<strong>Instantaneous</strong> ZSI on EntelliGuard TU Trip Units in ANSI WavePro Circuit Breakers<br />
<strong>Selectivity</strong> with EntelliGuard TU Trip Units in ANSI WavePro Circuit Breakers<br />
Maximum instantaneous selectivity that may be achieved using <strong>Instantaneous</strong> Zone Selective Interlocking between these WavePro Low Voltage Power Circuit Breakers.<br />
Limited by short circuit rating of downstream device or upstream device.<br />
Downstream<br />
Upstream<br />
WavePro ANSI Low Voltage Power CB. Long Time Curves, short time pickup and instantaneous pick up must be adjusted per TCC<br />
Wave Pro WPS-08 WPH-08 WPX-08 WPS-16 WPH-16 WPX-16 WPS-20 WPS-32 WPH-32 WPX-32 WPS-40 WPX-40 WPS-50 WPX-50<br />
WPS-08 30 30 30 30 30 30 30 30 30 30 30 30 30 30<br />
WPH-08 30 42 42 30 42 42 42 42 42 42 42 42 42 42<br />
WPX-08 30 42 65 30 42 65 65 65 65 65 65 65 65 65<br />
WPS-16 30 30 30 30 30 30 30 30 30 30 30<br />
WPH-16 30 42 42 42 42 42 42 42 42 42 42<br />
WPX-16 30 42 65 65 65 65 65 65 65 65 65<br />
WPS-20 65 65 65 65 65 65 65 65<br />
WPS-32 65 65 65 65 65 65 65<br />
WPH-32 65 85 85 85 85 85 85<br />
WPX-32 65 85 100 85 100 85 100<br />
WPS-40 85 85 85 85<br />
WPX-40 85 100 85 100<br />
WPS-50 85 85<br />
WPX-50 85 100<br />
<strong>Selectivity</strong> values are shown in kA.<br />