Mounting<br />
Mounting and temperature conditions<br />
≥ 50 mm<br />
≥ 50 mm<br />
(1.97 in.) (1.97 in.)<br />
Install the unit vertically, at ± 10°.<br />
Do not place it close to heating elements.<br />
Leave sufficient free space to ensure that the air required for cooling purposes can<br />
circulate from the bottom to the top of the unit.<br />
Free space in front of unit: 10 mm (0.4 in.) minimum<br />
When IP20 protection is adequate, it is recommended that the protective cover on<br />
the top of the drive is removed as shown below.<br />
Removing the protective cover<br />
Example ATV<strong>21</strong>HU15M3X<br />
Example ATV<strong>21</strong>HD22N4<br />
ENGLISH<br />
3 types of mounting are possible<br />
Type A<br />
mounting:<br />
Free space u 50 mm (1.97 in.) on each side, with protective cover fitted<br />
u 50 mm<br />
u 50 mm<br />
(1.97 in.) (1.97 in.)<br />
Type B<br />
mounting:<br />
Drives mounted side by side, with the protective cover removed (the degree of protection<br />
becomes IP20)<br />
Type C<br />
mounting:<br />
Free space u 50 mm (1.97 in.) on each side, with protective cover removed (the degree of<br />
protection becomes IP20)<br />
u 50 mm<br />
u 50 mm<br />
(1.97 in.) (1.97 in.)<br />
These types of mounting are possible without derating up to 40°C at the factory-set switching frequency. For other<br />
ambient temperatures and switching frequencies, derating may be required (please consult our catalog).<br />
1760794 09/2009 31