4.4.2 CAUTIONS FOR WIRING<br />

!<br />

CAUTION<br />

The external interconnection wiring must be performed with the following procedures.<br />

After completing <strong>7200GS</strong> interconnections, be sure to check that connections<br />

are correct. Never use control circuit buzzer check.<br />

(A) MAIN CIRCUIT INPUT/OUTPUT<br />

(1) Phase rotation of input terminals L1 (R), L2 (S), L3 (T) is available in either<br />

direction. (Clockwise and counterclockwise).<br />

(2) When inverter output terminals T1 (U), T2 (V), and T3 (W) are connected to<br />

motor terminals T1 (U), T2 (V), and T3 (W), respectively, motor rotates<br />

counterclockwise. (Viewed from opposite side of drive end, upon forward<br />

operation command). To reverse the rotation interchange any two of the motor<br />

leads.<br />

(3) Never connect AC main circuit power supply to output terminals T1 (U), T2<br />

(V), and T3 (W). This may cause damage to the inverter.<br />

(4) Care should be taken to prevent contact of wiring leads with <strong>7200GS</strong> cabinet.<br />

If this occurs, a short-circuit may result.<br />

(5) Never connect power factor correction capacitors or noise filters to <strong>7200GS</strong><br />

output.<br />

(6) Never open or close contactors in the output circuit unless inverter is properly<br />

sized.<br />

-18-