05<br />
5.5 Lubrication<br />
Lubrication of the operating mechanism is necessary only<br />
every 10 years or every 5,000 operating cycles.<br />
In general, the circuit breaker requires only moderate<br />
lubrication at regular intervals and all excess must be<br />
removed with a clean cloth to prevent any accumulation of<br />
dust or dirt. Avoid any lubricant on insulation or other<br />
electrical parts.<br />
Moving parts should then be moved slightly to let the<br />
grease penetrate and become properly distributed.<br />
Now operate the breaker several times manually.<br />
Our recommended grease for lubrication is Shell Albania<br />
No. 2.<br />
The points to be lubricated inside of mechanism housing<br />
are shown in Fig. 5-2.<br />
24