2.5 Proteção de Sobrecorrente Temporizada para Corrente de Terra<br />

End.. Título do Ajuste Opções de Ajustes Ajuste Padrão Comentários<br />

2425 IEC CURVE Normal Inverse<br />

Very Inverse<br />

Extremely Inverse<br />

Long Inverse<br />

2426 ANSI CURVE Very Inverse<br />

Inverse<br />

Short Inverse<br />

Long Inverse<br />

Moderately Inverse<br />

Extremely Inverse<br />

Definite Inverse<br />

Manual 7UT612<br />

C53000–G1179–C148–1<br />

Normal Inverse Curva IEC<br />

Very Inverse Curva ANSI<br />

2521 IEp 0.05..4.00 A 1.00 A Valor de Pickup IEp<br />

2522 T IEp 0.05..3.20 sec; ∞ 0.50 sec Dial de Tempo T IEp<br />

2523 D IEp 0.50..15.00; ∞ 5.00 Dial de Tempo D IEp<br />

2431 I/IEp PU T/TEp 1.00..20.00 I / Ip; ∞<br />

0.01..999.00 Time Dial<br />

2432 MofPU Res T/TEp 0.05..0.95 I / Ip; ∞<br />

0.01..999.00 Time Dial<br />

Curva de Pickup IE/IEp - TIE/TIEp<br />

Múltiplo de Pickup TI/TIEp<br />

2441 2.HARM. Earth 10..45 % 15 % 2º harmônico O/C E em % da fundamental<br />

2442 I Max InRr. E 0.30..25.00 A 7.50 A Corr. Max. para Restr, Inrush O/C Terra<br />