GB - Installation Instructions<br />

4<br />

Product overview<br />

The thermostat is designed for use in systems equipped<br />

with fan coils served by a 2-pipe central changeover system.<br />

The thermostat controls the operation of a motorized valve<br />

which, during heating periods, opens when heat is required<br />

and which, during cooling periods, opens when cooling is<br />

required.<br />

The changeover from heating to cooling is achieved<br />

automatically by measuring the temperature of the fl ow<br />

pipe. If the fl ow temperature exceeds 30°C the thermostat<br />

operates as a heating thermostat, if the fl ow temperature<br />

is less than 16°C the thermostat operates as a cooling<br />

thermostat<br />

!<br />

Important note: It is essential that the circuit in which<br />

the pipe sensor is located is not closed off and that water<br />

circulates past the sensor at all times. This may require<br />

the fi tting of a bypass valve between system fl ow and<br />

return at the end of each circuit.<br />

Installation<br />

First remove the wallplate from the back of the unit.<br />

Ensure that there is a minimum of 50mm above the<br />

unit and 100mm below the unit in order to mount the<br />

plug-in module.