<strong>TGB</strong>-<strong>40</strong>/<strong>60</strong> Maintenance instructions<br />
• Remove the plug connections from the following<br />
components: ignition, ionisation, earth, flow and return<br />
temperature sensor, flue gas temperature sensor and gas<br />
fan.<br />
Remove the hose from the mixing chamber.<br />
Gas fan plug<br />
Mixing chamber<br />
Flow sensor<br />
plug<br />
Flue gas<br />
sensor plug<br />
Ignition plug<br />
Ionisation plug<br />
Earth plug<br />
Return<br />
sensor plug<br />
Gas fired condensing boiler with combustion chamber<br />
housing removed<br />
• Pull the anti-radiation panel forward and unhook the<br />
panel.<br />
Anti-radiation panel<br />
Location of anti-radiation panel<br />
• Release the joint between the gas connection and the<br />
mixing chamber.<br />
Joint between the gas connection and mixing chamber<br />
Location of joint<br />
• Release the nuts (3 no.) on the burner flange.<br />
• Remove the whole assembly (mixing chamber, fan and<br />
burner flange).<br />
Nut on the burner flange<br />
<strong>40</strong><br />
Location of nut on the burner flange