Malfunctions - Trouble-shooting<br />

Fault Cause Remedy<br />

1. Indicator lamp<br />

Does not light up No voltage Check<br />

Controller not properly adjusted Adjust<br />

Light up Automatic oil firing unit set to malfunction Reset<br />

Automatic oil firing unit <strong>de</strong>fective Replace<br />

Connection terminal not tightly connected Tighten screws<br />

2. Motor<br />

Plug at oil preheater not tight Plug-in properly<br />

Does not start Release thermostat for oil preheater <strong>de</strong>fective Replace<br />

Capacitor <strong>de</strong>fective Replace<br />

Bearings are frozen/jammed Replace motor<br />

Oil pump is frozen/jammed Replace<br />

Runs with loud noise Motor <strong>de</strong>fective Replace<br />

Bearings <strong>de</strong>fective Replace motor<br />

3. Ignition<br />

Oil pump <strong>de</strong>fective Replace<br />

No ignition spark Ignition transformer <strong>de</strong>fective Replace<br />

Ignition cable scorched Replace<br />

Automatic oil firing unit <strong>de</strong>fective Replace<br />

Insulator cracked Replace<br />

Weak ignition spark Ignition electro<strong>de</strong> setting incorrect Adjust<br />

4. Oil pump<br />

Ignition electro<strong>de</strong> contaminated Clean<br />

Fluctuating oil pressure Leaks in suction line Seal properly<br />

Dimensioning of suction line not favorable Change according to table<br />

Runs with loud noise Too little oil Check suction line<br />

No oil pressure Suction line not vented Vent<br />

Oil shut-off valve closed Open<br />

Coupling <strong>de</strong>fective Replace<br />

Does not pump oil Leaks in suction line Seal properly<br />

Oil pump filter dirty Clean<br />

Prefilter dirty Clean/replace<br />

Paraffin <strong>de</strong>posits (+4°C) Install cold-insulation<br />

Heating oil no longer flowable (-1°C) Install cold-insulation<br />

5. Solenoid valve<br />

Does not open Coil <strong>de</strong>fective Replace<br />

6. Automatic oil firing unit<br />

Switches to malfunction<br />

Automatic oil firing unit <strong>de</strong>fective Replace<br />

without flame Outsi<strong>de</strong> light (> 5,5 µA) Eliminate outsi<strong>de</strong> light<br />

Photo-resistor <strong>de</strong>fective Replace<br />

with flame Photo-resistor dirty Clean<br />

7. Nozzle<br />

Photo-resistor too weak (< 55 µA) Re-adjust burner<br />

Sprays irregularly Nozzle <strong>de</strong>fective Replace<br />

8. Baffle plate<br />

Oil pressure too low Set higher<br />

Very dirty Incorrectly adjustet Re-adjust burner<br />

Nozzle spray irregularly Replace<br />

Nozzle too drips Check oil line<br />

Install LE system<br />

Nozzle too large Replace<br />

Nozzle too small Replace<br />

Spraying angle of the nozzle incorrect Replace nozzle<br />

9. Blower wheel<br />

Changed combustion air volume Re-adjust burner<br />

Delivers too little air Blower wheel contaminated Clean<br />

Air flap jammed Replace<br />

Runs with loud noise Air flap incorrectly installed Install correctly<br />

Blower wheel damaged Replace<br />