13.07.2015 Views

Z-TIO PLC Communication Quick Instruction Manual - CasCade ...

Z-TIO PLC Communication Quick Instruction Manual - CasCade ...

Z-TIO PLC Communication Quick Instruction Manual - CasCade ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6.5. <strong>PLC</strong> <strong>Communication</strong> Environment SettingThe <strong>PLC</strong> communication environmental settings must be made to perform <strong>PLC</strong>communication. The system data settings are made by the loader communication.1. Turn on the power of the Z-<strong>TIO</strong>-C or Z-<strong>TIO</strong>-D module.(<strong>PLC</strong> power is off.)2. On the personal computer, set the communication data of the <strong>PLC</strong> communicationenvironment indicated below.3. When the settings for the communication data of the <strong>PLC</strong> communication environmentare completed, turn the power of the Z-<strong>TIO</strong>-C/D module off, and then turn it on again.When the power is turned ON, the changed system data values are enabled.Set the communication data for each module. After completing the communicationsettings of the first module, connect the loader communication cable to the nextmodule and set the <strong>PLC</strong> communication environment.Connect to loader communicationcable of next module.Loader communication cable(W-BV-01) [Option]Z-<strong>TIO</strong>-C orZ-<strong>TIO</strong>-D module• <strong>Communication</strong> data list (<strong>PLC</strong> communication environment)RO: Read only data R/W: Read and Write dataNameRKC ModbusAttri-FactoryIden- register address DigitsData rangebuteset valuetifier HEX DECStation number QV 0164 356 7 R/W 0 to 310Set the <strong>PLC</strong> station number. Setit to the same number as the<strong>PLC</strong>.PC number QW 0165 357 7 R/W 0 to 255255Set the <strong>PLC</strong> PC number. Set it tothe same number as the <strong>PLC</strong>.Set all Z-<strong>TIO</strong>-C/D modules to thesame values.Register type QZ 0166 358 7 R/W 0: D register01: R register2: W register3: ZR registerMethod of specifyingconsecutive numbers when32767 of R register isexceeded.When the ZR register isselected, QnA compatible 3Cframe communication is used.Set the register types used in<strong>PLC</strong> communication.Register start QS 0167 359 7 R/W 0 to 150numberSet the start number of the(High-orderregister of system data used in4-bit)<strong>PLC</strong> communication. Set this ifthe register address 65535 isexceeded in the ZR register.Register startnumber(Low-order16-bit)QX 0168 360 7 R/W 0 to 9999A compatible, 1C frame, ACPUcommon command (WR/WW)0 to 65535A compatible 1C frameAnA/AnUCPU commoncommand (QR/QW), QnAcompatible 3C frameSet the start number of theregister of system data used in<strong>PLC</strong> communication.System data is required toperform <strong>PLC</strong> communication.The system data occupies ten<strong>PLC</strong> registers.1000NameMonitor itemregister biasSetting itemregister biasMonitor itemselectionSetting itemselectionZ-<strong>TIO</strong> modulelink recognitiontime<strong>PLC</strong> scanningtime<strong>PLC</strong>communicationstart timeSlave registerbiasFactoryRKCIden-Modbusregister addresstifier HEX DECDigits Attri- Data rangebuteR3 0169 361 7 R/W 10 to 9999A compatible, 1C frame, ACPUcommon command (WR/WW)10 to 65535A compatible 1C frameAnA/AnUCPU commoncommand (QR/QW), QnAcompatible 3C frameSet the start number of theregister of monitor groupcommunication data.A bias is applied to the registerstart number. The factory setvalue for the register bias is 10,and thus the register start numberof the monitor group is D01010.Equation for calculating:Register start number of monitorgroup = Register start number +Monitor item register biasR4 016A 362 7 R/W 0, 10 to 9999A compatible, 1C frame, ACPUcommon command (WR/WW)0, 10 to 65535A compatible 1C frameAnA/AnUCPU commoncommand (QR/QW), QnAcompatible 3C frameSet the start number of theregister of setting groupcommunication data.When set to 0 to 9In the monitor group, the registerstart number of the setting groupis set after the communicationdata of the last address.When set to 10 or moreA bias is applied to the registerstart number of the system data.If set to 10 or greater, take carethat overlapping of thecommunication data of themonitor group and the registeraddress does not occur.Equation for calculating:Register start number of settinggroup = Register start number +Setting item register biasR6 016C 364 7 R/W 0 to 65535Select the communication data ofmonitor group.The selected communicationdata only performs <strong>PLC</strong>communication.Convert binary to decimal andconfigure the setting.(See Table 1)R7016D⋅0170365⋅368set value100335357 R/W 0 to 65535(A) 62427Select the communication data of (B) 15583setting group.The selected communication(C) 512(D) 512data only performs <strong>PLC</strong>communication.Convert binary to decimal andconfigure the setting.(See Table 2)QT 0171 369 7 R/W 0 to 255 secondsWhen connecting two or moreZ-<strong>TIO</strong>-C/D module, set the timerequired until a module after thesecond module is recognized.Set this item to the mastermodule (address 0).VT 0172 370 7 R/W 0 to 3000 msSet the time of waiting for aresponse from the <strong>PLC</strong>.Usually, no factory set values arenecessary to be changed.R5 0173 371 7 R/W 1 to 255 secondsTime until communication withthe <strong>PLC</strong> starts is set after thepower is turned on.R8 0175 373 7 R/W 0 to 65535When connecting two or moreZ-<strong>TIO</strong>-C/D module, a bias is setfor the register addresses of eachmodule so that no addressduplication occurs.Set bias enable/disable with theaddress setting switch.When set the address settingswitch to 0: Bias disabledWhen set the address settingswitch to other than 0: BiasenabledEquation for calculating:Slave register start number =Register start number +(Address setting switch) × Slaveregister bias52555150NameRKC ModbusIdentifierHEX DECregister address DigitsAttributeData rangeInterval time ZX 035B 859 7 R/W 0 to 250 msOn some <strong>PLC</strong> models, theinterval time must be set or the<strong>PLC</strong> will not be able to respond.If communication does not takeplace correctly on an olderMELSEC A Series model, set theinterval time to 30 milliseconds ormore.Interval time is the engineeringsetting data. When the Z-<strong>TIO</strong>module of setting data is stopped,write is possible.Factoryset valueTable 1: Monitor item selection (<strong>Communication</strong> data of monitor group)<strong>Communication</strong> data of monitor group is assigned as a bit image in binary numbers. Set decimal-convertedvalues.Bit<strong>Communication</strong> data (Monitor item)10Number of Factory set valuedata Binary Decimal0 Measured value (PV) 4 11 Comprehensive event state 4 12 Operation mode state monitor 4 13 Error code 4* 14 Manipulated output value (MV) monitor [heat-side] ♣ 4 15 Manipulated output value (MV) monitor [cool-side] ♣ 4 16 Current transformer (CT) input value monitor 4 17 Set value (SV) monitor 4 1 335358 Remote setting (RS) input value monitor 4 09 Output state monitor 4* 110 Memory area soak time monitor 4 011 Integrated operating time monitor 4* 012 Holding peak value ambient temperature monitor 4 013 Backup memory state monitor 4* 014 Logic output monitor 4* 015 Memory area number monitor 4 1♣ When heat/cool control or position proportioning control is performed, there will be communication data(indicated by ♣ in the name column) for which the 2nd channel and 4th channel will be invalid.[Read is possible (0 is shown), but the result of Write is disregarded.]* Occupies four <strong>PLC</strong> registers, however, the actual number of data items is 1 (data units are modules),and thus only the data of CH1 is effective.The selected communication data is justified upward in the <strong>PLC</strong> register.Table 2: Setting item selection (<strong>Communication</strong> data of Setting group)<strong>Communication</strong> data of setting group is assigned as a bit image in binary numbers. Set decimal-convertedvalues in the setting columns of (A) ch1 to (D) ch4.(A) Setting column of ch1BitItemnumberBit image: 0000000000000000bit 15 bit 0Bit image: 0000000000000000bit 15 bit 0Number of data (Setting item)0: Unused1: Used0: Unused1: UsedNumber of Factory set valuedata Binary Decimal0 1 PID/AT transfer 4 11 2 Auto/<strong>Manual</strong> transfer 4 12 3 Remote/Local transfer 4 03 4 RUN/STOP transfer 4* 14 5 Memory area transfer 4 15 6 Interlock release 4 06 7 Event 1 set value (EV1) 4 17 8 Event 2 set value (EV2) 4 1 624278 9 Event 3 set value (EV3) 4 19 10 Event 4 set value (EV4) 4 110 11 Control loop break alarm (LBA) time 4 011 12 LBA deadband 4 012 13 Set value (SV) 4 113 14 Proportional band [heat-side] ♣ 4 114 15 Integral time [heat-side] ♣ 4 115 16 Derivative time [heat-side] ♣ 4 1♣ When heat/cool control or position proportioning control is performed, there will be communication data(indicated by ♣ in the name column) for which the 2nd channel and 4th channel will be invalid.[Read is possible (0 is shown), but the result of Write is disregarded.]* Occupies four <strong>PLC</strong> registers, however, the actual number of data items is 1 (data units are modules),and thus only the data of CH1 is effective. Parameters which can be used in multi-memory area functionThe selected communication data is justified upward in the <strong>PLC</strong> register.(B) Setting column of ch2BitItemnumberNumber of data (Setting item)Number of Factory set valuedata Binary Decimal0 17 Control response parameter ♣ 4 11 18 Proportional band [cool-side] ♣ 4 12 19 Integral time [cool-side] ♣ 4 13 20 Derivative time [cool-side] ♣ 4 14 21 Overlap/Deadband ♣ 4 15 22 <strong>Manual</strong> reset 4 06 23 Setting change rate limiter (up) 4 17 24 Setting change rate limiter (down) 4 1 155838 25 Area soak time 4 09 26 Link area number 4 010 27 Heater break alarm (HBA) set value 4 111 28 Heater break determination point 4 112 29 Heater melting determination point 4 113 30 PV bias 4 114 31 PV digital filter 4 015 32 PV ratio 4 0♣ When heat/cool control or position proportioning control is performed, there will be communication data(indicated by ♣ in the name column) for which the 2nd channel and 4th channel will be invalid.[Read is possible (0 is shown), but the result of Write is disregarded.] Parameters which can be used in multi-memory area function(C) Setting column of ch3BitItemnumberNumber of data (Setting item)Number of Factory set valuedata Binary Decimal0 33 PV low input cut-off 4 01 34 RS bias 4 02 35 RS digital filter 4 03 36 RS ratio 4 04 37 Output distribution selection 4 05 38 Output distribution bias 4 06 39 Output distribution ratio 4 07 40 Proportional cycle time 4 0 5128 41 Minimum ON/OFF time of proportioning cycle 4 09 42 <strong>Manual</strong> manipulated output value ♣ 4 110 43 Area soak time stop function 4 011 44 EDS mode (for disturbance 1) 4 012 45 EDS mode (for disturbance 2) 4 013 46 EDS value 1 (for disturbance 1) 4 014 47 EDS value 1 (for disturbance 2) 4 015 48 EDS value 2 (for disturbance 1) 4 0♣ When heat/cool control or position proportioning control is performed, there will be communication data(indicated by ♣ in the name column) for which the 2nd channel and 4th channel will be invalid.[Read is possible (0 is shown), but the result of Write is disregarded.](D) Setting column of ch4BitItemnumberNumber of data (Setting item)Number of Factory set valuedata Binary Decimal0 49 EDS value 2 (for disturbance 2) 4 01 50 EDS transfer time (for disturbance 1) 4 02 51 EDS transfer time (for disturbance 2) 4 03 52 EDS action time (for disturbance 1) 4 04 53 EDS action time (for disturbance 2) 4 05 54 EDS action wait time (for disturbance 1) 4 06 55 EDS action wait time (for disturbance 2) 4 07 56 EDS value learning times 4 0 5128 57 EDS start signal 4 09 58 Operation mode 4 110 59 Startup tuning (ST) 4 011 60 Automatic temperature rise learning 4 012 61 <strong>Communication</strong> switch for logic 4* 013 62 Unused 4 014 63 Unused 4 015 64 Unused 4 0* Occupies four <strong>PLC</strong> registers, however, the actual number of data items is 1 (data units are modules),and thus only the data of CH1 is effective.The selected communication data is justified upward in the <strong>PLC</strong> register.Modbus is a registered trademark of Schneider Electric.The name of each programmable controller (<strong>PLC</strong>) means the products of each manufacturer.Company names and product names used in this manual are the trademarks or registeredtrademarks of the respective companies.RKC INSTRUMENT INC.®The first edition: SEP. 2006 [IMQ00]HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPANPHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jpFAX: 03-3751-8585 (+81 3 3751 8585) SEP. 2006

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!