• During assembly, please note particularly, that:<br />
<strong>TGB</strong>-<strong>40</strong>/<strong>60</strong> Maintenance instructions<br />
- The flue pipe is inserted into the condensate pan<br />
until it bottoms out.<br />
- The pneumatic control cables are connected in<br />
accordance with the adjacent figure.<br />
- The electrode plug is connected in accordance with<br />
the adjacent figure.<br />
Pneumatic control cable position<br />
Safety instructions<br />
Carry out the following steps after completing the above<br />
maintenance work:<br />
• Refill the siphon, install and check for tightness against<br />
the condensate pan.<br />
• Open the shut-off valve on the heating flow and return.<br />
Open the cold water inlet.<br />
• Top up the heating system to approx. 1.5 bar, if necessary,<br />
and vent the entire heating system.<br />
• Open the gas shut-off valve.<br />
• Switch ON the emergency stop switch (or insert fuses).<br />
• Switch ON the system ON/OFF switch on the Wolf gas<br />
fired boiler.<br />
• Check the boiler for leaks at gas and water connections.<br />
• Check the boiler for perfect function and its flue gas<br />
values.<br />
• Hook in the front panel.<br />
Electrode plug<br />
Fan control cable<br />
Fan supply and earth cable<br />