laws & regulations relating to portable fire extinguisher - Office of the ...
laws & regulations relating to portable fire extinguisher - Office of the ...
laws & regulations relating to portable fire extinguisher - Office of the ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Maximum travel distance <strong>to</strong><br />
<strong>extinguisher</strong><br />
10/16/2012<br />
75 ft 75 ft 75 ft<br />
*Two 2 1/2 gal (9.46 L) water type <strong>extinguisher</strong>s can be used <strong>to</strong> fulfill <strong>the</strong><br />
requirements <strong>of</strong> one 4-A rated <strong>extinguisher</strong>.<br />
NOTE: 1 ft. = 0.305 m<br />
1 sq ft = 0.0929 m 2<br />
(c) Extinguishers as specified in Table 2 may be replaced by uniformly<br />
spaced 1 1/2 inch (3.810 cm) hose stations for use by <strong>the</strong> occupants <strong>of</strong> <strong>the</strong><br />
building. When hose stations are so provided <strong>the</strong>y shall conform <strong>to</strong> Part 9, Title<br />
24, California Code <strong>of</strong> Regulations, Chapter 9. The location <strong>of</strong> hose stations and<br />
<strong>the</strong> placement <strong>of</strong> <strong>fire</strong> <strong>extinguisher</strong>s shall be in such a manner that <strong>the</strong> hose<br />
stations do not replace more than every o<strong>the</strong>r <strong>extinguisher</strong>.<br />
(d) Where <strong>the</strong> floor area <strong>of</strong> a building is less than that specified in Table<br />
2, at least one <strong>extinguisher</strong> <strong>of</strong> <strong>the</strong> minimum size recommended shall be<br />
provided.<br />
(e) The protection requirements may be fulfilled with <strong>extinguisher</strong>s <strong>of</strong> a<br />
higher rating provided <strong>the</strong> travel distance from anywhere in <strong>the</strong> building <strong>to</strong> such<br />
larger <strong>extinguisher</strong>s shall not exceed 75 ft (22.7m), as shown in Table 2 above.<br />
NOTE: Authority cited: Section 13160, Health and Safety Code. Reference:<br />
Section 13160, Health and Safety Code.<br />
569. Fire Extinguisher Size and Placement for Class B Fires o<strong>the</strong>r than<br />
for Fires in Flammable Liquids <strong>of</strong> Appreciable Depth.<br />
(a) Minimal sizes <strong>of</strong> <strong>fire</strong> <strong>extinguisher</strong>s for <strong>the</strong> listed grades <strong>of</strong> hazard shall<br />
be provided on <strong>the</strong> basis <strong>of</strong> Table 3. Extinguishers shall be located so that <strong>the</strong><br />
maximum travel distances from anywhere in <strong>the</strong> building shall not exceed those<br />
specified in <strong>the</strong> table used.<br />
EXCEPTION: Extinguishers <strong>of</strong> lesser rating, desired for small specific hazards<br />
within <strong>the</strong> general hazard area, may be used, but shall not be considered as<br />
fulfilling any part <strong>of</strong> <strong>the</strong> requirements <strong>of</strong> Table 3.<br />
Type <strong>of</strong> Hazard<br />
Light (low)<br />
Ordinary (moderate)<br />
Basic Minimum<br />
Extinguisher<br />
Rating<br />
5B<br />
10B<br />
10B<br />
20B<br />
Extra (high) 40B<br />
80B<br />
TABLE 3<br />
Maximum Travel<br />
Distance <strong>to</strong><br />
Extinguishers<br />
(in feet)<br />
30<br />
50<br />
30<br />
50<br />
30<br />
50<br />
(in meters)<br />
9.15<br />
15.25<br />
9.15<br />
15.25<br />
9.15<br />
15.25<br />
38