When fastening ductwork to side duct flanges on<br />

unit, insert screws through duct flanges only. DO<br />

NOT insert screws through casing. Outdoor ductwork<br />

must be insulated <strong>and</strong> water-proofed.<br />

FIGURE 13 - SIDE PANELS WITH HOLE PLUGS<br />

Note orientation. Panel is “insulation” side up.<br />

FIGURE 14 - RETURN DOWNFLOW PLENUM WITH<br />

PANEL<br />

FIGURE 15 - DISCHARGE PANEL IN PL<strong>AC</strong>E<br />

CONDENSATE DRAIN<br />

167690-Y<strong>IM</strong>-B-0606<br />

The side condensate drain is reversible <strong>and</strong> maybe re-oriented<br />

to the rear of the cabinet to facilitate condensate piping.<br />

A condensate drain connection is available through the<br />

base pan for piping inside the roof curb. Trap the connection<br />

per Figure 16. The trap <strong>and</strong> drain lines should be protected<br />

from freezing.<br />

Plumbing must conform to local codes. Use a sealing compound<br />

on male pipe threads. Install condensate drain line<br />

from the 3/4 inch NPT female connection on the unit to an<br />

open drain.<br />

COMPRESSORS<br />

The compressors are mounted on elastomer insulators. The<br />

mounting bolts have been fully tightened for shipping.<br />

FILTERS<br />

! E E K <br />

2 6 1 ) + 1<br />

/ 7 ) 4 ,<br />

FIGURE 16 - CONDENSATE DRAIN<br />

Do not loosen the compressor mounting bolts.<br />

Two-inch filters are supplied with each unit. One-inch filters<br />

may be used with no modification to the filter racks. Filters<br />

must always be installed ahead of evaporator coil <strong>and</strong> must<br />

be kept clean or replaced with same size <strong>and</strong> type. Dirty filters<br />

reduce the capacity of the unit <strong>and</strong> result in frosted coils<br />

or safety shutdown. Refer to physical data tables, for the<br />

number <strong>and</strong> size of filters needed for the unit. The unit should<br />

not be operated without filters properly installed.<br />

Make sure that panel latches are properly positioned<br />

on the unit to maintain an airtight seal.<br />