1. Application<br />

The air-termination rod can be used to install isolated lightning protection air-termination<br />

systems according to DIN EN 62305-3 (VDE 0185-305-3), IEC 62305-3. When using the airtermination<br />

rod, the ”protective angle method” has to be applied. The protective angle depends<br />

on the class of LPS (risk level) and on the height of the air-termination rod above the surface<br />

to be protected. For more details on values, please refer to DIN EN 62305-3 (VDE 0185-305-3),<br />

IEC 62305-3 Table 3 (see also Table 1 and Fig. 1). Alternatively, the ”rolling sphere method” can<br />

be applied for positioning the air-termination rod.<br />

The air-termination rods specified in the installation instructions are designed for wind load zone<br />

II according to DIN 4131. If installed correctly, the air-termination rods can stand up to wind<br />

load influences up to 145 km/h.<br />

air-termination rod without supporting braces<br />

heights 4 m, 4,5 m, 5 m oder 5,5 m<br />

a a<br />

air-termination rod with supporting braces<br />

heights 6 m, 6,5 m, 7 m, 7,5 m, 8 m oder 8,5 m<br />

protective angle a<br />

a<br />

a<br />

protective angle a<br />

radius(R)<br />

a (°)<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

0<br />

class of LPS I II III IV<br />

0 10 20 30 40 50 60<br />

h (m)<br />

Calculation the air-termination rod<br />

Fig. 1 Protectiv angle a according to Table 1<br />

radius ( R )<br />

Page<br />