15.01.2013 Views

TO: NECA 400-200X ANSI Canvass Participants FROM: Billie Zidek ...

TO: NECA 400-200X ANSI Canvass Participants FROM: Billie Zidek ...

TO: NECA 400-200X ANSI Canvass Participants FROM: Billie Zidek ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>TO</strong>: <strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> <strong>ANSI</strong> <strong>Canvass</strong> <strong>Participants</strong><br />

<strong>FROM</strong>: <strong>Billie</strong> <strong>Zidek</strong><br />

Director of Standards<br />

DATE: December 12, 2006<br />

RE: Revision of <strong>NECA</strong> <strong>400</strong>, Standard for Installing and Maintaining<br />

Switchboards, as an American National Standard<br />

As a result of comments received on the first ballot, the proposed standard has<br />

been revised. Section 6 has been completely rewritten for your review and<br />

comment.<br />

<strong>NECA</strong> <strong>400</strong>-200x reballot is attached for your review. Please note that the<br />

Foreword and Annexes are not a part of the proposed American National<br />

Standard.<br />

Also enclosed is a copy of the canvass list for this standard indicating the various<br />

interests represented and a comment response form.<br />

Action Request:<br />

After completing your review, please email or fax your <strong>ANSI</strong> canvass ballot to<br />

301-215-4500. We would appreciate receiving your response on or before<br />

Monday, January 29, 2007.<br />

NATIONAL ELECTRICAL CONTRAC<strong>TO</strong>RS ASSOCIATION<br />

3 Bethesda Metro Center, Suite 1100, Bethesda, MD 20814<br />

301-657-3110 x546 ℡; 301-215-4500 �; billie.zidek@necanet.org �


Date: March 30, 2006<br />

<strong>ANSI</strong> CANVASS REAFFIRMATION<br />

LETTER BALLOT<br />

Ballot Due Date: January 29, 2007<br />

<strong>TO</strong>PIC: Revision of <strong>NECA</strong> <strong>400</strong>-<strong>200X</strong>, Standard for Installing and<br />

Maintaining Switchboards, as an American National Standard.<br />

QUESTION: Should this standard, developed by the National Electrical<br />

Contractors Association (<strong>NECA</strong>), be approved as an American<br />

National Standard?<br />

_____ Yes No technical changes required.<br />

_____ Yes With Editorial Comments<br />

_____ No Technical changes required (see attached file).<br />

_____ Abstain If you find you cannot vote “yes” or “no” and<br />

want to be recorded as abstaining, please explain<br />

the reasons for your abstention on the reverse<br />

side.<br />

Signature: ___________________________________________<br />

Name: ___________________________________________<br />

Email Address:<br />

Organization<br />

______________________________________<br />

Represented: ______________________________________<br />

Phone No.: ______________________________________<br />

Fax No.: ______________________________________<br />

Date: ______________________________________<br />

Return to:<br />

<strong>Billie</strong> <strong>Zidek</strong><br />

Standards & Safety<br />

National Electrical Contractors Association<br />

3 Bethesda Metro Center, Suite 1100<br />

Bethesda, MD 20814<br />

301/215-4546 ℡<br />

301/215-4500 �<br />

billie.<strong>Zidek</strong>@necanet.org


1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

15<br />

16<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

TABLE OF CONTENTS<br />

Foreword..........................................................................................................................ii<br />

1. Scope .......................................................................................................................1<br />

2. Switchboard Receiving, Handling and Storing ....................................................2<br />

3. Installation ...............................................................................................................5<br />

4. Pre-Energizing Checkout Procedure...................................................................15<br />

5. Energizing the Switchboard.................................................................................18<br />

6. Switchboard Maintenance ................................................................................19<br />

7. Adverse Circumstances .......................................................................................27<br />

8. Recommended Torque Values.............................................................................30<br />

9. Switchboard Insulation Resistance Chart ..........................................................32<br />

10. Operations and Maintenance Documents.......................................................33<br />

Appendix A: Reference Standards .............................................................................34<br />

i


17<br />

18<br />

19<br />

20<br />

21<br />

22<br />

23<br />

24<br />

25<br />

26<br />

27<br />

28<br />

29<br />

30<br />

31<br />

32<br />

33<br />

34<br />

35<br />

36<br />

37<br />

38<br />

39<br />

40<br />

41<br />

42<br />

43<br />

44<br />

45<br />

46<br />

47<br />

48<br />

49<br />

50<br />

51<br />

52<br />

53<br />

54<br />

55<br />

56<br />

57<br />

58<br />

59<br />

60<br />

61<br />

62<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

(This foreword is not part of the standard)<br />

Foreword<br />

National Electrical Installation Standards (NEIS ® ) are designed to improve<br />

communication among specifiers, purchasers, and suppliers of electrical<br />

construction services. They define a minimum baseline of quality and<br />

workmanship for installing electrical products and systems. NEIS are intended to<br />

be referenced in contract documents for electrical construction projects. The<br />

following language is recommended:<br />

Deadfront distribution switchboards rated 600 volts or less shall be<br />

installed and maintained in accordance with <strong>NECA</strong> <strong>400</strong>, Standard for<br />

Installing and Maintaining Switchboards.<br />

Use of NEIS is voluntary, and the National Electrical Contractors Association<br />

(<strong>NECA</strong>) assumes no obligation or liability to users of this publication. Existence<br />

of a standard shall not preclude any member or non-member of <strong>NECA</strong> from<br />

specifying or using alternate construction methods permitted by applicable<br />

regulations.<br />

This publication is intended to comply with the edition of the National Electrical<br />

Code (NEC) in effect at the time of publication. Because they are quality<br />

standards, NEIS may in some instances go beyond the minimum safety<br />

requirements of the NEC. It is the responsibility of users of this publication to<br />

comply with state and local electrical codes when installing electrical products<br />

and systems.<br />

Suggestions for revisions and improvements to this standard are welcome. They<br />

should be addressed to:<br />

<strong>NECA</strong> Standards & Safety<br />

3 Bethesda Metro Center, Suite 1100<br />

Bethesda, MD 20814<br />

(301) 657-3110 telephone<br />

(301) 215-4500 fax<br />

neis@necanet.org<br />

www.neca-neis.org<br />

To purchase NEIS, contact the <strong>NECA</strong> Order Desk at (301) 215-4504 tel, (301)<br />

215-4500 fax, or orderdesk@necanet.org. NEIS can also be purchased in .pdf<br />

download format at www.neca-neis.org/standards.<br />

Copyright © 200x, National Electrical Contractors Association. All rights reserved. Unauthorized<br />

reproduction prohibited.<br />

National Electrical Installation Standards and NEIS are trademarks of <strong>NECA</strong>, National Electrical<br />

Code and NEC are registered trademarks of the National Fire Protection Association.<br />

ii


63<br />

64<br />

65<br />

66<br />

67<br />

68<br />

69<br />

70<br />

71<br />

72<br />

73<br />

74<br />

75<br />

76<br />

77<br />

78<br />

79<br />

80<br />

81<br />

82<br />

83<br />

84<br />

85<br />

86<br />

87<br />

88<br />

89<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

1. Scope<br />

This standard describes installation procedures for deadfront distribution<br />

switchboards rated 600 volts or less.<br />

1.1 Products and Applications Included:<br />

It also covers periodic routine maintenance procedures for switchboards, and<br />

special procedures to be used after adverse circumstances such as a shortcircuit,<br />

ground-fault, or immersion in water.<br />

1.2 Regulatory and Other Requirements:<br />

a) All information in this publication is intended to conform to the National<br />

Electrical Code (<strong>ANSI</strong>/NFPA 70). Installers should always follow the NEC,<br />

applicable state and local codes, manufacturer’s instructions, and contract<br />

documents when installing switchboards.<br />

b) Only qualified persons familiar with the construction and installation of<br />

switchboards should perform the work described in this publication. It is<br />

recommended that all work be performed in accordance with NFPA 70E,<br />

Standard for Electrical Safety in the Workplace.<br />

c) General requirements for installing electrical products and systems are<br />

described in <strong>NECA</strong> 1, Standard Practices for Good Workmanship in<br />

Electrical Contracting (<strong>ANSI</strong>). Other NEIS provide additional guidance for<br />

installing particular types of electrical products and systems. A complete<br />

list of NEIS is provided in Annex A.<br />

1


90<br />

91<br />

92<br />

93<br />

94<br />

95<br />

96<br />

97<br />

98<br />

99<br />

100<br />

101<br />

102<br />

103<br />

104<br />

105<br />

106<br />

107<br />

108<br />

109<br />

110<br />

111<br />

112<br />

113<br />

114<br />

115<br />

116<br />

117<br />

118<br />

119<br />

120<br />

121<br />

122<br />

123<br />

124<br />

125<br />

126<br />

127<br />

128<br />

129<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

2. Switchboard Receiving, Handling and Storing<br />

2.1 Receiving the Switchboard<br />

a) Unload carefully, observing all packing label warnings.<br />

b) Use forklifts or other loading equipment only for palletized<br />

shipments.<br />

c) Leaving protective coverings in place as much as possible, open<br />

and inspect the switchboard completely for shipping damage.<br />

Undamaged material should be carefully repacked unless intended<br />

for immediate installation.<br />

NOTE: Depending on company policy or project circumstances, it may be<br />

necessary to receive, unpack and check all material at the company shop<br />

or other staging area, in which case, careful repacking is essential.<br />

2.2 Handling the Switchboard<br />

Switchboards are typically large, bulky pieces of equipment weighing several<br />

hundred pounds or more. The packing list will provide the actual weight of each<br />

item. Handle the switchboard properly in order to avoid injury to personnel and<br />

damage to equipment. Verify that the lifting capacity of the handling equipment<br />

is more than the shipping weight and type of truck making the delivery prior to<br />

receiving the shipment. Delivery on an open truck at the job-site is<br />

recommended.<br />

Suitable protection against the weather must be provided if the equipment is<br />

designed only for indoor installation (NEMA Type 1).<br />

There are two primary ways of lifting the equipment: with lifting straps and with<br />

lifting straps, using a sling instead. Using the manufacturer’s lifting straps is the<br />

preferable method when these are supplied.<br />

2.2.1 Handling with lifting straps<br />

Switchboard manufacturers provide lifting straps as standard equipment when<br />

the weight of the switchboard section(s) does not exceed the recommended<br />

capacity of the lifting straps. Use a rigid spreader or a spanner beam to provide<br />

vertical lift on the lifting straps (see Figure 1), and avoid damage to the frame or<br />

finish. Follow lifting warning labels on the switchboard.<br />

2


130<br />

131<br />

132<br />

133<br />

134<br />

135<br />

136<br />

137<br />

138<br />

139<br />

140<br />

141<br />

142<br />

143<br />

144<br />

145<br />

146<br />

147<br />

148<br />

149<br />

150<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

2.2.2 Handling without lifting straps<br />

Lifting straps are not furnished on switchboards when the weight of the section(s)<br />

exceeds their capacity, or when the lifting straps would cause stress to the<br />

switchboards. They also are not provided when the design does not permit, such<br />

as NEMA Type 3R outdoor equipment with overhangs. These switchboards can<br />

be handled by either slings, forklifts, rollers or a combination of these means.<br />

Typically, a handling warning is provided on those switchboard sections for which<br />

lifting straps are not provided.<br />

a) Sling: A crane or suitably rigged equipment with a chain arranged<br />

in a sling, or wire cable with safety hooks and shackles, should be<br />

used to lift a switchboard shipping section not equipped with lifting<br />

straps. Rig the sling completely around the switchboard and<br />

shipping stringers (see Figure 2), and use a forklift or jacks to lift<br />

the switchboard vertically off the floor to attach the sling.<br />

3


151<br />

152<br />

153<br />

154<br />

155<br />

156<br />

157<br />

158<br />

159<br />

160<br />

161<br />

162<br />

163<br />

164<br />

165<br />

166<br />

167<br />

168<br />

169<br />

170<br />

171<br />

172<br />

173<br />

174<br />

175<br />

176<br />

177<br />

178<br />

179<br />

180<br />

181<br />

182<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

b) Forklifts: Forklifts are an alternate method of handling<br />

switchboards. Verify that the capacity of the forklift is more than the<br />

weight of the load to be lifted. Always insure that the form lengths<br />

extend under the entire switchboard and extend beyond the<br />

opposite side (see Figure 3).<br />

c) Rollers: If equipment is not available for lifting the switchboard, or<br />

the ceiling is not high enough, rollers suitable for the application<br />

may be used to move the switchboard into position. A forklift or<br />

jacks can be used to initially lift the switchboard and position it on<br />

the rollers. Rollers should be positioned approximately every 18<br />

inches (457 mm), and be at least the width of the switchboard for<br />

stability. Extreme care should be taken when using rollers due to<br />

switchboard height and weight. Rollers are most suitable for<br />

moving switchboards on a level surface; use a winch or chainfall<br />

where inclines must be traveled over to prevent “runaway.”<br />

2.2 Storing the Switchboard<br />

a) Cover the switchboard with a tarp or plastic to keep the equipment<br />

from getting wet and accumulating dust or debris (cement dust can be<br />

corrosive and cause insulation breakdown when it accumulate across<br />

insulators). The cover should be heavy enough to keep from tearing<br />

during wind gusts at the storage location.<br />

b) To reduce condensation within the switchboard, store the switchboard<br />

indoors whenever possible to keep harmful condensation from<br />

accumulating inside the enclosure.<br />

c) Install a minimum of 250 watts of heat per vertical section, even for<br />

outdoor enclosures. Remove all loose packing or materials that could<br />

catch fire prior to applying the heat.<br />

4


183<br />

184<br />

185<br />

186<br />

187<br />

188<br />

189<br />

190<br />

191<br />

192<br />

193<br />

194<br />

195<br />

196<br />

197<br />

198<br />

199<br />

200<br />

201<br />

202<br />

203<br />

204<br />

205<br />

206<br />

207<br />

208<br />

209<br />

210<br />

211<br />

212<br />

213<br />

214<br />

215<br />

216<br />

217<br />

218<br />

219<br />

220<br />

221<br />

222<br />

223<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

3. Installation<br />

Proper installation is essential to the proper operation of all switchboard<br />

components. Thoroughly study associated instruction manuals, literature and<br />

drawings before attempting to install the switchboard. In most cases, this<br />

information will already have been requested prior to the shipment of the<br />

switchboard to enable advanced planning.<br />

3.1 Location<br />

a) The floor plan of the structure for an inside switchboard, or the site<br />

plan for an outdoor switchboard will show the area where the<br />

switchboard is to be installed. The location of the switchboard should<br />

comply with all building codes and at a minimum should meet the<br />

working space requirements of the NEC, Section 110.26.<br />

NOTE: Provisions for temporary ramps or installation hoists may require<br />

working clearances greater than NEC minimums.<br />

b) Consult the switchboard drawings to determine where accessibility is<br />

required for the switchboard (e.g., a rear access switchboard cannot<br />

be placed against a wall).<br />

c) Indoor switchboards in damp locations require shielding to prevent<br />

moisture and water from entering and accumulating. If the room<br />

temperature around the indoor switchboard is not between 77° – 104°F<br />

(25 – 40°C), use a minimum of 250 watts of heating per vertical section<br />

until the suitable environment can be provided.<br />

d) In locations where a sump pump is required, the pump should be<br />

properly working before the switchboard is installed to prevent<br />

accumulation of water that may seriously damage the switchboard and<br />

its internal components (see Section 7, Adverse Circumstances). The<br />

sump pump should be connected to a standby power source.<br />

3.2 Foundation Preparation<br />

a) The floor or foundation on which the switchboard will be installed needs to<br />

be strong enough to support the weight of the switchboard without bowing<br />

or sagging. A concrete surface is preferred.<br />

b) In special instances where earthquakes may occur, <strong>400</strong>0 psi concrete<br />

should be used along with specific anchoring means such as stud<br />

anchors, sleeves anchors or concrete anchor bolts (anchoring hardware is<br />

not supplied as a standard item with most switchboards). Performance of<br />

the switchboard under earthquake conditions is directly related to the<br />

foundation preparation.<br />

5


224<br />

225<br />

226<br />

227<br />

228<br />

229<br />

230<br />

231<br />

232<br />

233<br />

234<br />

235<br />

236<br />

237<br />

238<br />

239<br />

240<br />

241<br />

242<br />

243<br />

244<br />

245<br />

246<br />

247<br />

248<br />

249<br />

250<br />

251<br />

252<br />

253<br />

254<br />

255<br />

256<br />

257<br />

258<br />

259<br />

260<br />

261<br />

262<br />

263<br />

264<br />

265<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

NOTE: Local building codes may have seismic requirements that affect<br />

switchboard installation. Installers should consult these codes or<br />

coordinate with the general contractor prior to installing switchboards.<br />

c) A level mounting pad raised four inches (100 mm) above the general floor<br />

level is typical with the surrounding floor area gently sloping toward a<br />

drain. To ensure correct bus bar alignment within the switchboard and to<br />

enable bolting vertical sections together it is critical that the mounting pad<br />

or floor be smooth and level.<br />

NOTE: Provisions for temporary ramps or installation hoists may require<br />

working clearances greater than NEC minimums.<br />

d) If floor channels are embedded in the concrete pad, they should be level<br />

over the entire length of the switchboard in order to avoid distortion of the<br />

switchboard structure.<br />

e) Before pouring the concrete for the pad, install all conduits including future<br />

conduits required for bottom entry into the switchboard. Consult the<br />

switchboard drawing bottom view during this process to verify that the<br />

conduit layout matches the available conduit entry area into the<br />

switchboard. The manufacturer will already have taken into account the<br />

NEC and product listing requirements for conduit entry.<br />

f) Embedded conduits typically project above the finished pad approximately<br />

2 inches (50.8 mm). If embedded conduits project more than 2 inches<br />

(50.8 mm) above the concrete pad, it may be necessary to lift each<br />

shipping section vertically into place using a crane, timbers, jacks, or<br />

forklift. After the sections are installed, and approximate extension<br />

sleeves added to the conduits, the maximum projection should be 3<br />

inches (76 mm); NEC Section 408.5 prohibits projections greater than 3<br />

inches (76 mm).<br />

3.3 General Installation Instructions<br />

a) Clean dirt and debris from the pad and surrounding area where the<br />

switchboard will be located before moving the switchboard into its final<br />

position.<br />

b) Remove the shipping skids before installing the switchboard on the<br />

pad.<br />

c) If the switchboard is equipped with bottom closure plates, temporarily<br />

remove these plates and set them aside. Cut holes for the conduits<br />

entering the bottom of each enclosure in the bottom plates (if supplied)<br />

6


266<br />

267<br />

268<br />

269<br />

270<br />

271<br />

272<br />

273<br />

274<br />

275<br />

276<br />

277<br />

278<br />

279<br />

280<br />

281<br />

282<br />

283<br />

284<br />

285<br />

286<br />

287<br />

288<br />

289<br />

290<br />

291<br />

292<br />

293<br />

294<br />

295<br />

296<br />

297<br />

298<br />

299<br />

300<br />

301<br />

302<br />

303<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

based on that section’s conduits. Once the vertical sections have been<br />

installed, reinstall the bottom closure plates.<br />

d) Block the opening of each conduit with material that rodents will not be<br />

able to gnaw through, squeeze through, or push out of the way.<br />

Bottom closure plates will not keep out rodents that come in through<br />

the conduits.<br />

3.4 Installing Vertical Sections<br />

3.4.1 Initial placement<br />

a) If the switchboard has incoming cables or busway near or in its center,<br />

start with that vertical section first and work outward on each side.<br />

b) If the switchboard is left-feed, start from the left. If right-fee, start from<br />

the right.<br />

c) If the switchboard is close-coupled to a transformer, start at the<br />

transformer and work away from the transformer.<br />

3.4.2 Positioning<br />

Position each shipping section carefully, following the instructions in 2.2 Handling<br />

the Switchboard. Level with shims if necessary, and align each section with the<br />

previous section. Proper alignment will make joining the structures and throughbus<br />

easier.<br />

NOTE: Improper alignment of the through-bus may result in property loss, death,<br />

or serious injury.<br />

3.4.3 Lifting straps<br />

Remove lifting straps or slings so that vertical sections can be joined flush.<br />

Leave lifting straps or hardware on the switchboard if their removal is not<br />

required to join adjacent sections flush together.<br />

3.5 Joining Switchboard Sections<br />

a) Open or remove the front and, if necessary, the rear door or panels<br />

that provide access for bolting adjacent shipping sections together.<br />

b) Torque the bolts based on the manufacturer’s instructions.<br />

NOTE: The authority having jurisdiction (AHJ) may require that all bolts<br />

connecting bus sections be inspected for proper torque prior to closing up the<br />

switchboard.<br />

3.6 Anchoring the Switchboard<br />

Switchboard sections are freestanding structures but hard bumps or shifting<br />

movements can result in damage to interior components, conduit hubs and<br />

7


304<br />

305<br />

306<br />

307<br />

308<br />

309<br />

310<br />

311<br />

312<br />

313<br />

314<br />

315<br />

316<br />

317<br />

318<br />

319<br />

320<br />

321<br />

322<br />

323<br />

324<br />

325<br />

326<br />

327<br />

328<br />

329<br />

330<br />

331<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

cable/busway connections. Therefore, each vertical section of the switchboard is<br />

anchored to the floor. Some manufacturers provide formed base channels that<br />

run the entire length of the switchboard, mounting holes in the structure base, or<br />

both (see Figure 4).<br />

Anchor each section using the hardware recommended (but not usually supplied<br />

by) the switchboard manufacturer and torque the bolts to their recommended<br />

value.<br />

3.6.1 Seismic considerations<br />

Carefully follow the plans and specification when anchoring a switchboard for<br />

seismic conditions since the top of the switchboard structure can move as much<br />

as 3 inches (76 mm) in any direction.<br />

NOTE: Local building codes may have seismic requirements that affect<br />

switchboard installation. Installers should consult these codes or coordinate with<br />

the general contractor prior to installing switchboards.<br />

3.7 Installing Cables<br />

Install the incoming services conductors and load side cables after all<br />

switchboard sections are properly joined together and the entire switchboard<br />

structure is anchored to the floor. If the switchboard is in a seismic environment<br />

and cables or busway enter at the top of the switchboard, it is necessary to take<br />

into account the motion of the top of the switchboard during a seismic<br />

occurrence.<br />

NOTE: If the switchboard consists of only one shipping section, proceed to<br />

Section 3.10.<br />

8


332<br />

333<br />

334<br />

335<br />

336<br />

337<br />

338<br />

339<br />

340<br />

341<br />

342<br />

343<br />

344<br />

345<br />

346<br />

347<br />

348<br />

349<br />

350<br />

351<br />

352<br />

353<br />

354<br />

355<br />

356<br />

357<br />

358<br />

359<br />

360<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

3.8 Installing Interconnections between Switchboard Sections<br />

Switchboard vertical sections are electrically connected together using either<br />

through-bus or cables.<br />

3.8.1 Through-bus splice connections<br />

Through-bus splice connections are extremely important to the performance of<br />

the switchboard, since these connections are expected to carry the full current<br />

intended for their operation. Failure to properly make through-bus splice<br />

connections may result in property damage, death, or serious injury.<br />

a) Through-bus splice kits are provided by the switchboard manufacturer<br />

when more than one section is required to be electrically connected<br />

together by through-bus.<br />

b) Splice kits may come in separate boxes, be installed on the throughbus<br />

of one or more vertical sections, or be stored inside the sections to<br />

be spliced.<br />

c) Follow the proper sequence of hardware installation, as specified in the<br />

manufacturer’s installation instructions. Install conical washers such<br />

that their convex or “top” side is against the nut (see Figure 5).<br />

d) Torque the splice bolts to their recommended values. Mark each<br />

torqued connection with a permanent marker.<br />

e) The through-bus of some switchboards is covered with an insulating<br />

material. Follow the manufacturer’s instructions for installing insulation<br />

on each through-bus splice connection.<br />

3.8.2 Cable Interconnections<br />

Install the interconnection cables (which may or may not be supplied by the<br />

manufacturer) between sections as shown on manufacturer’s drawings. Torque<br />

all connections to the manufacturer’s recommended values.<br />

9


361<br />

362<br />

363<br />

364<br />

365<br />

366<br />

367<br />

368<br />

369<br />

370<br />

371<br />

372<br />

373<br />

374<br />

375<br />

376<br />

377<br />

378<br />

379<br />

380<br />

381<br />

382<br />

383<br />

384<br />

385<br />

386<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

3.9 Ground Bus Splice Connections<br />

Ground bus splice kits are provided by the switchboard manufacturers when<br />

more than one section is required to be electrically connected (see Figure 6).<br />

Proper installation of ground bus splice connections is essential to providing a<br />

low-impedance path to ground for temporary current resulting from phase-toground<br />

faults.<br />

a) Splice kits may come in separate boxes, be installed on the ground<br />

bus of one or more sections, or be stored inside the switchboard<br />

sections.<br />

b) Follow the proper sequence of hardware installation, as specified in the<br />

manufacturer’s installation instructions. Install conical washers such<br />

that their convex side is against the nut.<br />

c) Torque the splice bolts to the recommended value. Mark each torqued<br />

connection with a permanent marker.<br />

3.10 Grounding and Bonding<br />

3.10.1 Ground systems – service-entrance switchboards and<br />

switchboards used on separately derived systems<br />

NEC Section 250.64 describes complete grounding requirements for grounded<br />

separately derived systems.<br />

a) Run a grounding electrode conductor from the grounding electrode at<br />

the installation site to the grounding electrode conductor connection,<br />

10


387<br />

388<br />

389<br />

390<br />

391<br />

392<br />

393<br />

394<br />

395<br />

396<br />

397<br />

398<br />

399<br />

<strong>400</strong><br />

401<br />

402<br />

403<br />

404<br />

405<br />

406<br />

407<br />

408<br />

409<br />

410<br />

411<br />

412<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

commonly called a ground lug, located on the switchboard ground bus<br />

(see Figure 7).<br />

b) NEC Section 250.67 describes requirements for grounding electrode<br />

conductor material, installation, and size.<br />

c) Torque the ground lug binding screw based on the manufacturer’s<br />

recommendation or crimp in accordance with the crimp tool’s<br />

instructions.<br />

d) For service entrance equipment, or a switchboard used on a<br />

separately derived system, install the system bonding jumper between<br />

the neutral bus and the ground bus. A label on the front of the<br />

switchboard will identify the section(s) that incorporate the system<br />

bonding jumper(s).<br />

e) Torque the hardware of the main bonding jumper in accordance with<br />

the manufacturer’s recommendations.<br />

f) Equipment ground-fault protection will be rendered inoperative if the<br />

system is grounded down-stream from the ground fault sensor.<br />

g) For switchboards with multiple source of power, there will be two or<br />

more main bonding jumpers to install.<br />

3.10.2 Ungrounded systems – service-entrance switchboards<br />

and switchboards used on separately derived systems.<br />

NEC Section 250.64 describes complete grounding requirements for ungrounded<br />

separately derived systems.<br />

a) Run a grounding electrode conductor from the ground electrode at the<br />

installation site to the grounding electrode conductor connection,<br />

11


413<br />

414<br />

415<br />

416<br />

417<br />

418<br />

419<br />

420<br />

421<br />

422<br />

423<br />

424<br />

425<br />

426<br />

427<br />

428<br />

429<br />

430<br />

431<br />

432<br />

433<br />

434<br />

435<br />

436<br />

437<br />

438<br />

439<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

commonly called the ground lug, located on the switchboard ground<br />

bus (see Figure 7).<br />

b) NEC Section 250.66 describes requirements for grounding electrode<br />

conductor material, installation, and size.<br />

c) Torque the ground lug binding screw based on the manufacturer’s<br />

recommendation or crimp per the crimp tools instruction.<br />

3.11 Busway Connections<br />

Power is often distributed from switchboards using busway, also called bus duct.<br />

Busway is provided in different configurations by different manufacturers; one<br />

typical configuration is shown in Figure 8.<br />

a) When connecting busway, install conical washers so the convex side<br />

of the washer is against the nut.<br />

b) Confirm proper phasing of the busway before energizing the busway<br />

run.<br />

c) Do not use the switchboard to support the weight of the busway.<br />

Support the busway independently of the switchboard.<br />

3.12 Conduit Area<br />

a) The switchboard conduit entry drawings show the available conduit<br />

entry for the switchboard. External circuit cables for each section<br />

should be routed into and through these designated conduit areas,<br />

then routed internally to their designed termination areas.<br />

b) Do not use the switchboard to support the weight of the conduits.<br />

Support the conduits independently of the switchboard.<br />

c) If a bottom plate is furnished, remove it to cut holes for the conduit and<br />

cable entry. Bottom plates with holes are not furnished as a standard<br />

12


440<br />

441<br />

442<br />

443<br />

444<br />

445<br />

446<br />

447<br />

448<br />

449<br />

450<br />

451<br />

452<br />

453<br />

454<br />

455<br />

456<br />

457<br />

458<br />

459<br />

460<br />

461<br />

462<br />

463<br />

464<br />

465<br />

466<br />

467<br />

468<br />

469<br />

470<br />

471<br />

472<br />

473<br />

474<br />

475<br />

476<br />

477<br />

478<br />

479<br />

480<br />

481<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

item. Reinstall the bottom plates after the holes are made. Saw kerf<br />

between conduit holes in bottom plate for installations where individual<br />

conduits, such as duct bank risers.<br />

d) Under seismic conditions, the top of the switchboard may move up to 3<br />

inches (76 mm) in any direction. Any cables entering the top of the<br />

switchboard need sufficient slack to accommodate this motion. If the<br />

floor of the switchboard is designed for movement during a seismic<br />

event, the cables entering the bottom of the switchboard should also<br />

have enough slack to accommodate this motion.<br />

e) Use approved hubs and ring connectors to protect the cables and<br />

prevent condensation from entering the switchboard through the<br />

conduits.<br />

f) Bond all conduits, stubs, and ring connectors to the switchboard<br />

enclosure following the manufacturer’s recommendations.<br />

3.13 Cable Pulling<br />

Switchboard components are arranged to provide clearance and wire bending<br />

space for both line and load cables. Each cable should be pulled into the<br />

switchboard to conform to the arrangement specified on the switchboard<br />

drawings.<br />

a) Verify that the lugs correspond to the switchboard cable schedule and<br />

are suitable for the cables being terminated. Consult the markings on<br />

overcurrent protective devices to determine that the conductor size<br />

range is correct and the temperature rating is appropriate. Conductors<br />

rated 194°F (90°C) are permitted to be used with most connectors and<br />

terminals, but only at 167°F (75°C) ampacity. Some overcurrent<br />

protective devices, mostly those listed for operation at 100 percent of<br />

rated ampacity, require the use of 194°F (90°C) conductors sized at<br />

167°F (75°C) ampacity.<br />

b) Consult NEC Article 310 to calculate the proper size and number of<br />

conductors for the loads served.<br />

c) Prior to pulling the cables into the switchboard, plan ahead as to which<br />

overcurrent device to cable first. This is particularly important for<br />

group-mounted constructions.<br />

d) Cable pulling lubricants should not be allowed to drip or come into<br />

contact with overcurrent devices and/or plating of the bus bars.<br />

Remove all pulling compound from the interior of the switchboard prior<br />

to energizing the unit.<br />

e) Position the conductors in the switchboard enclosure so they are not<br />

subject to physical damage. If any conductors are in contact with<br />

structural members, place suitable protective material at the contact<br />

point to protect the cable insulation.<br />

13


482<br />

483<br />

484<br />

485<br />

486<br />

487<br />

488<br />

489<br />

490<br />

491<br />

492<br />

493<br />

494<br />

495<br />

496<br />

497<br />

498<br />

499<br />

500<br />

501<br />

502<br />

503<br />

504<br />

505<br />

506<br />

507<br />

508<br />

509<br />

510<br />

511<br />

512<br />

513<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

f) NEC Section 300.20(a) requires that all phase and grounded<br />

conductors of the same circuit pass through the same metal opening<br />

together. Otherwise, a magnetic loop will be created causing<br />

overheating within the switchboard.<br />

g) Where required, brace or lace the conductors in accordance with the<br />

manufacturer’s instructions or consulting engineer’s specification.<br />

h) Train cables within wire gutters of switchboards in a neat and<br />

workmanlike manner.<br />

3.14 Cable Terminations<br />

Terminating and tightening cable connections to the manufacturer’s<br />

recommended torque is imperative for a satisfactory connection. Follow these<br />

steps when terminating conductors at the switchboard:<br />

a) Strip a sufficient length of insulation from the cable end to fit into the<br />

full length of the lugs barrel. Use a proper insulation stripping tool to<br />

avoid nicking conductor strands. Stripping cable too long should be<br />

avoided since the through-air clearance could be reduced below the<br />

minimums required by the NEC.<br />

b) Mechanical lugs (set-screw type) are the most common type of<br />

connector furnished with switchboards. Torque these lugs in<br />

accordance with the manufacturer’s recommendations to avoid<br />

stripping threads or cracking the lug body.<br />

c) When compression lugs are used to terminate aluminum conductors,<br />

remove oxides from the conductors and apply an anti-oxidant<br />

compound to the aluminum conductor before inserting into the lug<br />

body. Oxides on aluminum conductors are poor conductors and will<br />

cause abnormal heating at the connection.<br />

d) Remove compression lugs from their point of termination in order to<br />

crimp them onto cables. Follow the manufacturer’s recommendation<br />

as to the proper number of crimps and their position on the lug. Use<br />

the recommended sealant. Re-install the crimp lugs to the lug pad and<br />

toque the hardware used with the lugs.<br />

14


514<br />

515<br />

516<br />

517<br />

518<br />

519<br />

520<br />

521<br />

522<br />

523<br />

524<br />

525<br />

526<br />

527<br />

528<br />

529<br />

530<br />

531<br />

532<br />

533<br />

534<br />

535<br />

536<br />

537<br />

538<br />

539<br />

540<br />

541<br />

542<br />

543<br />

544<br />

545<br />

546<br />

547<br />

548<br />

549<br />

550<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

4. Pre-Energizing Checkout Procedure<br />

4.1 General<br />

Conduct a complete inspection of the switchboard before it is energized to<br />

ensure that the components within the switchboard function properly.<br />

a) Check all field installed bus bar connections for correct torque value.<br />

b) Check all accessible connections for tightness.<br />

c) Check all factory and field installed lug terminations for the correct<br />

torque value.<br />

d) Visually check the bussing insulators for cracks and supports for<br />

damage.<br />

e) Check to insure that dents or other damage to the enclosure have not<br />

resulted in clearances that violate NEC requirements.<br />

f) Remove foam blocks, packing material, and temporary cushioning<br />

from the switchboard and components inside the switchboard.<br />

g) Check all relays, meters and instrumentation device wiring and<br />

terminations.<br />

4.2 Insulation Test<br />

Perform a direct current (DC) insulation test on the switchboard and record the<br />

value for future maintenance tests; a switchboard insulation resistance chart is<br />

shown in Section 9. Values less than 1 megohm are typically unacceptable.<br />

Prior to this test, remove control power fuses and any other equipment that<br />

should not be subjected to this level of potential.<br />

4.3 Current Transformers<br />

Ensure that current transformers secondary terminals are connected to a load or<br />

are shorted together using shorting straps or terminal block shorting screws.<br />

CAUTION: Open secondary terminals may have high voltages, which could be a<br />

hazard to people or equipment.<br />

The shortening means are removed when the current transformers operate<br />

normally with their intended load.<br />

4.4 Circuit Breakers and Fusible Switches<br />

a) Manually open and close all circuit breakers and fusible switches to<br />

ensure proper operation.<br />

b) Adjust the magnetic trip on thermal magnetic circuit breakers to their<br />

proper setting based on the system study or switchboard schedule. A<br />

15


551<br />

552<br />

553<br />

554<br />

555<br />

556<br />

557<br />

558<br />

559<br />

560<br />

561<br />

562<br />

563<br />

564<br />

565<br />

566<br />

567<br />

568<br />

569<br />

570<br />

571<br />

572<br />

573<br />

574<br />

575<br />

576<br />

577<br />

578<br />

579<br />

580<br />

581<br />

582<br />

583<br />

584<br />

585<br />

586<br />

587<br />

588<br />

589<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

setting too low for a load that has a high peak inrush current will trip<br />

the circuit breaker on start-up.<br />

c) Electronic circuit breakers have functions such as long-time,<br />

instantaneous, short-time, and ground fault, that requires initial<br />

adjustment. Settings typically are provided in a coordination study<br />

prepared by the consulting engineer, or other persons responsible for<br />

the switchboard set-up.<br />

NOTE: These values typically are not found on the drawings supplied by the<br />

switchboard manufacturer.<br />

If values are not provided, consult the manufacturer’s circuit breaker<br />

instruction manual for values that will set the electronic circuit breaker<br />

functions to emulate thermal magnetic circuit breaker characteristics.<br />

4.5 Ground-fault Protection<br />

a) The trip and time-delay on ground-fault protective equipment are<br />

typically set by the manufacturer at their lowest settings. Adjust these<br />

settings based on information provided in a coordination study<br />

prepared by the consulting engineer, or other persons responsible for<br />

the switchboard set-up.<br />

b) Some ground-fault protection systems require field connections at the<br />

job site. Consult the switchboard interconnection wiring diagram for<br />

details.<br />

c) Check the ground-fault circuitry and establish that there are no<br />

grounds on the neutral downstream from the service entrance point.<br />

d) The NEC requires that the ground-fault protection system be<br />

performance tested when first installed, and that a written record of this<br />

test be available to the AHJ. A testing group with experience in<br />

switchboard ground-fault testing should perform an injection test.<br />

4.6 Interconnections<br />

Verify that all interconnecting wiring between switchboard sections has been<br />

connected.<br />

4.7 Power Fuses and Control Power Disconnects<br />

Replace all control power fuses removed in the Insulation Test (see Section 4.2)<br />

and turn on all control power disconnects.<br />

4.8 Clean-up<br />

Vacuum all scrap, wire, dust and other debris from the switchboard. Do not use<br />

compressed air to blow debris out of the switchboard, since debris may, instead,<br />

settle inside devices and impair their ability to function.<br />

16


590<br />

591<br />

592<br />

593<br />

594<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

4.9 Close-up<br />

Replace all covers. Check for any pinched wires and close all doors. Make sure<br />

that the enclosure parts are properly aligned and fastened securely.<br />

17


595<br />

596<br />

597<br />

598<br />

599<br />

600<br />

601<br />

602<br />

603<br />

604<br />

605<br />

606<br />

607<br />

608<br />

609<br />

610<br />

611<br />

612<br />

613<br />

614<br />

615<br />

616<br />

617<br />

618<br />

619<br />

620<br />

621<br />

622<br />

623<br />

624<br />

625<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

5. Energizing the Switchboard<br />

WARNING: Arc flash, arc blast, and shock hazards exist when energizing<br />

switchboards. Switchboards should only be energized by qualified persons,<br />

following work practiced defined in the NFPA 70E.<br />

Hazards exist in energizing a switchboard; energizing should only be<br />

performed by qualified electrical personnel.<br />

If a short circuit or ground-fault condition exists, caused by damage or poor<br />

installation practices, and this is not detected and corrected during the check-out<br />

procedures, serious personal injury and/or damage to the switchboard can result<br />

when the switchboard is first energized. Follow the steps below to energize the<br />

switchboards; read all steps before proceeding.<br />

Step 1 Turn off all downstream loads. No load should be on the<br />

switchboard when it is first energized.<br />

Step 2 Use remote operators, if available, to close devices and energize<br />

switchboards and loads for the first time.<br />

Step 3 Prior to energizing any circuit that supplies rotating machinery,<br />

verify that the phase sequence is correct. Serious damage can<br />

result to motors and similar equipment rotating in the wrong<br />

direction.<br />

Step 4 One by one, close each circuit breaker or fusible switch in the<br />

switchboard.<br />

Step 5 Proceed to energize (turn on) the downstream loads (lighting<br />

circuits, contactors, heaters, motors, etc.) one at a time.<br />

18


626<br />

627<br />

628<br />

629<br />

630<br />

631<br />

632<br />

633<br />

634<br />

635<br />

636<br />

637<br />

638<br />

639<br />

640<br />

641<br />

642<br />

643<br />

644<br />

645<br />

646<br />

647<br />

648<br />

649<br />

650<br />

651<br />

652<br />

653<br />

654<br />

655<br />

656<br />

657<br />

658<br />

659<br />

660<br />

661<br />

662<br />

663<br />

664<br />

665<br />

666<br />

667<br />

668<br />

669<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

6. Switchboard Maintenance<br />

Periodic maintenance of switchboards extends service life and increases<br />

reliability. Cleaning, inspection, maintenance, and testing should only be<br />

performed by qualified personnel on switchboards to which power has been<br />

turned-off, disconnected, and electrically isolated, unless required for testing, so<br />

that no accidental contact can be made with energized parts. Follow all<br />

manufacturer’s warnings and instructions.<br />

The interval between maintenance checks varies depending on the environment,<br />

such as ambient temperature and conditions in the switchboard room, and usage<br />

of the equipment. Perform routine inspections, such as making limited visual<br />

observations and recording operational data, periodically with switchboards<br />

energized and in service.<br />

Perform cleaning, inspections, maintenance and testing of switchboards at least<br />

annually, but as often as the operating environment requires keeping<br />

switchboards clean. Perform the first inspection and maintenance no more than<br />

one year after the original installation. Plan cleaning, inspections, maintenance<br />

and testing to minimize outages.<br />

Clean, inspect, maintain, and test switchboards following any unusual operating<br />

condition, such as whenever an overcurrent protective device opens, or a phaseto-phase<br />

short circuit or ground-fault occurs (see Section 7.1), in accordance with<br />

manufacturer recommendations.<br />

6.1 Routine Inspections<br />

Inspect areas and spaces around switchboards for any accumulation of dirt or<br />

dust. Remove any accumulations of dirt or dust. Remove trash, combustible<br />

material, and other debris from areas around switchboards. Use the rate of<br />

accumulation of dust and moisture on visible surfaces as a guide for scheduling<br />

cleaning, inspections, maintenance, and testing.<br />

Inspect switchboards for external signs of overheating. Measure and record the<br />

ambient temperature. Check equipment installed near switchboards that might<br />

be an external source of heat. Eliminate external sources of heat to<br />

switchboards. Check the operating temperature of switchboards that have been<br />

operating under normal load and at normal ambient temperature for a minimum<br />

of 3 hours by measuring the surface temperature of switchboard access covers,<br />

doors, circuit breakers and switches. If the temperature exceeds manufacturer<br />

recommendations, de-energize switchboard and investigate sources of<br />

overheating.<br />

Record switchboard voltage and load currents, if equipped with meters, noting<br />

the date and time of day. Provide comments regarding known causes of<br />

variations in loading, such as load additions or equipment maintenance outages.<br />

19


670<br />

671<br />

672<br />

673<br />

674<br />

675<br />

676<br />

677<br />

678<br />

679<br />

680<br />

681<br />

682<br />

683<br />

684<br />

685<br />

686<br />

687<br />

688<br />

689<br />

690<br />

691<br />

692<br />

693<br />

694<br />

695<br />

696<br />

697<br />

698<br />

699<br />

700<br />

701<br />

702<br />

703<br />

704<br />

705<br />

706<br />

707<br />

708<br />

709<br />

710<br />

711<br />

712<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

Check all accessible exterior switchboard hardware for tightness.<br />

Visually inspect enclosures for physical damage. Repair physical damage, if<br />

practical and as approved by the manufacturer. Consult owner and switchboard<br />

manufacturer for recommendations for suitable protective barriers to prevent<br />

future damage.<br />

Inspect areas and spaces around switchboards for evidence of water or<br />

moisture. Eliminate sources of water or moisture, or provide suitable protection<br />

for switchboards from sources of water.<br />

6.2 Safety Procedures<br />

Before cleaning, inspecting, testing, or maintaining, de-energize and electrically<br />

isolate equipment in accordance with established procedures. Consider all<br />

circuits live until they are confirmed to be de-energized by testing and are locked<br />

out of operation. Do not work on energized equipment. Guard energized<br />

conductors and equipment in close proximity to work. Failure to observe these<br />

precautions may result in severe personal injury or death.<br />

Personnel working on or near energized switchboards should follow the safe<br />

work practices described in NFPA 70E, including the use of personal protective<br />

equipment (PPE) appropriate for the task being performed.<br />

Apply lockout/tagout procedures in accordance with documented and established<br />

policies and practices. Render electrical circuit conductors and circuit parts<br />

electrically safe by removing all sources of energy by opening all upstream<br />

source disconnecting means, locking and tagging out all source disconnecting<br />

means, verifying the absence of voltage using an approved voltage testing<br />

device, and guarding any exposed energized components.<br />

Remove the front cover of the switchboard and attach grounding leads to the line<br />

terminals of the main circuit breaker or main lugs, to the neutral terminal bus bar,<br />

if so equipped, and to the grounding terminal.<br />

6.3 Cleaning and Inspections<br />

Consult manufacturer recommendations for cleaning and inspecting<br />

switchboards and components. De-energize switchboards in accordance with<br />

Section 6.2 prior to performing any cleaning or inspections.<br />

Visually inspect switchboards for evidence of discoloration, abnormal dust<br />

accumulation, metal shards, or any other indication of overheating, wear, or other<br />

abnormal conditions prior to cleaning.<br />

Visually inspect the switchboard for signs of overheating. Discoloration and<br />

flaking of insulation or metal parts are indications of possible overheating.<br />

20


713<br />

714<br />

715<br />

716<br />

717<br />

718<br />

719<br />

720<br />

721<br />

722<br />

723<br />

724<br />

725<br />

726<br />

727<br />

728<br />

729<br />

730<br />

731<br />

732<br />

733<br />

734<br />

735<br />

736<br />

737<br />

738<br />

739<br />

740<br />

741<br />

742<br />

743<br />

744<br />

745<br />

746<br />

747<br />

748<br />

749<br />

750<br />

751<br />

752<br />

753<br />

754<br />

755<br />

756<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

Correct conditions that cause the overheating, and replace the affected parts<br />

before re-energizing the switchboard.<br />

Vacuum the inside of switchboards to remove any debris, dirt, or dust that has<br />

accumulated, noting anything unusual such as signs of insects or rodent activity<br />

or moisture. Avoid blowing dust into switchboards. Do not use a blower or<br />

compressed air. Maintain adequate ventilation during cleaning.<br />

Wipe bus bars, insulators, conductors and other parts with a clean, dry lint-free<br />

cloth. Do not use chemicals or petroleum-based solvents that may degrade<br />

plastics or insulating materials.<br />

Visually inspect the inside of the switchboard for moisture, condensation build-up<br />

or signs of any previous wetness. Moisture causes insulation failures and rapid<br />

oxidation of current carrying parts. Pay particular attention to conduit entrances<br />

and the top of the switchboard between sections. Remove any moisture present<br />

inside the switchboard and seal off all leaks. Replace any components that show<br />

evidence of damage from moisture.<br />

Carefully inspect all switchboard devices for any worn-out, cracked or missing<br />

parts. Inspect terminations, connections, and lugs for alignment, physical<br />

damage, burns, corrosion, discoloration, flaking, heat damage, arcing, pitting,<br />

melting, deterioration, carbonization, cracks, chips, breaks, partial discharge, or<br />

moisture. Replace damaged components. Investigate and eliminate sources of<br />

damage.<br />

Plated parts may become dark over a period of time due to oxidation. Removing<br />

this discoloration will reduce the thickness of the plating. Consult the<br />

manufacturer for recommendations regarding discoloration of parts.<br />

Verify that all key interlocks and door interlocking provisions are working<br />

properly.<br />

6.4 Maintenance and Testing<br />

Consult manufacturer recommendations for maintaining and testing switchboards<br />

and components. De-energize switchboards in accordance with Section 6.2 prior<br />

to performing any maintenance or testing.<br />

6.4.1 Infrared Scan<br />

After cleaning and inspecting switchboards and components in accordance with<br />

Section 6.3, perform an infrared scan in accordance with switchboard and test<br />

equipment manufacturer recommendations. With the switchboard de-energized,<br />

remove accessible covers, plates, weathershields, etc. Provide supplemental<br />

barriers and safety precautions during infrared scan to prevent accidental contact<br />

with exposed energized components. Personnel working on or near energized<br />

switchboards should follow the safe work practices described in NFPA 70E,<br />

21


757<br />

758<br />

759<br />

760<br />

761<br />

762<br />

763<br />

764<br />

765<br />

766<br />

767<br />

768<br />

769<br />

770<br />

771<br />

772<br />

773<br />

774<br />

775<br />

776<br />

777<br />

778<br />

779<br />

780<br />

781<br />

782<br />

783<br />

784<br />

785<br />

786<br />

787<br />

788<br />

789<br />

790<br />

791<br />

792<br />

793<br />

794<br />

795<br />

796<br />

797<br />

798<br />

799<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

including the use of personal protective equipment (PPE) appropriate for the task<br />

being performed.<br />

Energize the switchboard in accordance with Section 6.6, and turn on all normal<br />

loads supplied by the switchboard. Perform an infrared scan of all switchboard<br />

electrical connections and terminals while energized and operating under normal<br />

load conditions.<br />

Use an infrared scanning device designed to measure actual operating<br />

temperatures, or designed to detect significant deviations from surrounding<br />

conditions. Provide documentation of device calibration.<br />

Prepare a certified report identifying the switchboard tested and describing the<br />

results of the infrared scan. Include notations of deficiencies detected, remedial<br />

actions taken, and results from retesting after remedial actions.<br />

Consult switchboard manufacturer for repair or replacement recommendations if<br />

infrared scan results indicate overheating of components.<br />

De-energize the switchboard in accordance with Section 6.2.<br />

6.4.2 Bus Bar Joints<br />

Consult the manufacturer’s recommendations concerning bus bar joints and retorque<br />

where required. Some switchboard bus bar joints are maintenance-free.<br />

Additional tightening after installation may degrade these connections.<br />

Replace parts that show indications of pitting, corrosion, discoloration or<br />

annealing due to overheating. Do not use abrasive materials on bus bar joints.<br />

Use hardware and washers of a grade identical to or better than the hardware<br />

replaced.<br />

6.4.3 Molded-Case Circuit Breakers<br />

a) Clean circuit breaker surfaces. Remove dust, soot, grease, moisture, and<br />

foreign material.<br />

b) Operate circuit breakers several times to exercise the mechanism and<br />

contacts, and to ensure smooth operation. Many circuit breakers have a<br />

test feature which trips, exercises and lubricates the mechanism. This<br />

method of exercising circuit breakers should be used if available. If<br />

unavailable, operate circuit breakers manually. Do not oil or grease parts<br />

of molded case circuit breakers. Replace circuit breakers that do not<br />

operate smoothly.<br />

c) Check circuit breakers for visual defects, chips, cracks, breaks, burns, and<br />

deterioration. Visually check circuit breakers for evidence of overheating<br />

22


800<br />

801<br />

802<br />

803<br />

804<br />

805<br />

806<br />

807<br />

808<br />

809<br />

810<br />

811<br />

812<br />

813<br />

814<br />

815<br />

816<br />

817<br />

818<br />

819<br />

820<br />

821<br />

822<br />

823<br />

824<br />

825<br />

826<br />

827<br />

828<br />

829<br />

830<br />

831<br />

832<br />

833<br />

834<br />

835<br />

836<br />

837<br />

838<br />

839<br />

840<br />

841<br />

842<br />

843<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

and thermal damage. Investigate and eliminate sources of overheating.<br />

Replace damaged circuit breakers.<br />

d) For circuit breakers that use solid-state circuitry or a microprocessor, run<br />

the self-diagnostic program, if available. For electronic circuit breakers,<br />

use the test set to run trip unit test automatically with user prompts.<br />

Repair or replace circuit breakers in accordance with manufacturer<br />

recommendations.<br />

6.4.4 Bolted Pressure Switches<br />

Exercise bolted pressure switch operating mechanisms. Check the cover<br />

interlock with the switch in the “on” position. The cover should not open using<br />

normal hand force. Lubricate parts using materials and methods in accordance<br />

with manufacturer’s recommendations.<br />

6.4.5 Fusible Switches<br />

a) Thoroughly clean fusible switches inside and outside. Clean contact<br />

areas of fuses and fuse holders. Wipe insulating areas of fuses with a<br />

clean, dry, lint-free cloth.<br />

b) Operate each switch several times to ensure that all mechanisms are free<br />

and in proper working order. Check switches for damaged or broken<br />

parts, free movement, corrosion, dirt, and excessive wear. Verify proper<br />

blade penetration, travel stops, and mechanical operation. Repair or<br />

replace switches in accordance with manufacturer recommendations.<br />

c) Inspect contact surfaces, blades, and jaws for discoloration, overheating,<br />

pitting, arcing, and corona. Inspect arc chutes. Clean and dress readily<br />

accessible copper electrical contacts, blades, and jaws in accordance with<br />

manufacturer recommendations. Repair or replace burned contacts.<br />

Many contact surfaces, such as arcing contacts, are silver tungsten or<br />

other types of materials that must never be dressed. When contacts of<br />

these materials require maintenance, they must be replaced. If contact<br />

clips have lost their tension, replace clips or replace the switch. Consult<br />

the manufacturer for recommendations.<br />

d) Tighten fuse holder connections in accordance with manufacturer<br />

recommendations. Inspect each fuse holder to determine whether it<br />

seems to be adequately supporting the fuse and that the fuse holder is<br />

securely attached to the mounting base. Inspect fuse clips for<br />

discoloration, overheating, corrosion, or physical damage. Replace weak<br />

or burned clips. Install new fuse clips and suitable clamps. Use<br />

manufacturer’s replacement parts.<br />

e) Lubricate operating mechanisms and sliding contact surfaces, if required,<br />

according to manufacturer’s instructions. If no instructions are given on<br />

23


844<br />

845<br />

846<br />

847<br />

848<br />

849<br />

850<br />

851<br />

852<br />

853<br />

854<br />

855<br />

856<br />

857<br />

858<br />

859<br />

860<br />

861<br />

862<br />

863<br />

864<br />

865<br />

866<br />

867<br />

868<br />

869<br />

870<br />

871<br />

872<br />

873<br />

874<br />

875<br />

876<br />

877<br />

878<br />

879<br />

880<br />

881<br />

882<br />

883<br />

884<br />

885<br />

886<br />

887<br />

888<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

the devices, sliding copper contacts, operating mechanisms, and<br />

interlocks may be lubricated with clean, light grease. Wipe off excess<br />

lubrication to avoid contamination.<br />

f) Check the cover interlock with the switch in the “on” position. The cover<br />

should not open using normal hand force. Inspect switches for any<br />

damaged or broken parts. Check the fuse mounting clips or bolted<br />

contact area for corrosion or discoloration due to overheating. Replace<br />

damaged or broken parts as necessary.<br />

6.4.6 Inspecting and Replacing Fuses<br />

Ensure that equipment is de-energized before inspecting and replacing fuses.<br />

Test line and load terminals of switches for the presence of voltage before<br />

replacing fuses. Turn the switches to the “off” position before opening the door.<br />

Do not defeat cover interlocks to gain access to fuses.<br />

Visually inspect switch blades to verify that all blades are disconnected from the<br />

line connections. Consult the manufacturer for recommendations when blades<br />

do not disconnect from line connections.<br />

a) Check all fuses to assure that the correct type and rating are installed.<br />

Where renewable fuses are used, examine fuse links to ensure that the<br />

correct link is installed.<br />

NOTE: Certain switchboard manufacturers do not recommend the use of<br />

renewable link fuses in their equipment.<br />

b) Look for fuses that have been bridged with wire, metal strips, disks, or<br />

appear to have been forced or hammered in, etc. Replace with correct<br />

fuses and consult the manufacturer for recommendations for preventing a<br />

recurrence.<br />

c) Look for evidence of overheating of cartridge fuses. Replace fuses having<br />

discolored or weakened casings. Investigate the cause of overheating.<br />

d) Inspect ferruled or knife blades of cartridge fuses for corrosion or<br />

oxidation. Clean and polish contact surfaces. Clean surfaces with a noncorrosive<br />

cleaning agent. Plated parts may become dark over a period of<br />

time due to oxidation. Removing this discoloration will reduce the<br />

thickness of the plating. Consult the manufacturer for recommendations<br />

regarding discoloration of parts.<br />

e) Measure fuse resistance. Investigate fuse-resistance values that deviate<br />

from each other by more than 15 percent. Replace defective or partiallyburned<br />

fuses. Re-tighten plug fuses.<br />

24


889<br />

890<br />

891<br />

892<br />

893<br />

894<br />

895<br />

896<br />

897<br />

898<br />

899<br />

900<br />

901<br />

902<br />

903<br />

904<br />

905<br />

906<br />

907<br />

908<br />

909<br />

910<br />

911<br />

912<br />

913<br />

914<br />

915<br />

916<br />

917<br />

918<br />

919<br />

920<br />

921<br />

922<br />

923<br />

924<br />

925<br />

926<br />

927<br />

928<br />

929<br />

930<br />

931<br />

932<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

f) Replace fuses with fuses of like types and ratings. Ensure that noncurrent-limiting<br />

devices are not used as replacements for current-limiting<br />

devices. Do not defeat any rejection feature in any switchboard fusible<br />

device.<br />

6.4.7 Ground-Fault Protection Systems<br />

a) Check the torque of terminal connections on ground-fault protection<br />

systems annually. Inspect for corrosion and for physical, thermal, and<br />

electrical damage. Replace any damaged components.<br />

b) Test the ground-fault protection system in accordance with manufacturer<br />

recommendations. Testing may be conducted with or without tripping<br />

main or branch overcurrent protective devices. Testing with trip is<br />

preferable since it ensures the whole system is functioning. Energize the<br />

switchboard in accordance with Section 6.6 prior to testing.<br />

c) If the ground-fault protection system does not operate properly and<br />

additional equipment has been connected to the installation since the last<br />

maintenance test/check, de-energize the entire system in accordance with<br />

Section 6.2, disconnect the main bonding jumper, and check for continuity<br />

between the neutral and ground on the load-side of the main bonding<br />

jumper. If grounds are found, remove them and test again. If no grounds<br />

are detected and the ground-fault protection system is still not functioning<br />

properly, consult the switchboard manufacturer for recommendations.<br />

d) If the ground-fault protection system does not operate properly and no<br />

additional equipment has been connected to the installation since the last<br />

maintenance test/check, check the devices for physical or electrical<br />

damage and replace accordingly. Check wiring for damage or loose<br />

connections and correct any problems found. Consult the switchboard<br />

manufacturer for recommendations.<br />

6.5 Insulation Resistance Test<br />

Perform an insulation resistance test on switchboards using a 1000 V dc<br />

megohmmeter. Disconnect all accessories and electronic devices that may be<br />

subjected to the test voltage. Test from phase-to-ground and from phase-tophase<br />

with all switches and circuit breakers in both the open and closed<br />

positions, all instrumentation and control fuses removed, and no loads connected<br />

to the switchboard. Ground all phases not being tested. Connect megohmmeter<br />

between each phase and ground and between each phase. Measure insulation<br />

resistance at one minute intervals following the application of the test voltage.<br />

Record the megohm values of each phase and between each phase, along with<br />

the description of the instrument, voltage level, humidity, temperature, time, and<br />

date of the test. Consult switchboard manufacturer's published data for<br />

acceptable test results. If published data is not available, investigate any values<br />

25


933<br />

934<br />

935<br />

936<br />

937<br />

938<br />

939<br />

940<br />

941<br />

942<br />

943<br />

944<br />

945<br />

946<br />

947<br />

948<br />

949<br />

950<br />

951<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

that deviate from previous test results under similar conditions by more than 50<br />

percent of the lowest value. Investigate any results less than 1 megohm with the<br />

overcurrent protective devices in the open position for possible tracking on<br />

insulation or insulation breakdown. Ground each phase at the completion of the<br />

test. Maintain records of testing for future reference.<br />

6.6 Re-energizing Switchboards<br />

Energize switchboards in accordance with Section 5. Remove grounding leads<br />

from the line terminals of the switchboard. Visually inspect the system to ensure<br />

that all tools, electrical jumpers, test devices, etc., have been removed. Visually<br />

inspect equipment and areas around equipment to ensure that all persons are<br />

clear from circuits and equipment to be re-energized. Remove locks and tags<br />

only after work is complete and tested, and all personnel are clear of the area.<br />

Test for short circuits or ground faults. Energize circuits using established<br />

switching procedures. Close disconnect means starting at the source, working<br />

towards the load. Measure phase-to-phase and phase-to-neutral voltages, if<br />

applicable. Investigate source of voltage unbalance greater than 3 percent.<br />

Measure switchboard feeder and branch load currents. Verify that conductors<br />

are properly sized and protected for actual loading.<br />

26


952<br />

953<br />

954<br />

955<br />

956<br />

957<br />

958<br />

959<br />

960<br />

961<br />

962<br />

963<br />

964<br />

965<br />

966<br />

967<br />

968<br />

969<br />

970<br />

971<br />

972<br />

973<br />

974<br />

975<br />

976<br />

977<br />

978<br />

979<br />

980<br />

981<br />

982<br />

983<br />

984<br />

985<br />

986<br />

987<br />

988<br />

989<br />

990<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

7. Adverse Circumstances<br />

Special procedures are necessary to determine whether a switchboard can<br />

safely remain in service following a short-circuit, ground-fault, or exposure to<br />

water.<br />

7.1 Inspection Following a Short-Circuit or Ground-Fault<br />

Condition<br />

Do not attempt to re-energize a switchboard following a short-circuit or groundfault<br />

condition within the switchboard. Do not re-energize a feeder or branch<br />

overcurrent protection device in the switchboard that has opened due to a short<br />

circuit or ground-fault until the problem downstream has been corrected.<br />

Following a short-circuit or ground-fault within a switchboard, inspect the<br />

equipment thoroughly as described in Section 6.1 to verify that damage has not<br />

occurred to conductors or insulators within the switchboard.<br />

NOTE: The insulating properties of some organic insulating materials may<br />

deteriorate during an electrical arc. Replacement of the damaged insulating<br />

material is the only remedy.<br />

7.1.1 Short-circuits develop high mechanical stresses that can<br />

damage conductors and insulation<br />

Improper and loosened connections may result in conductors pulling out of their<br />

terminations on subsequent short-circuits; for this reason all connections should<br />

be inspected and, if necessary, re-evaluated. Great care must be taken in<br />

evaluating the cause of the short-circuit. Do not replace the fuse(s) and turn the<br />

overcurrent protective device back on, or reset the circuit breaker, without first<br />

determining whether it is safe to energize the circuit. Phase-to-phase shortcircuits<br />

that originate on bus bars can travel the length of the bussing system<br />

through the switchboard, and the greatest damage may not occur where the<br />

arcing condition originated. Conduct an insulation test to determine the integrity<br />

of the switchboard insulation prior to re-energizing the switchboard.<br />

7.1.2 Ground-faults are unintentional current paths between a phase<br />

conductor and ground<br />

Depending on the magnitude of the ground-fault and its duration, carbon build-up<br />

and metallic splatter may need to be removed, insulators cleaned or replaced.<br />

Perform phase-to-phase and phase-to-ground insulation tests, with a minimum<br />

reading of one megohm, prior to turning the switchboard power back on.<br />

27


991<br />

992<br />

993<br />

994<br />

995<br />

996<br />

997<br />

998<br />

999<br />

1000<br />

1001<br />

1002<br />

1003<br />

1004<br />

1005<br />

1006<br />

1007<br />

1008<br />

1009<br />

1010<br />

1011<br />

1012<br />

1013<br />

1014<br />

1015<br />

1016<br />

1017<br />

1018<br />

1019<br />

1020<br />

1021<br />

1022<br />

1023<br />

1024<br />

1025<br />

1026<br />

1027<br />

1028<br />

1029<br />

1030<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

7.2 Replacing a Switchboard Soaked by or Submerged Under<br />

Water<br />

a) Do not work on energized electrical equipment when standing in water.<br />

b) Do not energize a switchboard that is wet.<br />

c) Do not clean or repair a switchboard that has been exposed to large volumes<br />

of water or submerged. Current-carrying parts, insulation systems, and<br />

electrical/electronic components may be damaged beyond repair through<br />

contamination by chemicals, river or creek water, sewage and other<br />

pollutants. In this event, replace the switchboard rather than attempt to repair<br />

it.<br />

7.3 Inspecting and Re-Energizing a Switchboard Sprayed or<br />

Splashed with Clean Water<br />

Apply heat (a minimum of 250 watts per section) to the switchboard to dry it out<br />

until visible signs of dampness cannot be seen. Remove materials that could<br />

catch fire prior to applying the heat. Consult the manufacturer’s<br />

recommendations for specific guidelines on how to insure that it is safe to reenergize<br />

the switchboard, or follow this procedure.<br />

7.3.1 Preliminary Inspection<br />

Follow the steps in Section 7.3.2 to re-energize the switchboard only if a<br />

preliminary inspection verifies that the following conditions are satisfied:<br />

a) There are no signs of physical damage to the equipment.<br />

b) The switchboard has not been soaked or submerged in water.<br />

c) The water that has been in contact with the switchboard has not been<br />

contaminated with sewage, chemicals or other substances.<br />

d) Water has not entered any area of the switchboard enclosure that contains<br />

wiring, and has not come into contact with any live part. Look for water<br />

entering through conduits.<br />

If all of the conditions listed above are satisfied, proceed as follows.<br />

7.3.2 Cleaning, testing, and re-energizing a switchboard<br />

Step 1 Completely de-energize and electrically isolate the switchboard so<br />

that contact cannot be made with energized parts.<br />

Step 2 Wipe off all moisture from bus bars, insulators, and insulating<br />

materials with a clean, dry, lint free cloth. Never use cleaning<br />

agents or sprays unless specifically recommended by the<br />

switchboard manufacturer.<br />

Step 3 Prepare the switchboard for an insulation resistance test by<br />

disconnecting all line-side supply conductors and all load-side<br />

28


1031<br />

1032<br />

1033<br />

1034<br />

1035<br />

1036<br />

1037<br />

1038<br />

1039<br />

1040<br />

1041<br />

1042<br />

1043<br />

1044<br />

1045<br />

1046<br />

1047<br />

1048<br />

1049<br />

1050<br />

1051<br />

1052<br />

1053<br />

1054<br />

1055<br />

1056<br />

1057<br />

1058<br />

1059<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

conductors to isolate the switchboard from the wiring system. Turn<br />

all circuit breakers or fusible switches to the “ON” position. Voltage<br />

cannot be present on the switchboard during the insulation<br />

resistance test.<br />

Step 4 Use a DC insulation resistance tester with a capacity of 500-1000<br />

volts DC to perform phase-to-ground and phase-to-phase insulation<br />

tests.<br />

NOTE: Use of an AC dielectric tester is not recommended.<br />

a) Measure each phase (A, B, C) to ground with the circuit<br />

breakers or fusible switches “ON”.<br />

b) Measure each phase to another phase with the circuit breakers<br />

or fusible switches “ON”. Record the values of the insulation<br />

resistance on the insulation resistance chart shown in Section 9.<br />

Step 5 Do not re-energize the equipment if any of the resistance<br />

measurements are not at least one megohm. If moisture is the<br />

cause of the low resistance readings, the moisture can be removed<br />

from the switchboard by providing a minimum of 250 watts of heat<br />

per vertical section.<br />

Step 6 If the resistance measurements are greater than 0.5 megohom, the<br />

equipment can be re-energized.<br />

29


1060<br />

1061<br />

1062<br />

1063<br />

1064<br />

1065<br />

1066<br />

1067<br />

1068<br />

1069<br />

1070<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

8. Recommended Torque Values<br />

If the switchboard manufacturer does not provide specific torque<br />

recommendations, use the following as a guide.<br />

30


1071<br />

1072<br />

1073<br />

1074<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

31


1075<br />

1076<br />

1077<br />

1078<br />

1079<br />

1080<br />

1081<br />

1082<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

9. Switchboard Insulation Resistance Chart<br />

NOTE: The use of an AC dielectric tester for testing the switchboard is not<br />

recommended. Use an insulation resistance tester with a capacity of 500-1000<br />

VDC.<br />

32


1083<br />

1084<br />

1085<br />

1086<br />

1087<br />

1088<br />

1089<br />

1090<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

10. Operations and Maintenance Documents<br />

This standard refers to manufacturer’s packing label warnings (2.1a), instruction<br />

manuals, literature, drawings (Section 3), recorded values of tests (4.2, 7.3.2, 9),<br />

and set values of adjustable trips (4.4 and 4.5a, 4.5d). This material, plus asbuilt<br />

drawings, should be assembled, identified and delivered to the owner of the<br />

facility at the completion of the installation.<br />

33


1091<br />

1092<br />

1093<br />

1094<br />

1095<br />

1096<br />

1097<br />

1098<br />

1099<br />

1100<br />

<strong>NECA</strong> <strong>400</strong>-<strong>200X</strong> – Reballot Draft<br />

(This appendix is not part of the standard)<br />

Appendix A: Reference Standards<br />

This publication, when used in conjunction with the National Electrical Code and<br />

switchboard manufacturer’s literature, provides sufficient information to install<br />

and maintain deadfront switchboards operating at 600 volts and less. The<br />

following publications may also provide useful information:<br />

<strong>NECA</strong> will insert the list at publication.<br />

34

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!