2.2 MULTI PURPOSE CHILLER<br />

TENDER NO. DMRC/ELECT./IT&PD/ILBS/HVAC-LV-FF-02<br />

Chillers should be of High efficiency series with elevated total efficiency rates (TER). The chiller<br />

should be capable of working at Cooling Mode to generate only cooling, Heating mode to<br />

generate only heating and both cooling and Heating Mode to generate cooling and heating<br />

simultaneously.<br />

The chillers should have auto defrosting system that is able to optimize the defrosting time with<br />

improvement of the total efficiency.<br />

.<br />

Multi-purpose units should work with automatic mode switch suitable for outdoor installation on<br />

four-pipe plants with capability to work also with a 2 pipe system or with separate 4/2 pipe<br />

cooling/heating , and separate 2 pipe heating system. The unit should be supplied with anti-freeze oil<br />

and refrigerant and has been factory tested. On-site installation will just involve making connections<br />

to the mains power and water supplies. Unit should be factory charged with R410a / 407c / 134a<br />

refrigerant.<br />

UNIT COMPOSITION<br />

Supporting frame should have base and frame in thick hot-galvanised shaped sheet steel. All parts<br />

should be polyesters-painted.<br />

Compressor<br />

Semi-hermetic screw compressors should be designed for high efficiency both at full and partial load. The<br />

bearings should be provided along the rotor axis in a separate chamber isolated from the compression chamber<br />

are made in carbon steel. Each compressor should have provided with an inlet for refrigerant injection (for the<br />

extension of operating limits) and the use of the economiser (for the output capacity and efficiency´s<br />

increase). Each compressor should be fitted with manual-reset motor thermal protection. A check valve should<br />

be fitted on the refrigerant delivery line to prevent the rotors from reversing after stopping.<br />

PRODUCTION OF JUST CHILLED WATER<br />

The unit should work like a simple chiller and therefore discharges the excess heat from inside the<br />

building (condensation heat) to the atmosphere through the Air finned tube heat exchanger.<br />

The water is cooled in a water shell and tube heat exchanger. (Evaporator).<br />

PRODUCTION OF JUST HOT WATER<br />

In this case, the unit should work exactly like a heat pump which channels the heat of the external<br />

atmosphere through an Air finned coil (evaporator) in order to heat the water sent to the inside of the<br />

building through a water shell and tube heat exchanger (condenser). The hot water should be<br />

produced in a heat exchanger ( called a heat recovery shell and tube exchanger) and not a shell and<br />

tube evaporator. This is necessary in order to keep the hot and cold sections separate as required by a<br />

four-tube systems.<br />

COMBINED PRODUCTION OF HOT AND CHILLED WATER<br />

The unit should be capable of providing Hot & Cold water SIMULTANEOUSLY in any proportion,<br />

irrespective of the individual Heating & Cooling load at any given point of time. If the user’s<br />

PAGE No 19 of 204 Nov.2011