05<br />

5.5 Lubrication<br />

Lubrication of the operating mechanism is necessary only<br />

every 10 years or every 5,000 operating cycles.<br />

In general, the circuit breaker requires only moderate<br />

lubrication at regular intervals and all excess must be<br />

removed with a clean cloth to prevent any accumulation of<br />

dust or dirt. Avoid any lubricant on insulation or other<br />

electrical parts.<br />

Moving parts should then be moved slightly to let the<br />

grease penetrate and become properly distributed.<br />

Now operate the breaker several times manually.<br />

Our recommended grease for lubrication is Shell Albania<br />

No. 2.<br />

The points to be lubricated inside of mechanism housing<br />

are shown in Fig. 5-2.<br />