (AHJ) may require that all bolts<br />
connecting bus sections be inspected for proper torque prior to closing up the<br />
switchboard.<br />
3.6 Anchoring the Switchboard<br />
Switchboard sections are freestanding structures but hard bumps or shifting<br />
movements can result in damage to interior components, conduit hubs and<br />
7
304<br />
305<br />
306<br />
307<br />
308<br />
309<br />
310<br />
311<br />
312<br />
313<br />
314<br />
315<br />
316<br />
317<br />
318<br />
319<br />
320<br />
321<br />
322<br />
323<br />
324<br />
325<br />
326<br />
327<br />
328<br />
329<br />
330<br />
331<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
cable/busway connections. Therefore, each vertical section of the switchboard is<br />
anchored to the floor. Some manufacturers provide formed base channels that<br />
run the entire length of the switchboard, mounting holes in the structure base, or<br />
both (see Figure 4).<br />
Anchor each section using the hardware recommended (but not usually supplied<br />
by) the switchboard manufacturer and torque the bolts to their recommended<br />
value.<br />
3.6.1 Seismic considerations<br />
Carefully follow the plans and specification when anchoring a switchboard for<br />
seismic conditions since the top of the switchboard structure can move as much<br />
as 3 inches (76 mm) in any direction.<br />
NOTE: Local building codes may have seismic requirements that affect<br />
switchboard installation. Installers should consult these codes or coordinate with<br />
the general contractor prior to installing switchboards.<br />
3.7 Installing Cables<br />
Install the incoming services conductors and load side cables after all<br />
switchboard sections are properly joined together and the entire switchboard<br />
structure is anchored to the floor. If the switchboard is in a seismic environment<br />
and cables or busway enter at the top of the switchboard, it is necessary to take<br />
into account the motion of the top of the switchboard during a seismic<br />
occurrence.<br />
NOTE: If the switchboard consists of only one shipping section, proceed to<br />
Section 3.10.<br />
8
332<br />
333<br />
334<br />
335<br />
336<br />
337<br />
338<br />
339<br />
340<br />
341<br />
342<br />
343<br />
344<br />
345<br />
346<br />
347<br />
348<br />
349<br />
350<br />
351<br />
352<br />
353<br />
354<br />
355<br />
356<br />
357<br />
358<br />
359<br />
360<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
3.8 Installing Interconnections between Switchboard Sections<br />
Switchboard vertical sections are electrically connected together using either<br />
through-bus or cables.<br />
3.8.1 Through-bus splice connections<br />
Through-bus splice connections are extremely important to the performance of<br />
the switchboard, since these connections are expected to carry the full current<br />
intended for their operation. Failure to properly make through-bus splice<br />
connections may result in property damage, death, or serious injury.<br />
a) Through-bus splice kits are provided by the switchboard manufacturer<br />
when more than one section is required to be electrically connected<br />
together by through-bus.<br />
b) Splice kits may come in separate boxes, be installed on the throughbus<br />
of one or more vertical sections, or be stored inside the sections to<br />
be spliced.<br />
c) Follow the proper sequence of hardware installation, as specified in the<br />
manufacturer’s installation instructions. Install conical washers such<br />
that their convex or “top” side is against the nut (see Figure 5).<br />
d) Torque the splice bolts to their recommended values. Mark each<br />
torqued connection with a permanent marker.<br />
e) The through-bus of some switchboards is covered with an insulating<br />
material. Follow the manufacturer’s instructions for installing insulation<br />
on each through-bus splice connection.<br />
3.8.2 Cable Interconnections<br />
Install the interconnection cables (which may or may not be supplied by the<br />
manufacturer) between sections as shown on manufacturer’s drawings. Torque<br />
all connections to the manufacturer’s recommended values.<br />
9
361<br />
362<br />
363<br />
364<br />
365<br />
366<br />
367<br />
368<br />
369<br />
370<br />
371<br />
372<br />
373<br />
374<br />
375<br />
376<br />
377<br />
378<br />
379<br />
380<br />
381<br />
382<br />
383<br />
384<br />
385<br />
386<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
3.9 Ground Bus Splice Connections<br />
Ground bus splice kits are provided by the switchboard manufacturers when<br />
more than one section is required to be electrically connected (see Figure 6).<br />
Proper installation of ground bus splice connections is essential to providing a<br />
low-impedance path to ground for temporary current resulting from phase-toground<br />
faults.<br />
a) Splice kits may come in separate boxes, be installed on the ground<br />
bus of one or more sections, or be stored inside the switchboard<br />
sections.<br />
b) Follow the proper sequence of hardware installation, as specified in the<br />
manufacturer’s installation instructions. Install conical washers such<br />
that their convex side is against the nut.<br />
c) Torque the splice bolts to the recommended value. Mark each torqued<br />
connection with a permanent marker.<br />
3.10 Grounding and Bonding<br />
3.10.1 Ground systems – service-entrance switchboards and<br />
switchboards used on separately derived systems<br />
NEC Section 250.64 describes complete grounding requirements for grounded<br />
separately derived systems.<br />
a) Run a grounding electrode conductor from the grounding electrode at<br />
the installation site to the grounding electrode conductor connection,<br />
10
387<br />
388<br />
389<br />
390<br />
391<br />
392<br />
393<br />
394<br />
395<br />
396<br />
397<br />
398<br />
399<br />
<strong>400</strong><br />
401<br />
402<br />
403<br />
404<br />
405<br />
406<br />
407<br />
408<br />
409<br />
410<br />
411<br />
412<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
commonly called a ground lug, located on the switchboard ground bus<br />
(see Figure 7).<br />
b) NEC Section 250.67 describes requirements for grounding electrode<br />
conductor material, installation, and size.<br />
c) Torque the ground lug binding screw based on the manufacturer’s<br />
recommendation or crimp in accordance with the crimp tool’s<br />
instructions.<br />
d) For service entrance equipment, or a switchboard used on a<br />
separately derived system, install the system bonding jumper between<br />
the neutral bus and the ground bus. A label on the front of the<br />
switchboard will identify the section(s) that incorporate the system<br />
bonding jumper(s).<br />
e) Torque the hardware of the main bonding jumper in accordance with<br />
the manufacturer’s recommendations.<br />
f) Equipment ground-fault protection will be rendered inoperative if the<br />
system is grounded down-stream from the ground fault sensor.<br />
g) For switchboards with multiple source of power, there will be two or<br />
more main bonding jumpers to install.<br />
3.10.2 Ungrounded systems – service-entrance switchboards<br />
and switchboards used on separately derived systems.<br />
NEC Section 250.64 describes complete grounding requirements for ungrounded<br />
separately derived systems.<br />
a) Run a grounding electrode conductor from the ground electrode at the<br />
installation site to the grounding electrode conductor connection,<br />
11
413<br />
414<br />
415<br />
416<br />
417<br />
418<br />
419<br />
420<br />
421<br />
422<br />
423<br />
424<br />
425<br />
426<br />
427<br />
428<br />
429<br />
430<br />
431<br />
432<br />
433<br />
434<br />
435<br />
436<br />
437<br />
438<br />
439<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
commonly called the ground lug, located on the switchboard ground<br />
bus (see Figure 7).<br />
b) NEC Section 250.66 describes requirements for grounding electrode<br />
conductor material, installation, and size.<br />
c) Torque the ground lug binding screw based on the manufacturer’s<br />
recommendation or crimp per the crimp tools instruction.<br />
3.11 Busway Connections<br />
Power is often distributed from switchboards using busway, also called bus duct.<br />
Busway is provided in different configurations by different manufacturers; one<br />
typical configuration is shown in Figure 8.<br />
a) When connecting busway, install conical washers so the convex side<br />
of the washer is against the nut.<br />
b) Confirm proper phasing of the busway before energizing the busway<br />
run.<br />
c) Do not use the switchboard to support the weight of the busway.<br />
Support the busway independently of the switchboard.<br />
3.12 Conduit Area<br />
a) The switchboard conduit entry drawings show the available conduit<br />
entry for the switchboard. External circuit cables for each section<br />
should be routed into and through these designated conduit areas,<br />
then routed internally to their designed termination areas.<br />
b) Do not use the switchboard to support the weight of the conduits.<br />
Support the conduits independently of the switchboard.<br />
c) If a bottom plate is furnished, remove it to cut holes for the conduit and<br />
cable entry. Bottom plates with holes are not furnished as a standard<br />
12
440<br />
441<br />
442<br />
443<br />
444<br />
445<br />
446<br />
447<br />
448<br />
449<br />
450<br />
451<br />
452<br />
453<br />
454<br />
455<br />
456<br />
457<br />
458<br />
459<br />
460<br />
461<br />
462<br />
463<br />
464<br />
465<br />
466<br />
467<br />
468<br />
469<br />
470<br />
471<br />
472<br />
473<br />
474<br />
475<br />
476<br />
477<br />
478<br />
479<br />
480<br />
481<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
item. Reinstall the bottom plates after the holes are made. Saw kerf<br />
between conduit holes in bottom plate for installations where individual<br />
conduits, such as duct bank risers.<br />
d) Under seismic conditions, the top of the switchboard may move up to 3<br />
inches (76 mm) in any direction. Any cables entering the top of the<br />
switchboard need sufficient slack to accommodate this motion. If the<br />
floor of the switchboard is designed for movement during a seismic<br />
event, the cables entering the bottom of the switchboard should also<br />
have enough slack to accommodate this motion.<br />
e) Use approved hubs and ring connectors to protect the cables and<br />
prevent condensation from entering the switchboard through the<br />
conduits.<br />
f) Bond all conduits, stubs, and ring connectors to the switchboard<br />
enclosure following the manufacturer’s recommendations.<br />
3.13 Cable Pulling<br />
Switchboard components are arranged to provide clearance and wire bending<br />
space for both line and load cables. Each cable should be pulled into the<br />
switchboard to conform to the arrangement specified on the switchboard<br />
drawings.<br />
a) Verify that the lugs correspond to the switchboard cable schedule and<br />
are suitable for the cables being terminated. Consult the markings on<br />
overcurrent protective devices to determine that the conductor size<br />
range is correct and the temperature rating is appropriate. Conductors<br />
rated 194°F (90°C) are permitted to be used with most connectors and<br />
terminals, but only at 167°F (75°C) ampacity. Some overcurrent<br />
protective devices, mostly those listed for operation at 100 percent of<br />
rated ampacity, require the use of 194°F (90°C) conductors sized at<br />
167°F (75°C) ampacity.<br />
b) Consult NEC Article 310 to calculate the proper size and number of<br />
conductors for the loads served.<br />
c) Prior to pulling the cables into the switchboard, plan ahead as to which<br />
overcurrent device to cable first. This is particularly important for<br />
group-mounted constructions.<br />
d) Cable pulling lubricants should not be allowed to drip or come into<br />
contact with overcurrent devices and/or plating of the bus bars.<br />
Remove all pulling compound from the interior of the switchboard prior<br />
to energizing the unit.<br />
e) Position the conductors in the switchboard enclosure so they are not<br />
subject to physical damage. If any conductors are in contact with<br />
structural members, place suitable protective material at the contact<br />
point to protect the cable insulation.<br />
13
482<br />
483<br />
484<br />
485<br />
486<br />
487<br />
488<br />
489<br />
490<br />
491<br />
492<br />
493<br />
494<br />
495<br />
496<br />
497<br />
498<br />
499<br />
500<br />
501<br />
502<br />
503<br />
504<br />
505<br />
506<br />
507<br />
508<br />
509<br />
510<br />
511<br />
512<br />
513<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
f) NEC Section 300.20(a) requires that all phase and grounded<br />
conductors of the same circuit pass through the same metal opening<br />
together. Otherwise, a magnetic loop will be created causing<br />
overheating within the switchboard.<br />
g) Where required, brace or lace the conductors in accordance with the<br />
manufacturer’s instructions or consulting engineer’s specification.<br />
h) Train cables within wire gutters of switchboards in a neat and<br />
workmanlike manner.<br />
3.14 Cable Terminations<br />
Terminating and tightening cable connections to the manufacturer’s<br />
recommended torque is imperative for a satisfactory connection. Follow these<br />
steps when terminating conductors at the switchboard:<br />
a) Strip a sufficient length of insulation from the cable end to fit into the<br />
full length of the lugs barrel. Use a proper insulation stripping tool to<br />
avoid nicking conductor strands. Stripping cable too long should be<br />
avoided since the through-air clearance could be reduced below the<br />
minimums required by the NEC.<br />
b) Mechanical lugs (set-screw type) are the most common type of<br />
connector furnished with switchboards. Torque these lugs in<br />
accordance with the manufacturer’s recommendations to avoid<br />
stripping threads or cracking the lug body.<br />
c) When compression lugs are used to terminate aluminum conductors,<br />
remove oxides from the conductors and apply an anti-oxidant<br />
compound to the aluminum conductor before inserting into the lug<br />
body. Oxides on aluminum conductors are poor conductors and will<br />
cause abnormal heating at the connection.<br />
d) Remove compression lugs from their point of termination in order to<br />
crimp them onto cables. Follow the manufacturer’s recommendation<br />
as to the proper number of crimps and their position on the lug. Use<br />
the recommended sealant. Re-install the crimp lugs to the lug pad and<br />
toque the hardware used with the lugs.<br />
14
514<br />
515<br />
516<br />
517<br />
518<br />
519<br />
520<br />
521<br />
522<br />
523<br />
524<br />
525<br />
526<br />
527<br />
528<br />
529<br />
530<br />
531<br />
532<br />
533<br />
534<br />
535<br />
536<br />
537<br />
538<br />
539<br />
540<br />
541<br />
542<br />
543<br />
544<br />
545<br />
546<br />
547<br />
548<br />
549<br />
550<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
4. Pre-Energizing Checkout Procedure<br />
4.1 General<br />
Conduct a complete inspection of the switchboard before it is energized to<br />
ensure that the components within the switchboard function properly.<br />
a) Check all field installed bus bar connections for correct torque value.<br />
b) Check all accessible connections for tightness.<br />
c) Check all factory and field installed lug terminations for the correct<br />
torque value.<br />
d) Visually check the bussing insulators for cracks and supports for<br />
damage.<br />
e) Check to insure that dents or other damage to the enclosure have not<br />
resulted in clearances that violate NEC requirements.<br />
f) Remove foam blocks, packing material, and temporary cushioning<br />
from the switchboard and components inside the switchboard.<br />
g) Check all relays, meters and instrumentation device wiring and<br />
terminations.<br />
4.2 Insulation Test<br />
Perform a direct current (DC) insulation test on the switchboard and record the<br />
value for future maintenance tests; a switchboard insulation resistance chart is<br />
shown in Section 9. Values less than 1 megohm are typically unacceptable.<br />
Prior to this test, remove control power fuses and any other equipment that<br />
should not be subjected to this level of potential.<br />
4.3 Current Transformers<br />
Ensure that current transformers secondary terminals are connected to a load or<br />
are shorted together using shorting straps or terminal block shorting screws.<br />
CAUTION: Open secondary terminals may have high voltages, which could be a<br />
hazard to people or equipment.<br />
The shortening means are removed when the current transformers operate<br />
normally with their intended load.<br />
4.4 Circuit Breakers and Fusible Switches<br />
a) Manually open and close all circuit breakers and fusible switches to<br />
ensure proper operation.<br />
b) Adjust the magnetic trip on thermal magnetic circuit breakers to their<br />
proper setting based on the system study or switchboard schedule. A<br />
15
551<br />
552<br />
553<br />
554<br />
555<br />
556<br />
557<br />
558<br />
559<br />
560<br />
561<br />
562<br />
563<br />
564<br />
565<br />
566<br />
567<br />
568<br />
569<br />
570<br />
571<br />
572<br />
573<br />
574<br />
575<br />
576<br />
577<br />
578<br />
579<br />
580<br />
581<br />
582<br />
583<br />
584<br />
585<br />
586<br />
587<br />
588<br />
589<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
setting too low for a load that has a high peak inrush current will trip<br />
the circuit breaker on start-up.<br />
c) Electronic circuit breakers have functions such as long-time,<br />
instantaneous, short-time, and ground fault, that requires initial<br />
adjustment. Settings typically are provided in a coordination study<br />
prepared by the consulting engineer, or other persons responsible for<br />
the switchboard set-up.<br />
NOTE: These values typically are not found on the drawings supplied by the<br />
switchboard manufacturer.<br />
If values are not provided, consult the manufacturer’s circuit breaker<br />
instruction manual for values that will set the electronic circuit breaker<br />
functions to emulate thermal magnetic circuit breaker characteristics.<br />
4.5 Ground-fault Protection<br />
a) The trip and time-delay on ground-fault protective equipment are<br />
typically set by the manufacturer at their lowest settings. Adjust these<br />
settings based on information provided in a coordination study<br />
prepared by the consulting engineer, or other persons responsible for<br />
the switchboard set-up.<br />
b) Some ground-fault protection systems require field connections at the<br />
job site. Consult the switchboard interconnection wiring diagram for<br />
details.<br />
c) Check the ground-fault circuitry and establish that there are no<br />
grounds on the neutral downstream from the service entrance point.<br />
d) The NEC requires that the ground-fault protection system be<br />
performance tested when first installed, and that a written record of this<br />
test be available to the AHJ. A testing group with experience in<br />
switchboard ground-fault testing should perform an injection test.<br />
4.6 Interconnections<br />
Verify that all interconnecting wiring between switchboard sections has been<br />
connected.<br />
4.7 Power Fuses and Control Power Disconnects<br />
Replace all control power fuses removed in the Insulation Test (see Section 4.2)<br />
and turn on all control power disconnects.<br />
4.8 Clean-up<br />
Vacuum all scrap, wire, dust and other debris from the switchboard. Do not use<br />
compressed air to blow debris out of the switchboard, since debris may, instead,<br />
settle inside devices and impair their ability to function.<br />
16
590<br />
591<br />
592<br />
593<br />
594<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
4.9 Close-up<br />
Replace all covers. Check for any pinched wires and close all doors. Make sure<br />
that the enclosure parts are properly aligned and fastened securely.<br />
17
595<br />
596<br />
597<br />
598<br />
599<br />
600<br />
601<br />
602<br />
603<br />
604<br />
605<br />
606<br />
607<br />
608<br />
609<br />
610<br />
611<br />
612<br />
613<br />
614<br />
615<br />
616<br />
617<br />
618<br />
619<br />
620<br />
621<br />
622<br />
623<br />
624<br />
625<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
5. Energizing the Switchboard<br />
WARNING: Arc flash, arc blast, and shock hazards exist when energizing<br />
switchboards. Switchboards should only be energized by qualified persons,<br />
following work practiced defined in the NFPA 70E.<br />
Hazards exist in energizing a switchboard; energizing should only be<br />
performed by qualified electrical personnel.<br />
If a short circuit or ground-fault condition exists, caused by damage or poor<br />
installation practices, and this is not detected and corrected during the check-out<br />
procedures, serious personal injury and/or damage to the switchboard can result<br />
when the switchboard is first energized. Follow the steps below to energize the<br />
switchboards; read all steps before proceeding.<br />
Step 1 Turn off all downstream loads. No load should be on the<br />
switchboard when it is first energized.<br />
Step 2 Use remote operators, if available, to close devices and energize<br />
switchboards and loads for the first time.<br />
Step 3 Prior to energizing any circuit that supplies rotating machinery,<br />
verify that the phase sequence is correct. Serious damage can<br />
result to motors and similar equipment rotating in the wrong<br />
direction.<br />
Step 4 One by one, close each circuit breaker or fusible switch in the<br />
switchboard.<br />
Step 5 Proceed to energize (turn on) the downstream loads (lighting<br />
circuits, contactors, heaters, motors, etc.) one at a time.<br />
18
626<br />
627<br />
628<br />
629<br />
630<br />
631<br />
632<br />
633<br />
634<br />
635<br />
636<br />
637<br />
638<br />
639<br />
640<br />
641<br />
642<br />
643<br />
644<br />
645<br />
646<br />
647<br />
648<br />
649<br />
650<br />
651<br />
652<br />
653<br />
654<br />
655<br />
656<br />
657<br />
658<br />
659<br />
660<br />
661<br />
662<br />
663<br />
664<br />
665<br />
666<br />
667<br />
668<br />
669<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
6. Switchboard Maintenance<br />
Periodic maintenance of switchboards extends service life and increases<br />
reliability. Cleaning, inspection, maintenance, and testing should only be<br />
performed by qualified personnel on switchboards to which power has been<br />
turned-off, disconnected, and electrically isolated, unless required for testing, so<br />
that no accidental contact can be made with energized parts. Follow all<br />
manufacturer’s warnings and instructions.<br />
The interval between maintenance checks varies depending on the environment,<br />
such as ambient temperature and conditions in the switchboard room, and usage<br />
of the equipment. Perform routine inspections, such as making limited visual<br />
observations and recording operational data, periodically with switchboards<br />
energized and in service.<br />
Perform cleaning, inspections, maintenance and testing of switchboards at least<br />
annually, but as often as the operating environment requires keeping<br />
switchboards clean. Perform the first inspection and maintenance no more than<br />
one year after the original installation. Plan cleaning, inspections, maintenance<br />
and testing to minimize outages.<br />
Clean, inspect, maintain, and test switchboards following any unusual operating<br />
condition, such as whenever an overcurrent protective device opens, or a phaseto-phase<br />
short circuit or ground-fault occurs (see Section 7.1), in accordance with<br />
manufacturer recommendations.<br />
6.1 Routine Inspections<br />
Inspect areas and spaces around switchboards for any accumulation of dirt or<br />
dust. Remove any accumulations of dirt or dust. Remove trash, combustible<br />
material, and other debris from areas around switchboards. Use the rate of<br />
accumulation of dust and moisture on visible surfaces as a guide for scheduling<br />
cleaning, inspections, maintenance, and testing.<br />
Inspect switchboards for external signs of overheating. Measure and record the<br />
ambient temperature. Check equipment installed near switchboards that might<br />
be an external source of heat. Eliminate external sources of heat to<br />
switchboards. Check the operating temperature of switchboards that have been<br />
operating under normal load and at normal ambient temperature for a minimum<br />
of 3 hours by measuring the surface temperature of switchboard access covers,<br />
doors, circuit breakers and switches. If the temperature exceeds manufacturer<br />
recommendations, de-energize switchboard and investigate sources of<br />
overheating.<br />
Record switchboard voltage and load currents, if equipped with meters, noting<br />
the date and time of day. Provide comments regarding known causes of<br />
variations in loading, such as load additions or equipment maintenance outages.<br />
19
670<br />
671<br />
672<br />
673<br />
674<br />
675<br />
676<br />
677<br />
678<br />
679<br />
680<br />
681<br />
682<br />
683<br />
684<br />
685<br />
686<br />
687<br />
688<br />
689<br />
690<br />
691<br />
692<br />
693<br />
694<br />
695<br />
696<br />
697<br />
698<br />
699<br />
700<br />
701<br />
702<br />
703<br />
704<br />
705<br />
706<br />
707<br />
708<br />
709<br />
710<br />
711<br />
712<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
Check all accessible exterior switchboard hardware for tightness.<br />
Visually inspect enclosures for physical damage. Repair physical damage, if<br />
practical and as approved by the manufacturer. Consult owner and switchboard<br />
manufacturer for recommendations for suitable protective barriers to prevent<br />
future damage.<br />
Inspect areas and spaces around switchboards for evidence of water or<br />
moisture. Eliminate sources of water or moisture, or provide suitable protection<br />
for switchboards from sources of water.<br />
6.2 Safety Procedures<br />
Before cleaning, inspecting, testing, or maintaining, de-energize and electrically<br />
isolate equipment in accordance with established procedures. Consider all<br />
circuits live until they are confirmed to be de-energized by testing and are locked<br />
out of operation. Do not work on energized equipment. Guard energized<br />
conductors and equipment in close proximity to work. Failure to observe these<br />
precautions may result in severe personal injury or death.<br />
Personnel working on or near energized switchboards should follow the safe<br />
work practices described in NFPA 70E, including the use of personal protective<br />
equipment (PPE) appropriate for the task being performed.<br />
Apply lockout/tagout procedures in accordance with documented and established<br />
policies and practices. Render electrical circuit conductors and circuit parts<br />
electrically safe by removing all sources of energy by opening all upstream<br />
source disconnecting means, locking and tagging out all source disconnecting<br />
means, verifying the absence of voltage using an approved voltage testing<br />
device, and guarding any exposed energized components.<br />
Remove the front cover of the switchboard and attach grounding leads to the line<br />
terminals of the main circuit breaker or main lugs, to the neutral terminal bus bar,<br />
if so equipped, and to the grounding terminal.<br />
6.3 Cleaning and Inspections<br />
Consult manufacturer recommendations for cleaning and inspecting<br />
switchboards and components. De-energize switchboards in accordance with<br />
Section 6.2 prior to performing any cleaning or inspections.<br />
Visually inspect switchboards for evidence of discoloration, abnormal dust<br />
accumulation, metal shards, or any other indication of overheating, wear, or other<br />
abnormal conditions prior to cleaning.<br />
Visually inspect the switchboard for signs of overheating. Discoloration and<br />
flaking of insulation or metal parts are indications of possible overheating.<br />
20
713<br />
714<br />
715<br />
716<br />
717<br />
718<br />
719<br />
720<br />
721<br />
722<br />
723<br />
724<br />
725<br />
726<br />
727<br />
728<br />
729<br />
730<br />
731<br />
732<br />
733<br />
734<br />
735<br />
736<br />
737<br />
738<br />
739<br />
740<br />
741<br />
742<br />
743<br />
744<br />
745<br />
746<br />
747<br />
748<br />
749<br />
750<br />
751<br />
752<br />
753<br />
754<br />
755<br />
756<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
Correct conditions that cause the overheating, and replace the affected parts<br />
before re-energizing the switchboard.<br />
Vacuum the inside of switchboards to remove any debris, dirt, or dust that has<br />
accumulated, noting anything unusual such as signs of insects or rodent activity<br />
or moisture. Avoid blowing dust into switchboards. Do not use a blower or<br />
compressed air. Maintain adequate ventilation during cleaning.<br />
Wipe bus bars, insulators, conductors and other parts with a clean, dry lint-free<br />
cloth. Do not use chemicals or petroleum-based solvents that may degrade<br />
plastics or insulating materials.<br />
Visually inspect the inside of the switchboard for moisture, condensation build-up<br />
or signs of any previous wetness. Moisture causes insulation failures and rapid<br />
oxidation of current carrying parts. Pay particular attention to conduit entrances<br />
and the top of the switchboard between sections. Remove any moisture present<br />
inside the switchboard and seal off all leaks. Replace any components that show<br />
evidence of damage from moisture.<br />
Carefully inspect all switchboard devices for any worn-out, cracked or missing<br />
parts. Inspect terminations, connections, and lugs for alignment, physical<br />
damage, burns, corrosion, discoloration, flaking, heat damage, arcing, pitting,<br />
melting, deterioration, carbonization, cracks, chips, breaks, partial discharge, or<br />
moisture. Replace damaged components. Investigate and eliminate sources of<br />
damage.<br />
Plated parts may become dark over a period of time due to oxidation. Removing<br />
this discoloration will reduce the thickness of the plating. Consult the<br />
manufacturer for recommendations regarding discoloration of parts.<br />
Verify that all key interlocks and door interlocking provisions are working<br />
properly.<br />
6.4 Maintenance and Testing<br />
Consult manufacturer recommendations for maintaining and testing switchboards<br />
and components. De-energize switchboards in accordance with Section 6.2 prior<br />
to performing any maintenance or testing.<br />
6.4.1 Infrared Scan<br />
After cleaning and inspecting switchboards and components in accordance with<br />
Section 6.3, perform an infrared scan in accordance with switchboard and test<br />
equipment manufacturer recommendations. With the switchboard de-energized,<br />
remove accessible covers, plates, weathershields, etc. Provide supplemental<br />
barriers and safety precautions during infrared scan to prevent accidental contact<br />
with exposed energized components. Personnel working on or near energized<br />
switchboards should follow the safe work practices described in NFPA 70E,<br />
21
757<br />
758<br />
759<br />
760<br />
761<br />
762<br />
763<br />
764<br />
765<br />
766<br />
767<br />
768<br />
769<br />
770<br />
771<br />
772<br />
773<br />
774<br />
775<br />
776<br />
777<br />
778<br />
779<br />
780<br />
781<br />
782<br />
783<br />
784<br />
785<br />
786<br />
787<br />
788<br />
789<br />
790<br />
791<br />
792<br />
793<br />
794<br />
795<br />
796<br />
797<br />
798<br />
799<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
including the use of personal protective equipment (PPE) appropriate for the task<br />
being performed.<br />
Energize the switchboard in accordance with Section 6.6, and turn on all normal<br />
loads supplied by the switchboard. Perform an infrared scan of all switchboard<br />
electrical connections and terminals while energized and operating under normal<br />
load conditions.<br />
Use an infrared scanning device designed to measure actual operating<br />
temperatures, or designed to detect significant deviations from surrounding<br />
conditions. Provide documentation of device calibration.<br />
Prepare a certified report identifying the switchboard tested and describing the<br />
results of the infrared scan. Include notations of deficiencies detected, remedial<br />
actions taken, and results from retesting after remedial actions.<br />
Consult switchboard manufacturer for repair or replacement recommendations if<br />
infrared scan results indicate overheating of components.<br />
De-energize the switchboard in accordance with Section 6.2.<br />
6.4.2 Bus Bar Joints<br />
Consult the manufacturer’s recommendations concerning bus bar joints and retorque<br />
where required. Some switchboard bus bar joints are maintenance-free.<br />
Additional tightening after installation may degrade these connections.<br />
Replace parts that show indications of pitting, corrosion, discoloration or<br />
annealing due to overheating. Do not use abrasive materials on bus bar joints.<br />
Use hardware and washers of a grade identical to or better than the hardware<br />
replaced.<br />
6.4.3 Molded-Case Circuit Breakers<br />
a) Clean circuit breaker surfaces. Remove dust, soot, grease, moisture, and<br />
foreign material.<br />
b) Operate circuit breakers several times to exercise the mechanism and<br />
contacts, and to ensure smooth operation. Many circuit breakers have a<br />
test feature which trips, exercises and lubricates the mechanism. This<br />
method of exercising circuit breakers should be used if available. If<br />
unavailable, operate circuit breakers manually. Do not oil or grease parts<br />
of molded case circuit breakers. Replace circuit breakers that do not<br />
operate smoothly.<br />
c) Check circuit breakers for visual defects, chips, cracks, breaks, burns, and<br />
deterioration. Visually check circuit breakers for evidence of overheating<br />
22
800<br />
801<br />
802<br />
803<br />
804<br />
805<br />
806<br />
807<br />
808<br />
809<br />
810<br />
811<br />
812<br />
813<br />
814<br />
815<br />
816<br />
817<br />
818<br />
819<br />
820<br />
821<br />
822<br />
823<br />
824<br />
825<br />
826<br />
827<br />
828<br />
829<br />
830<br />
831<br />
832<br />
833<br />
834<br />
835<br />
836<br />
837<br />
838<br />
839<br />
840<br />
841<br />
842<br />
843<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
and thermal damage. Investigate and eliminate sources of overheating.<br />
Replace damaged circuit breakers.<br />
d) For circuit breakers that use solid-state circuitry or a microprocessor, run<br />
the self-diagnostic program, if available. For electronic circuit breakers,<br />
use the test set to run trip unit test automatically with user prompts.<br />
Repair or replace circuit breakers in accordance with manufacturer<br />
recommendations.<br />
6.4.4 Bolted Pressure Switches<br />
Exercise bolted pressure switch operating mechanisms. Check the cover<br />
interlock with the switch in the “on” position. The cover should not open using<br />
normal hand force. Lubricate parts using materials and methods in accordance<br />
with manufacturer’s recommendations.<br />
6.4.5 Fusible Switches<br />
a) Thoroughly clean fusible switches inside and outside. Clean contact<br />
areas of fuses and fuse holders. Wipe insulating areas of fuses with a<br />
clean, dry, lint-free cloth.<br />
b) Operate each switch several times to ensure that all mechanisms are free<br />
and in proper working order. Check switches for damaged or broken<br />
parts, free movement, corrosion, dirt, and excessive wear. Verify proper<br />
blade penetration, travel stops, and mechanical operation. Repair or<br />
replace switches in accordance with manufacturer recommendations.<br />
c) Inspect contact surfaces, blades, and jaws for discoloration, overheating,<br />
pitting, arcing, and corona. Inspect arc chutes. Clean and dress readily<br />
accessible copper electrical contacts, blades, and jaws in accordance with<br />
manufacturer recommendations. Repair or replace burned contacts.<br />
Many contact surfaces, such as arcing contacts, are silver tungsten or<br />
other types of materials that must never be dressed. When contacts of<br />
these materials require maintenance, they must be replaced. If contact<br />
clips have lost their tension, replace clips or replace the switch. Consult<br />
the manufacturer for recommendations.<br />
d) Tighten fuse holder connections in accordance with manufacturer<br />
recommendations. Inspect each fuse holder to determine whether it<br />
seems to be adequately supporting the fuse and that the fuse holder is<br />
securely attached to the mounting base. Inspect fuse clips for<br />
discoloration, overheating, corrosion, or physical damage. Replace weak<br />
or burned clips. Install new fuse clips and suitable clamps. Use<br />
manufacturer’s replacement parts.<br />
e) Lubricate operating mechanisms and sliding contact surfaces, if required,<br />
according to manufacturer’s instructions. If no instructions are given on<br />
23
844<br />
845<br />
846<br />
847<br />
848<br />
849<br />
850<br />
851<br />
852<br />
853<br />
854<br />
855<br />
856<br />
857<br />
858<br />
859<br />
860<br />
861<br />
862<br />
863<br />
864<br />
865<br />
866<br />
867<br />
868<br />
869<br />
870<br />
871<br />
872<br />
873<br />
874<br />
875<br />
876<br />
877<br />
878<br />
879<br />
880<br />
881<br />
882<br />
883<br />
884<br />
885<br />
886<br />
887<br />
888<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
the devices, sliding copper contacts, operating mechanisms, and<br />
interlocks may be lubricated with clean, light grease. Wipe off excess<br />
lubrication to avoid contamination.<br />
f) Check the cover interlock with the switch in the “on” position. The cover<br />
should not open using normal hand force. Inspect switches for any<br />
damaged or broken parts. Check the fuse mounting clips or bolted<br />
contact area for corrosion or discoloration due to overheating. Replace<br />
damaged or broken parts as necessary.<br />
6.4.6 Inspecting and Replacing Fuses<br />
Ensure that equipment is de-energized before inspecting and replacing fuses.<br />
Test line and load terminals of switches for the presence of voltage before<br />
replacing fuses. Turn the switches to the “off” position before opening the door.<br />
Do not defeat cover interlocks to gain access to fuses.<br />
Visually inspect switch blades to verify that all blades are disconnected from the<br />
line connections. Consult the manufacturer for recommendations when blades<br />
do not disconnect from line connections.<br />
a) Check all fuses to assure that the correct type and rating are installed.<br />
Where renewable fuses are used, examine fuse links to ensure that the<br />
correct link is installed.<br />
NOTE: Certain switchboard manufacturers do not recommend the use of<br />
renewable link fuses in their equipment.<br />
b) Look for fuses that have been bridged with wire, metal strips, disks, or<br />
appear to have been forced or hammered in, etc. Replace with correct<br />
fuses and consult the manufacturer for recommendations for preventing a<br />
recurrence.<br />
c) Look for evidence of overheating of cartridge fuses. Replace fuses having<br />
discolored or weakened casings. Investigate the cause of overheating.<br />
d) Inspect ferruled or knife blades of cartridge fuses for corrosion or<br />
oxidation. Clean and polish contact surfaces. Clean surfaces with a noncorrosive<br />
cleaning agent. Plated parts may become dark over a period of<br />
time due to oxidation. Removing this discoloration will reduce the<br />
thickness of the plating. Consult the manufacturer for recommendations<br />
regarding discoloration of parts.<br />
e) Measure fuse resistance. Investigate fuse-resistance values that deviate<br />
from each other by more than 15 percent. Replace defective or partiallyburned<br />
fuses. Re-tighten plug fuses.<br />
24
889<br />
890<br />
891<br />
892<br />
893<br />
894<br />
895<br />
896<br />
897<br />
898<br />
899<br />
900<br />
901<br />
902<br />
903<br />
904<br />
905<br />
906<br />
907<br />
908<br />
909<br />
910<br />
911<br />
912<br />
913<br />
914<br />
915<br />
916<br />
917<br />
918<br />
919<br />
920<br />
921<br />
922<br />
923<br />
924<br />
925<br />
926<br />
927<br />
928<br />
929<br />
930<br />
931<br />
932<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
f) Replace fuses with fuses of like types and ratings. Ensure that noncurrent-limiting<br />
devices are not used as replacements for current-limiting<br />
devices. Do not defeat any rejection feature in any switchboard fusible<br />
device.<br />
6.4.7 Ground-Fault Protection Systems<br />
a) Check the torque of terminal connections on ground-fault protection<br />
systems annually. Inspect for corrosion and for physical, thermal, and<br />
electrical damage. Replace any damaged components.<br />
b) Test the ground-fault protection system in accordance with manufacturer<br />
recommendations. Testing may be conducted with or without tripping<br />
main or branch overcurrent protective devices. Testing with trip is<br />
preferable since it ensures the whole system is functioning. Energize the<br />
switchboard in accordance with Section 6.6 prior to testing.<br />
c) If the ground-fault protection system does not operate properly and<br />
additional equipment has been connected to the installation since the last<br />
maintenance test/check, de-energize the entire system in accordance with<br />
Section 6.2, disconnect the main bonding jumper, and check for continuity<br />
between the neutral and ground on the load-side of the main bonding<br />
jumper. If grounds are found, remove them and test again. If no grounds<br />
are detected and the ground-fault protection system is still not functioning<br />
properly, consult the switchboard manufacturer for recommendations.<br />
d) If the ground-fault protection system does not operate properly and no<br />
additional equipment has been connected to the installation since the last<br />
maintenance test/check, check the devices for physical or electrical<br />
damage and replace accordingly. Check wiring for damage or loose<br />
connections and correct any problems found. Consult the switchboard<br />
manufacturer for recommendations.<br />
6.5 Insulation Resistance Test<br />
Perform an insulation resistance test on switchboards using a 1000 V dc<br />
megohmmeter. Disconnect all accessories and electronic devices that may be<br />
subjected to the test voltage. Test from phase-to-ground and from phase-tophase<br />
with all switches and circuit breakers in both the open and closed<br />
positions, all instrumentation and control fuses removed, and no loads connected<br />
to the switchboard. Ground all phases not being tested. Connect megohmmeter<br />
between each phase and ground and between each phase. Measure insulation<br />
resistance at one minute intervals following the application of the test voltage.<br />
Record the megohm values of each phase and between each phase, along with<br />
the description of the instrument, voltage level, humidity, temperature, time, and<br />
date of the test. Consult switchboard manufacturer's published data for<br />
acceptable test results. If published data is not available, investigate any values<br />
25
933<br />
934<br />
935<br />
936<br />
937<br />
938<br />
939<br />
940<br />
941<br />
942<br />
943<br />
944<br />
945<br />
946<br />
947<br />
948<br />
949<br />
950<br />
951<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
that deviate from previous test results under similar conditions by more than 50<br />
percent of the lowest value. Investigate any results less than 1 megohm with the<br />
overcurrent protective devices in the open position for possible tracking on<br />
insulation or insulation breakdown. Ground each phase at the completion of the<br />
test. Maintain records of testing for future reference.<br />
6.6 Re-energizing Switchboards<br />
Energize switchboards in accordance with Section 5. Remove grounding leads<br />
from the line terminals of the switchboard. Visually inspect the system to ensure<br />
that all tools, electrical jumpers, test devices, etc., have been removed. Visually<br />
inspect equipment and areas around equipment to ensure that all persons are<br />
clear from circuits and equipment to be re-energized. Remove locks and tags<br />
only after work is complete and tested, and all personnel are clear of the area.<br />
Test for short circuits or ground faults. Energize circuits using established<br />
switching procedures. Close disconnect means starting at the source, working<br />
towards the load. Measure phase-to-phase and phase-to-neutral voltages, if<br />
applicable. Investigate source of voltage unbalance greater than 3 percent.<br />
Measure switchboard feeder and branch load currents. Verify that conductors<br />
are properly sized and protected for actual loading.<br />
26
952<br />
953<br />
954<br />
955<br />
956<br />
957<br />
958<br />
959<br />
960<br />
961<br />
962<br />
963<br />
964<br />
965<br />
966<br />
967<br />
968<br />
969<br />
970<br />
971<br />
972<br />
973<br />
974<br />
975<br />
976<br />
977<br />
978<br />
979<br />
980<br />
981<br />
982<br />
983<br />
984<br />
985<br />
986<br />
987<br />
988<br />
989<br />
990<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
7. Adverse Circumstances<br />
Special procedures are necessary to determine whether a switchboard can<br />
safely remain in service following a short-circuit, ground-fault, or exposure to<br />
water.<br />
7.1 Inspection Following a Short-Circuit or Ground-Fault<br />
Condition<br />
Do not attempt to re-energize a switchboard following a short-circuit or groundfault<br />
condition within the switchboard. Do not re-energize a feeder or branch<br />
overcurrent protection device in the switchboard that has opened due to a short<br />
circuit or ground-fault until the problem downstream has been corrected.<br />
Following a short-circuit or ground-fault within a switchboard, inspect the<br />
equipment thoroughly as described in Section 6.1 to verify that damage has not<br />
occurred to conductors or insulators within the switchboard.<br />
NOTE: The insulating properties of some organic insulating materials may<br />
deteriorate during an electrical arc. Replacement of the damaged insulating<br />
material is the only remedy.<br />
7.1.1 Short-circuits develop high mechanical stresses that can<br />
damage conductors and insulation<br />
Improper and loosened connections may result in conductors pulling out of their<br />
terminations on subsequent short-circuits; for this reason all connections should<br />
be inspected and, if necessary, re-evaluated. Great care must be taken in<br />
evaluating the cause of the short-circuit. Do not replace the fuse(s) and turn the<br />
overcurrent protective device back on, or reset the circuit breaker, without first<br />
determining whether it is safe to energize the circuit. Phase-to-phase shortcircuits<br />
that originate on bus bars can travel the length of the bussing system<br />
through the switchboard, and the greatest damage may not occur where the<br />
arcing condition originated. Conduct an insulation test to determine the integrity<br />
of the switchboard insulation prior to re-energizing the switchboard.<br />
7.1.2 Ground-faults are unintentional current paths between a phase<br />
conductor and ground<br />
Depending on the magnitude of the ground-fault and its duration, carbon build-up<br />
and metallic splatter may need to be removed, insulators cleaned or replaced.<br />
Perform phase-to-phase and phase-to-ground insulation tests, with a minimum<br />
reading of one megohm, prior to turning the switchboard power back on.<br />
27
991<br />
992<br />
993<br />
994<br />
995<br />
996<br />
997<br />
998<br />
999<br />
1000<br />
1001<br />
1002<br />
1003<br />
1004<br />
1005<br />
1006<br />
1007<br />
1008<br />
1009<br />
1010<br />
1011<br />
1012<br />
1013<br />
1014<br />
1015<br />
1016<br />
1017<br />
1018<br />
1019<br />
1020<br />
1021<br />
1022<br />
1023<br />
1024<br />
1025<br />
1026<br />
1027<br />
1028<br />
1029<br />
1030<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
7.2 Replacing a Switchboard Soaked by or Submerged Under<br />
Water<br />
a) Do not work on energized electrical equipment when standing in water.<br />
b) Do not energize a switchboard that is wet.<br />
c) Do not clean or repair a switchboard that has been exposed to large volumes<br />
of water or submerged. Current-carrying parts, insulation systems, and<br />
electrical/electronic components may be damaged beyond repair through<br />
contamination by chemicals, river or creek water, sewage and other<br />
pollutants. In this event, replace the switchboard rather than attempt to repair<br />
it.<br />
7.3 Inspecting and Re-Energizing a Switchboard Sprayed or<br />
Splashed with Clean Water<br />
Apply heat (a minimum of 250 watts per section) to the switchboard to dry it out<br />
until visible signs of dampness cannot be seen. Remove materials that could<br />
catch fire prior to applying the heat. Consult the manufacturer’s<br />
recommendations for specific guidelines on how to insure that it is safe to reenergize<br />
the switchboard, or follow this procedure.<br />
7.3.1 Preliminary Inspection<br />
Follow the steps in Section 7.3.2 to re-energize the switchboard only if a<br />
preliminary inspection verifies that the following conditions are satisfied:<br />
a) There are no signs of physical damage to the equipment.<br />
b) The switchboard has not been soaked or submerged in water.<br />
c) The water that has been in contact with the switchboard has not been<br />
contaminated with sewage, chemicals or other substances.<br />
d) Water has not entered any area of the switchboard enclosure that contains<br />
wiring, and has not come into contact with any live part. Look for water<br />
entering through conduits.<br />
If all of the conditions listed above are satisfied, proceed as follows.<br />
7.3.2 Cleaning, testing, and re-energizing a switchboard<br />
Step 1 Completely de-energize and electrically isolate the switchboard so<br />
that contact cannot be made with energized parts.<br />
Step 2 Wipe off all moisture from bus bars, insulators, and insulating<br />
materials with a clean, dry, lint free cloth. Never use cleaning<br />
agents or sprays unless specifically recommended by the<br />
switchboard manufacturer.<br />
Step 3 Prepare the switchboard for an insulation resistance test by<br />
disconnecting all line-side supply conductors and all load-side<br />
28
1031<br />
1032<br />
1033<br />
1034<br />
1035<br />
1036<br />
1037<br />
1038<br />
1039<br />
1040<br />
1041<br />
1042<br />
1043<br />
1044<br />
1045<br />
1046<br />
1047<br />
1048<br />
1049<br />
1050<br />
1051<br />
1052<br />
1053<br />
1054<br />
1055<br />
1056<br />
1057<br />
1058<br />
1059<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
conductors to isolate the switchboard from the wiring system. Turn<br />
all circuit breakers or fusible switches to the “ON” position. Voltage<br />
cannot be present on the switchboard during the insulation<br />
resistance test.<br />
Step 4 Use a DC insulation resistance tester with a capacity of 500-1000<br />
volts DC to perform phase-to-ground and phase-to-phase insulation<br />
tests.<br />
NOTE: Use of an AC dielectric tester is not recommended.<br />
a) Measure each phase (A, B, C) to ground with the circuit<br />
breakers or fusible switches “ON”.<br />
b) Measure each phase to another phase with the circuit breakers<br />
or fusible switches “ON”. Record the values of the insulation<br />
resistance on the insulation resistance chart shown in Section 9.<br />
Step 5 Do not re-energize the equipment if any of the resistance<br />
measurements are not at least one megohm. If moisture is the<br />
cause of the low resistance readings, the moisture can be removed<br />
from the switchboard by providing a minimum of 250 watts of heat<br />
per vertical section.<br />
Step 6 If the resistance measurements are greater than 0.5 megohom, the<br />
equipment can be re-energized.<br />
29
1060<br />
1061<br />
1062<br />
1063<br />
1064<br />
1065<br />
1066<br />
1067<br />
1068<br />
1069<br />
1070<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
8. Recommended Torque Values<br />
If the switchboard manufacturer does not provide specific torque<br />
recommendations, use the following as a guide.<br />
30
1071<br />
1072<br />
1073<br />
1074<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
31
1075<br />
1076<br />
1077<br />
1078<br />
1079<br />
1080<br />
1081<br />
1082<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
9. Switchboard Insulation Resistance Chart<br />
NOTE: The use of an AC dielectric tester for testing the switchboard is not<br />
recommended. Use an insulation resistance tester with a capacity of 500-1000<br />
VDC.<br />
32
1083<br />
1084<br />
1085<br />
1086<br />
1087<br />
1088<br />
1089<br />
1090<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
10. Operations and Maintenance Documents<br />
This standard refers to manufacturer’s packing label warnings (2.1a), instruction<br />
manuals, literature, drawings (Section 3), recorded values of tests (4.2, 7.3.2, 9),<br />
and set values of adjustable trips (4.4 and 4.5a, 4.5d). This material, plus asbuilt<br />
drawings, should be assembled, identified and delivered to the owner of the<br />
facility at the completion of the installation.<br />
33
1091<br />
1092<br />
1093<br />
1094<br />
1095<br />
1096<br />
1097<br />
1098<br />
1099<br />
1100<br />
<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />
(This appendix is not part of the standard)<br />
Appendix A: Reference Standards<br />
This publication, when used in conjunction with the National Electrical Code and<br />
switchboard manufacturer’s literature, provides sufficient information to install<br />
and maintain deadfront switchboards operating at 600 volts and less. The<br />
following publications may also provide useful information:<br />
<strong>NECA</strong> will insert the list at publication.<br />
34