Product Data
Product Data
Product Data
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
LEGEND<br />
RATING BASIS AND CAPACITY MULTIPLIERS<br />
RATED<br />
ACTUAL SUCTION GAS TEMP TO COMPR (F)<br />
SST SUCTION GAS<br />
TEMP<br />
–30 –20 –10 0 10 20 30 40 50 60 65<br />
–30<br />
.810 .830 .850 .870 .890 .910 .930 .950 .970 .990 1.000<br />
–20 .830 .850 .870 .890 .910 .930 .950 .970 .990 1.000<br />
–10<br />
.850<br />
.930<br />
.870<br />
.939<br />
.890<br />
.949<br />
.910<br />
.958<br />
.930<br />
.967<br />
.950<br />
.977<br />
.970<br />
.986<br />
.990<br />
.995<br />
1.000<br />
1.000<br />
0<br />
.870<br />
.940<br />
.890<br />
.949<br />
.910<br />
.958<br />
.930<br />
.968<br />
.950<br />
.977<br />
.970<br />
.986<br />
.990<br />
.995<br />
1.000<br />
1.000<br />
10<br />
20<br />
65<br />
.890<br />
.950<br />
.910<br />
.959<br />
.910<br />
.960<br />
.930<br />
.968<br />
.930<br />
.969<br />
.950<br />
.977<br />
.950<br />
.978<br />
.970<br />
.986<br />
.970<br />
.987<br />
.990<br />
.995<br />
.990<br />
.996<br />
1.000<br />
1.000<br />
1.000<br />
1.000<br />
30<br />
.930<br />
.970<br />
.950<br />
.979<br />
.970<br />
.987<br />
.990<br />
.996<br />
1.000<br />
1.000<br />
40<br />
.950<br />
.987<br />
.970<br />
.992<br />
.990<br />
.997<br />
1.000<br />
1.000<br />
50<br />
.970<br />
.997<br />
.990<br />
.999<br />
1.000<br />
1.000<br />
SST —<br />
R-507/404A<br />
R-134a<br />
Saturated Suction Temperature (F)<br />
COMPRESSOR CAPACITY CONTROL REDUCTION STEPS* AND<br />
PART-LOAD PERFORMANCE<br />
COMPRESSOR<br />
06D, 06E<br />
NO. OF<br />
CONTR<br />
CYL<br />
% Full Load Capacity<br />
100 67 49 32<br />
% Full Load kW<br />
100 73 57 46<br />
Number of Active Cylinders<br />
ALL 4 CYLINDER MODELS 2 4 — 2 —<br />
ALL 6 CYLINDER MODELS 4 6 4 — 2<br />
*Compressor cylinders unload in response to a self-contained suction-pressure controlled unloader<br />
valve(s) for 06D and 06E compressors. When suction pressure drops below unloader set point,<br />
cylinders unload. When suction pressure rises above cylinder load set point pressure, cylinders<br />
return to operation. Capacity control unloader set points and differential (load point – unload point)<br />
are adjustable.<br />
17