GE Overcurrent Device Instantaneous Selectivity Tables - GE Energy
GE Overcurrent Device Instantaneous Selectivity Tables - GE Energy
GE Overcurrent Device Instantaneous Selectivity Tables - GE Energy
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Instantaneous</strong> ZSI on EntelliGuard TU Trip Units in UL489 EntelliGuard G Circuit Breakers<br />
Continued from previous page<br />
Downstream<br />
EntelliGuard<br />
G, UL CB<br />
Upstream<br />
EntelliGuard G ANSI Low Voltage Power CB. Long Time Curves, Short Time pickup<br />
and <strong>Instantaneous</strong> pickup must be adjusted per TCC<br />
Frame & AIC Tier, at 3000A 3000A 3000A 3000A 4000A 4000A 5000A 5000A 6000A 6000A<br />
Sensor 240 & 480V N-65kA H-85kA M-100kA L-150kA M-100kA L-150kA M-100kA L-150kA M-100kA L-150kA<br />
800A N-65kA 42 50 65 65 65 65 65 65 65 65<br />
800A H-85kA 42 50 65 85 65 85 65 85 65 85<br />
800A M-100kA 42 50 65 85 65 85 65 85 65 85<br />
1600A N-65kA 42 50 65 65 65 65 65 65 65 65<br />
1600A H-85kA 42 50 65 85 65 85 65 85 65 85<br />
1600A M-100kA 42 50 65 85 65 85 65 85 65 85<br />
2000A N-65kA 42 50 65 65 65 65 65 65 65 65<br />
2000A H-85kA 42 50 65 85 65 85 65 85 65 85<br />
2000A M-100kA 42 50 65 85 65 85 65 85 65 85<br />
3000A N-65kA 42 50 65 65 65 65 65 65 65 65<br />
3000A H-85kA 42 50 65 85 65 85 65 85 65 85<br />
3000A M-100kA 42 50 65 85 65 85 65 85 65 85<br />
3000A L-150kA 42 50 65 85 65 85 65 85 65 85<br />
4000A M-100kA 65 85 65 85 65 85<br />
4000A L-150kA 65 85 65 85 65 85<br />
5000A M-100kA 65 85 65 85<br />
5000A L-150kA 65 85 65 85<br />
6000A M-100kA 65 85<br />
6000A L-150kA 65 85<br />
<strong>Selectivity</strong> values are shown in kA.<br />
16