2. Are <strong>of</strong> adequate making and breaking capacity and,<br />

3. Are suitably located and <strong>of</strong> such construction as to prevent danger from<br />

overheating, arcing, or <strong>the</strong> scattering <strong>of</strong> hot metal when <strong>the</strong>y come into<br />

operation and as to permit ready renewal <strong>of</strong> fuse cartridges without danger.<br />

B) Where <strong>the</strong> earth fault leakage current from a circuit, due to fault <strong>of</strong> negligible<br />

impedance from a live conductor to ear<strong>the</strong>d metal, is insufficient to operate <strong>the</strong><br />

fuses or circuit breakers <strong>of</strong> o<strong>the</strong>r similar devices provided, so as to comply with<br />

regulation 302 ( A ), <strong>the</strong> circuit shall be protected against <strong>the</strong> persistence <strong>of</strong><br />

earth leakage currents liable to cause danger by an earth leakage circuit<br />

breaker or equivalent device.<br />

Note 03: Rewireable fuses are not permitted under any circumstances.<br />

Every single pole shall be inserted in <strong>the</strong> live conductor only. Any switch connected in<br />

<strong>the</strong> conductor connected with earth or neutral shall be a linked switch and shall be<br />

arranged to break also all <strong>the</strong> live conductors.<br />

303 All one way switches both single and double pole, shall be mounted so that <strong>the</strong> dolly is<br />

up when <strong>the</strong> switch is in <strong>the</strong> “Off” position. This shall not be considered to be<br />

applicable to fireman‟s switches.<br />

304 Where metal work, o<strong>the</strong>r than current carrying conductors, is liable to become charged<br />

with electricity is in such manner as to create a danger if <strong>the</strong> insulation <strong>of</strong> a conductor<br />

should become defective or if a defect should occur in any apparatus:<br />

1. The metal work shall be ear<strong>the</strong>d in such a manner as will ensure immediate<br />

electrical discharge without danger <strong>of</strong> shock or fire.<br />

2. O<strong>the</strong>r adequate precautions shall be taken to prevent danger.<br />

305 Effective means, suitably placed <strong>for</strong> ready operations, shall be provided so that all<br />

voltage may be cut <strong>of</strong>f from every circuit and sub circuit and from all apparatus, as may<br />

be necessary to prevent danger.<br />

306 Every electric motor shall be controlled by an efficient device <strong>for</strong> starting and stopping,<br />

such switch is to be readily operated and so placed as to prevent danger.<br />

307 A) All apparatus and conductors exposed to wea<strong>the</strong>r, corrosive atmosphere, or<br />

o<strong>the</strong>r adverse condition, shall be so constructed or protected as may be<br />

necessary to prevent danger arising from such exposure.<br />

B) Where a conductor or apparatus is, or is likely to be, exposed to flammable<br />

surroundings or an explosive atmosphere, it shall be protected by a flamepro<strong>of</strong><br />

enclosure or be o<strong>the</strong>rwise so designed and constructed as to prevent danger.<br />

308 Conductors and apparatus operating at voltage between conductors or to earth and<br />

exceeding 250 Volts shall ei<strong>the</strong>r:<br />

1. Be completely enclosed in ear<strong>the</strong>d metal, which is electrically continuous and<br />

adequately protected against mechanical damage<br />