<strong>Combustible</strong> <strong>Dust</strong> Explosion 7-<strong>76</strong><br />
<strong>FM</strong> <strong>Global</strong> Property Loss <strong>Prevention</strong> Data Sheets Page 17<br />
Fig. 7. Explosion diverter Fig. 8. Indoor installation <strong>of</strong> explosion diverter<br />
c) Ensure the abort-gate reset is manual. Automatic reset is not acceptable.<br />
2.3.3.3.8 Double-Dump Valve<br />
Provide an interlock to ensure both valves do not open simultaneously.<br />
2.3.3.3.9 Back-Blast Damper<br />
Fig. 9. High-speed abort gate<br />
This is essentially a check valve that is effective in stopping explosion propagation in the opposite direction<br />
<strong>of</strong> normal flow. Ensure the device is provided with an explosion vent downstream from the normal flow in<br />
the system.<br />