Stored <strong>Energy</strong> Mains<br />

Upstream: Stored energy with adjustable<br />

electronic LSI or LSIG trip types<br />

Amperes<br />

Max.<br />

Inst.<br />

Pickup<br />

30<br />

Current limiting lighting panel circuit breakers (1)<br />

Type<br />

Frame Sensor<br />

Type<br />

Trip<br />

FB<br />

15-100A<br />

TEY<br />

70-100A<br />

TEY<br />

15-60A<br />

THHQB<br />

125A<br />

THHQB<br />

15-100A<br />

THQB<br />

125A<br />

THQB<br />

15-100A<br />

Plug<br />

or trip<br />

(X Plug) Poles 1/2/3 1/2/3 1/2/3 2 1/2/3 2 1/2/3<br />

ANSI 5,000 5,000 5,000 7 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 4,000 4,000 4,000 9 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 4,000 3,600 3,600 9 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI 3,200 3,200 3,200 13 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ICCB 3,000 3,000 3,000 13 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI 4,000 3,000 3,000 9 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ICCB 3,000 2,500 2,500 13 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI 3,200 3,200 2,400 13 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 2,000 2,000 2,000 15 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 1,600 1,600 1,600 15 100,000 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 1,600 1,600 1,200 15 71,200 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 1,600 1,600 1,000 15 44,100 14,000 14,000 22,000 22,000 10,000 10,000<br />

ANSI & ICCB 800 800 800 15 35,000 12,800 12,800 18,100 18,100 10,000 10,000<br />

ANSI & ICCB 800 800 400 15 5,400 5,400 5,400 5,400 5,400 5,400 5,400<br />

ANSI & ICCB 800 800 150 15 TCC TCC TCC TCC TCC TCC TCC<br />

1 Current Limiting Molded Case Circuit Breaker. Use upstream EntelliGuard TU for highest selectivity ratings.<br />

NIS = not instantaneously selective. TCC = refer to time current curve.<br />

ANSI = AKR, WavePro & EntelliGuard<br />

ICCB = Power Break II