4.4.2 CAUTIONS FOR WIRING<br />
!<br />
CAUTION<br />
The external interconnection wiring must be performed with the following procedures.<br />
After completing <strong>7200GS</strong> interconnections, be sure to check that connections<br />
are correct. Never use control circuit buzzer check.<br />
(A) MAIN CIRCUIT INPUT/OUTPUT<br />
(1) Phase rotation of input terminals L1 (R), L2 (S), L3 (T) is available in either<br />
direction. (Clockwise and counterclockwise).<br />
(2) When inverter output terminals T1 (U), T2 (V), and T3 (W) are connected to<br />
motor terminals T1 (U), T2 (V), and T3 (W), respectively, motor rotates<br />
counterclockwise. (Viewed from opposite side of drive end, upon forward<br />
operation command). To reverse the rotation interchange any two of the motor<br />
leads.<br />
(3) Never connect AC main circuit power supply to output terminals T1 (U), T2<br />
(V), and T3 (W). This may cause damage to the inverter.<br />
(4) Care should be taken to prevent contact of wiring leads with <strong>7200GS</strong> cabinet.<br />
If this occurs, a short-circuit may result.<br />
(5) Never connect power factor correction capacitors or noise filters to <strong>7200GS</strong><br />
output.<br />
(6) Never open or close contactors in the output circuit unless inverter is properly<br />
sized.<br />