testing labora<strong>to</strong>ry for use on <strong>fire</strong> <strong>extinguisher</strong>s or be <strong>the</strong> manufacturer’s<br />

approved replacement.<br />

(b) At <strong>the</strong> time <strong>of</strong> maintenance, <strong>the</strong> tamper seal <strong>of</strong> rechargeable <strong>fire</strong><br />

<strong>extinguisher</strong>s shall be removed by operating <strong>the</strong> pull pin or locking device. After<br />

<strong>the</strong> applicable maintenance procedures are completed, a new tamper seal shall<br />

be installed.<br />

NOTE: Authority cited: Section 13160, Health and Safety Code. Reference<br />

cited: Sections 13160 and 13162, Health and Safety Code.<br />

575.13. Anti-freeze Solution.<br />

Anti-freeze solution for anti-freeze <strong>extinguisher</strong>s shall be put through a<br />

fine strainer prior <strong>to</strong> placing it in<strong>to</strong> <strong>the</strong> <strong>extinguisher</strong> so as <strong>to</strong> prevent any<br />

possibility <strong>of</strong> undissolved salts impairing <strong>the</strong> normal function <strong>of</strong> <strong>the</strong> <strong>extinguisher</strong>.<br />

NOTE: Authority cited: Section 13160, Health and Safety Code. Reference<br />

cited: Sections 13160, Health and Safety Code.<br />

575.14. Nitrogen Cylinder Operated Wheeled Extinguishers.<br />

Pressure regula<strong>to</strong>rs and nitrogen cylinders on wheeled <strong>fire</strong> <strong>extinguisher</strong>s<br />

shall be maintained in accordance with manufacturer’s instructions.<br />

NOTE: Authority cited: Section 13160, Health and Safety Code. Reference<br />

cited: Sections 13160, 13177, Health and Safety Code.<br />

575.15. Conductivity Test.<br />

(a) An annual conductivity test shall be conducted on all carbon dioxide<br />

hose assemblies. Hose assemblies found <strong>to</strong> be nonconductive shall be<br />

replaced.<br />

(b) Carbon dioxide hose assemblies that pass a conductivity test shall<br />

have <strong>the</strong> test information recorded on a suitable metallic label or equally durable<br />

material that has a minimum size <strong>of</strong> ½ in. x 3 in. (1.3 cm x 7.6 cm). The label<br />

shall be affixed <strong>to</strong> <strong>the</strong> hose by means <strong>of</strong> a heatless process. The label shall<br />

include <strong>the</strong> following information:<br />

(1) Month and year <strong>the</strong> test was performed, indicated by perforation, such<br />

as is done by a hand punch.<br />

(2) Initials and EE# <strong>of</strong> person performing <strong>the</strong> test.<br />

NOTE: Authority cited: Section 13160, Health and Safety Code. Reference<br />

cited: Section 13160, Health and Safety Code.<br />

575.16. Wet Chemical Fire Extinguishers.<br />

Internal maintenance <strong>of</strong> wet chemical <strong>fire</strong> <strong>extinguisher</strong>s shall be<br />

performed every 5 years at <strong>the</strong> time <strong>of</strong> hydrostatic test in accordance with <strong>the</strong><br />

manufacturer’s recommendations.<br />

NOTE: Authority cited: Section 13160, Health and Safety Code. Reference:<br />

Section 13160, Health and Safety Code.<br />

576.1. Maintenance Recordkeeping.<br />

Upon completion <strong>of</strong> <strong>the</strong> maintenance procedures prescribed by Section<br />

575.3, each <strong>portable</strong> <strong>fire</strong> <strong>extinguisher</strong> shall be fitted with an annual maintenance<br />

tag as prescribed in Article 9.<br />