Leroy Somer alternators can be equipped with AREP<br />

excitation system with integrated LAM function to offer<br />

following advantages:<br />

Excitation current 3In for 10s<br />

No distortions caused by the load<br />

Faster load acceptance<br />

AREP<br />

In the alternators with AREP excitation, the electronic<br />

voltage rgulator is powered by two auxiliary windings,<br />

independent from the voltage detection circuit. The fi rst<br />

winding has a voltage directly proportional to the output<br />

voltage of the alternator (Shunt), the second winding<br />

has a voltage directly proportional to the current of the<br />

stator (Compound: Booster effect).<br />

The power supply voltage is redressed and fi ltered<br />

before it gets to the regulator’s monitoring transistor.<br />

This ensures that regulation will not be affected by any<br />

distortions generated by the load.<br />

Dans l’alternateur avec excitation AREP, le régulateur<br />

électronique est alimenté par deux bobinages auxiliaires<br />

indépendants du circuit de détection de tension.<br />

Le premier bobinage a une tension proportionnelle à<br />

celle de l’alternateur (caractéristique Shunt), le second<br />

a une tension proportionnelle au courant du stator<br />

(caractéristique Compound: effet Booster).<br />

La tension d’alimentation est redressée et fi ltrée avant<br />

d’être exploitée par le transistor de contrôle du régulateur.<br />

Ce principe apporte à la machine une capacité de courant<br />

de court-circuit de 3In pendant 10 s, et rend la régulation<br />

insensible aux déformations générées par la change.<br />

Tensione/Voltage<br />

UN<br />

0,9<br />

0,8<br />

CADUTA TENSIONE TRANSITORIA<br />

LAM<br />

Frequenza/Frequency<br />

FN<br />

0,9<br />

0,8<br />

Potenza/<strong>Power</strong><br />

Carico<br />

sull’albero (kW)<br />

CADUTA VELOCITÀ MAX<br />

ALLEGGERIMENTO “LAM”<br />

(U/f)<br />

AREP excitation and LAM function<br />

LAM<br />

LAM<br />

Variazione di carico<br />

0 1 s<br />

2 s<br />

Temp<br />

(s)<br />

3 s<br />

Effetti tipici del “LAM” con motore diesel con LAM senza LAM (solo U/F)<br />

Excitation AREP et fonction LAM<br />

Avvolg. STATORE<br />

Tensione (V)<br />

100%<br />

Les alternateurs Leroy Somer peuvent être équipés d’un<br />

système d’excitation avec fonction LAM integrée ce qui porte<br />

les avantages suivants:<br />

Courant d’excitation 3 IN pendant ‘10s<br />

Aucune deformation generée par la charge<br />

Acceptation plus vite de la charge<br />

Caduta di Tensione sostenuta<br />

CARATTERISTICHE<br />

SHUNT PRINCIPALI<br />

CONCORRENTI<br />

Sovraccarico basso<br />

Raddrizzatori<br />

Corrente<br />

diretta<br />

CARATTERISTICHE<br />

SHUNT LS<br />

Avvolg. ROTORE<br />

Corrente<br />

alternata<br />

100% 120-130% 150-180% 300%<br />

Eccitatrice di campo<br />

Carico %<br />

Sovraccarico alto - Corto circuito<br />

LAM<br />

The LAM (Load Adjustment Module) function is integrated as standard in the regulator (can also<br />

be deactivated): on load impact, the rotation speed of the generator set decreases. When it goes<br />

below the preset frequency threshold, LAM causes the voltage to drop by approximately 15% and<br />

the active load applied will be reduced by approximately 25% unti! The speed will reach again its<br />

rated value. LAM can therefore be used to either reduce the speed variation (frequency) and its<br />

duration for the given load applied, or to increase the possible applied load for one same speed<br />

variation (turbo-charged engines).<br />

To avoid voltage oscillations, the trip threshold for the LAM function should be set approximately<br />

2 Hz below the lowest frequency in the steady state.<br />

Le LAM est un système intégré au régulateur, en standard il est actif (II peut être désactivé).<br />

Rôle du “LAM” (Atténuateur d’à-coups de charge):<br />

A l’application d’une charge, la vitesse de rotation du groupe électrogène diminue. Quand celle-ci<br />

passe en dessous du seuil de fréquence préréglé, le “LAM” fait chuter la tension d’environ 15% et<br />

de ce fait l’échelon de charge active appliqué est réduit de 25% environ, tant que la vitesse n’est<br />

pas remontée à sa valeur nominale. Le “LAM” permet donc, soit de réduire la variation de vitesse<br />

(fréquence) et sa durée pour une charge appliquée donnée, soit d’augmenter la charge appliquée<br />

possible pour une même variation de vitesse (moteurs à turbo compresseurs). Pour éviter les<br />

oscillations de tension, le seuil de déclenchement de la fonction “LAM” doit être réglé environ 2 Hz<br />

en dessous de la fréquence la plus basse en régime établi.