LINE<br />

FILTER<br />

22<br />

EMC-TECHNOLOGY<br />

Range 7 – 2 500 A and 230 – 690 V<br />

Line fi lter<br />

NF-K and NF-K-IT (Three-phase-fi lter)<br />

ADVANTAGES AT A GLANCE<br />

| Current ratings from 7 – 2500 A<br />

| High attenuation from 150 kHz to 30 Mhz<br />

| Small dimensions (bookstyle) and low weight<br />

| IP20 terminals<br />

| According European Standard EN 133200<br />

TECHNICAL DATA<br />

| Rated voltage: 480 VAC (NF-K), 690 VAC<br />

(NF-K-IT), 48 – 62 Hz<br />

| Rated current: 3-phase, 7 – 2500 A<br />

(see table)<br />

| Overload capability: 4-times rated current<br />

with the turning on, afterwards 1,5-times<br />

rated current for one minute, once per hour<br />

| Construction: according to EN 133200<br />

| Leakage current: see table<br />

| Construction: metal housing<br />

| Mounting: Fixing angles with holes<br />

| Ambient temperatur: 40°C<br />

(50°C without power reduction)<br />

| Terminals: Screw terminals, terminal<br />

cross-section (see table), PE (earthing of the<br />

housing) via screwed end<br />

| Protection class: IP 20<br />

| Dimensions: see table<br />

Typ Rated Rated voltage Leakage Dimensions<br />

Weight<br />

current at (VAC) current (mm)<br />

(kg)<br />

40 °C (A)<br />

(mA) H W D<br />

NF-K-7 7 480<br />

1,0 190 40 70 0,5<br />

NF-K-16 16 480<br />

1,4 250 45 70 0,8<br />

NF-K-30 30 480<br />

1,0 270 50 85 1,0<br />

NF-K-42 42 480<br />

1,2 310 50 85 1,0<br />

NF-K-55 55 480<br />

1,2 250 85 90 1,6<br />

NF-K-55/25 55 480<br />

1,2 250 85 90 1,8<br />

NF-K-75 75 480<br />

1,4 270 80 135 2,4<br />

NF-K-75/50 75 480<br />

1,4 270 80 150 3,4<br />

NF-K-100 100 480<br />

1,4 270 90 150 3,6<br />

NF-K-130 130 480<br />

1,0 270 90 150 3,6<br />

NF-K-180 180 480<br />

1,4 380 120 170 4,2<br />

Type Rated Rated voltage Leakage Dimensions<br />

Weight<br />

(for IT-mains) current at (VAC) current (mm)<br />

(kg)<br />

40 °C (A)<br />

(mA) H W D<br />

NF-K-IT-7 7 690<br />

0,01 190 40 70 0,6<br />

NF-K-IT-16 16 690<br />

0,01 250 45 70 0,9<br />

NF-K-IT-30 30 690<br />

0,01 270 50 85 1,1<br />

NF-K-IT-42 42 690<br />

0,01 310 50 85 1,1<br />

NF-K-IT-55 55 690<br />

0,02 250 85 90 1,8<br />

NF-K-IT-55/25 55 690<br />

0,02 250 85 90 1,9<br />

NF-K-IT-75 75 690<br />

0,02 270 80 135 3,5<br />

NF-K-IT-100 100 690<br />

0,02 270 90 150 3,8<br />

NF-K-IT-130 130 690<br />

0,02 270 90 150 4,0<br />

NF-K-IT-180 180 690<br />

0,02 380 120 170 4,4<br />