BEARINGS:<br />

TENDER NO. DMRC/ELECT./IT&PD/ILBS/HVAC-LV-FF-02<br />

The pump shaft shall be adequately supported by the pump bearings to limit the shaft deflection to<br />

0.002 inches.<br />

Bearings shall be ball type, grease lubricated and locked to the shaft with positive locks of ample size<br />

to withstand any axial thrust loads. Bearing shall provide a minimum life of 10years when calculated<br />

at 50% of Best-Efficiency-Point for the scheduled pumps.<br />

WORKING PRESSURE:<br />

Maximum allowable working pressure (MAWP) for all the pressure containing parts shall in no case<br />

be less than the maximum discharge pressure produced by the pump at shut off(including<br />

tolerances), at the max suction pressure, for the maximum impeller diameter and the maximum<br />

continuous speed.<br />

Note: MAWP shall not be less than 16 kg/cm² for condenser water pumps and not be less than 25<br />

Kg/cm2 for chilled water pumps of primary and secondary applications.<br />

Volute shall have gauge tapping at the suction and discharge nozzles and vent and drain tapping at<br />

the top and bottom.<br />

VIBRATION:<br />

The pump(s) vibration limits shall conform to Hydraulic Institute ANSI/HI 1.1-1.5-1994; section<br />

1.4.6.1.1 or ISO 10816 for recommend acceptable unfiltered field vibration limits (as measured per<br />

HI 1.4.6.5.2) for pumps with rolling contact bearings.<br />

SOUND LEVEL:<br />

The maximum permissible sound pressure level of the pump shall not exceed 85 dbA measured at<br />

1m from pump surface for the recommended range of operation.<br />

COUPLING:<br />

A flexible type, with optional center drop-out (Spacer) design coupler, capable of absorbing torsional<br />

vibration, shall be employed between the pump and motor. Pumps for variable speed application<br />

shall be provided with a suitable coupler sleeve.<br />

The coupling shall be shielded by a dual rated ANSI B15.1, Section 8 & OSHA 1910.219<br />

Compliance coupling guard.<br />

Base Plates:<br />

Base plate shall be of structural steel or fabricated steel channel with fully enclosed sides and ends,<br />

and securely welded cross members. Grouting area shall be fully open. The combined pump and<br />

motor base plate shall be sufficiently stiff as to limit the susceptibility of vibration. The minimum<br />

base plate stiffness shall conform to ANSI/HI 1.3.4-1997 for Horizontal Base plate Design standards.<br />

PAGE No 29 of 204 Nov.2011