Miscellaneous<br />

Load Calculations<br />

APPENDIX A<br />

Rev. Jan 2011<br />

Application Manual – Liquid Cooled Generator Sets<br />

occur. This occurs when rapidly changing UPS input frequency results from a sudden<br />

transient load change on a generator set. During this transient event, static UPSs with<br />

solid–state bypass switches must break synch with the source and disable the bypass.<br />

RkW RkW = RkVA x RPF<br />

RkVA RkVA = (Output kVA x Recharge Rate) ÷ Efficiency<br />

RPF Running power factor as entered or default<br />

SkW SkW = RkW<br />

SkVA SkVA = RkVA<br />

SPF SPF = RPF<br />

AkW For 3 pulse, AkW = 2.5 x RkW<br />

For 6 pulse, AkW = 1.4 x RkW<br />

For 12 pulse, AkW = 1.1.5 x RkW<br />

With input filter, AkW = 1.15 x RkW for 6 and 12 pulse<br />

AkW = 1.40 x RkW for 3 pulse<br />

Ramps 1∅ Ramps = (RkVA x 1000) ÷ voltage<br />

3∅ Ramps = (RkVA x 1000) ÷ (voltage x 1.73)<br />

Described below are the types and calculations GenSize uses for the various<br />

miscellaneous loads:<br />

Welder Load Calculations<br />

RkW If RkVA entered: RkW = RkVA x RPF<br />

If Ramps entered: 1∅ RkW = (Ramps x voltage x RPF) ÷ 1000<br />

3∅ RkW = (Ramps x voltage x RPF x 1.73) ÷ 1000<br />

RkVA If Ramps entered: RkVA = RkW ÷ RPF<br />

RPF Running power factor as entered or default<br />

SkW SkW = RkW<br />

SkVA SkVA = SkW ÷ SPF<br />

PkW PkW = PkVA x SPF<br />

PkVA As entered, or 1∅ PkVA = (Pamps x voltage) ÷ 1000<br />

3∅ PkVA = (Pamps x voltage x 1.73) ÷ 1000<br />

SPF SPF = SkVA ÷ SkW<br />

AkW AkW = RkW<br />

Ramps 1∅ Ramps = (RkVA x 1000) ÷ voltage<br />

3∅ Ramps = (RkVA x 1000) ÷ (voltage x 1.73)<br />

General Receptacle Load Calculations<br />

RkW RkW = Entered kW<br />

RkVA RkVA = RkW ÷ RPF<br />

RPF Running power factor as entered or default<br />

SkW SkW = RkW<br />

SkVA SkVA = SkW ÷ SPF<br />

SPF SPF = RPF<br />

PkW PkW = RkW<br />

PkVA PkVA = RkVA<br />

AkW AkW = RkW<br />

Ramps 1∅ Ramps = (RkW x 1000) ÷ (voltage x RPF)<br />

3∅ Ramps = (RkW x 1000) ÷ (voltage x RPF x 1.73)<br />

User Defined Load Calculations<br />

RkW If kW entered: RkW = Kw<br />

If kVA entered: RkW = kVA x RPF<br />

If Ramps entered: 1∅ RkW = (Ramps x voltage x RPF) ÷ 1000<br />

3∅ RkW = (Ramps x voltage x RPF x 1.73) ÷ 1000<br />

RkVA If kW entered: RkVA = RkW ÷ RPF<br />

If RkVA entered: RkVA = kVA<br />

If Ramps entered: 1∅ RkVA = (Ramps x voltage) ÷ 1000<br />

3∅ RkVA = (Ramps x voltage x 1.73) ÷ 1000<br />

A–13