Static Smoke Ventilators (477) Hexadome "Hexasteel" & "Hexacoif" Static Smoke<br />

Ventilators for Natural Venting of Staircase/a) Hexasteel b)<br />

Hexacoif (As indicated in the annex to EC Certificate of<br />

Conformity No.:0333-CPD-219003)<br />

VENTILATION DIVISION OF FIRE SERVICES DEPARTMENT<br />

LIST OF ACCEPTED MATERIALS FOR USE IN VENTILATION / FIRE SERVICE RELATED SYSTEMS<br />

Fire Rated Duct (491) "WinDuct" Fire Resistant Coated Ductwork System / a) Passive Fire Protection Sdn., Bhd.,<br />

Ductwork is constructed of galvanized steel sheet in 1,200<br />

mm long section to DW/144 of thickness 1.0 mm. b) A<br />

layer of spray or brush/roller applied "Winduct" intumescent<br />

water based fire prevention coating, minimum 0.6 mm thick.<br />

Malaysia<br />

Fire Rated Duct (495) FireMaster FastWrap XL / no model / FireMaster FastWrap<br />

XL is a fully foil encapsulated Thermal Ceramics patented<br />

Superwool® fibre (an alkaline-earth silicate wool) with a<br />

nominal density of 96 kg/m 3 and thickness of either 38 mm<br />

.<br />

Smoke Ventilators (499) "Brakel" Smoke Ventilators for Static Smoke Extraction<br />

System / a) Eura and Eura-R; b) Duo Therma<br />

Automatic Smoke Curtain (533) "BLE" (UK) SD60 Automatic Smoke Curtain / SD 60 / A<br />

woven glass referenced "X32K" incorporating a<br />

polyurethane coating with aluminium pigments on both<br />

faces; the fabric has an overall weight of 455 g/m 2 and a<br />

thickness of 0.43 mm as described in report WFRC No.<br />

C131932 of 29.5.2003 by Warrington Fire Research Centre.<br />

Hexadome, France 6/12/2010 December 2015 A valid "EC-Certificate of Conformity"<br />

shall be maintained.<br />

Thermal Ceramics UK Ltd., United<br />

Kingdom<br />

1/2/2011 September 2015 a) Installation of the fire rated duct<br />

system shall be carried out by<br />

Dekkons Ltd. (who shall be holding a<br />

valid authorization issued by Passive<br />

Fire Protection Sdn., Bhd., Malaysia)<br />

or his authorized representatives. b) A<br />

letter shall be issued by Dekkons Ltd.<br />

to certify the quality of every<br />

completed "WinDuct" fire resistant<br />

coated ductwork system. c) Valid test<br />

reports and assessment reports as<br />

listed above shall be made available<br />

upon request.<br />

14/2/2011 March 2015 Nil<br />

Brakel Aluminium b.v., U.K. 24/2/2011 February 2016 A valid "EC-Certificate of Conformity"<br />

shall be maintained.<br />

BLE Smoke and Fire Curtains Ltd.,<br />

UK<br />

11/7/2011 July 2014 All test reports mentioned above shall<br />

maintain their validity through relevant<br />

review reports.<br />