n The Function Block number. This can span from 1 to 32 <strong>for</strong> all types of function<br />

blocks.<br />

Note: String16 has always a maximum length of 16 bytes.<br />

4.8 Protdir.dbf<br />

TAG FILE BIT_BLOCK MAX_LENGTH OPTIONS<br />

DANBUSS DANBUSS 16 256 0x0B47<br />

4.9 Parameters and INI options<br />

4.9.1 Standard Parameters<br />

Block 16 (<strong>Citect</strong> blocking is prohibited)<br />

Delay 250 ms<br />

MaxPending 75<br />

Polltime 100 ms<br />

Timeout 5000 ms<br />

Retry 2<br />

WatchTime 30 s<br />

4.9.2 <strong>Driver</strong> Specific Parameters<br />

All DANBUSS specific parameters are located in the section ‘<strong>DanBuss</strong>’<br />

PARAMETER DEFAULT DESCRIPTION<br />

<strong>Driver</strong> Design <strong>Specification</strong><br />

CacheLiveTime 30000 (ms) The time a Cache Element should stay allocated from that a DCB<br />

has made access to it. When a Cache Element is allocated, it will<br />

always be updated with values from the device.<br />

RefreshInterval 3600 (s) The interval that is used to update ‘One Shot’ variables. Function<br />

Block ‘TIMCON’ is an example of a set of variables that will be updated<br />

with this interval.<br />

IdleSlowDown 6 The factor the ‘Delay’ is multiplied with when there are no high priority<br />

requests in the cache list. If all variables has been updated once,<br />

the time between DANBUSS request will increase to 6 x 250 ms =<br />

1,5 seconds (defaults), if nothing causes any cache element to get<br />

high priority.<br />

DHCAddress 0:10 The address of the <strong>Citect</strong> I/O-server. If set to a faulty value, it could<br />

cause the GateWay not to know where to send packets returning<br />

from the devices. The default address is the Danfoss standard DHC<br />

address.<br />

<strong>DanBuss</strong> <strong>DNIP</strong>.doc 22