1 2<br />

TABLE 43: DM, DH 120 (10 TON) STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE<br />

ESP 3<br />

TURNS OPEN 4<br />

167690-Y<strong>IM</strong>-B-0606<br />

0 1 2 3 4 5<br />

CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP<br />

0.2 - - - - - - - - - 3896 1639 1.76 3688 1453 1.56 3447 1268 1.36<br />

0.4 4040 2076 2.23 4005 1934 2.07 3790 1698 1.82 3569 1508 1.62 3333 1330 1.43 3057 1147 1.23<br />

0.6 3890 2006 2.15 3697 1790 1.92 3427 1550 1.66 3152 1356 1.45 - - - - - -<br />

0.8 3620 1882 2.02 3324 1629 1.75 2972 1380 1.48 - - - - - - - - -<br />

1.0 3227 1708 1.83 - - - - - - - - - - - - - - -<br />

1. Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.<br />

2. Blower performance includes two-inch throwaway filters.<br />

3. ESP (External Static Pressure) given is that available for the supply <strong>and</strong> return air duct system. All internal resistances have been<br />

deducted from the total static pressure of the blower.<br />

4. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.<br />

5. W = Watts<br />

1 2<br />

TABLE 44: DM, DH 120 (10 TON) OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE<br />

ESP 3<br />

TURNS OPEN 4<br />

0 1 2 3 4 5<br />

CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP CFM W 5 BHP<br />

0.4 4965 3485 3.74 4875 3150 3.38 4613 2739 2.94 4322 2374 2.55 4156 2106 2.26 3907 1860 1.99<br />

0.6 4876 3416 3.66 4651 2997 3.21 4359 2582 2.77 4038 2220 2.38 3860 1966 2.11 3590 1724 1.85<br />

0.8 4713 3291 3.53 4387 2823 3.03 4077 2417 2.59 3719 2059 2.21 3541 1827 1.96 3242 1584 1.70<br />

1.0 4476 3116 3.34 4084 2632 2.82 3768 2245 2.41 3365 1892 2.03 3197 1691 1.81 - - -<br />

1.2 4165 2898 3.11 3741 2427 2.60 3432 2070 2.22 - - - - - - - - -<br />

1.4 3779 2646 2.84 3359 2212 2.37 3069 1895 2.03 - - - - - - - - -<br />

1.6 3319 2372 2.54 - - - - - - - - - - - - - - -<br />

1. Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.<br />

2.<br />

Blower performance includes two-inch throwaway filters.<br />

3. ESP (External Static Pressure) given is that available for the supply <strong>and</strong> return air duct system. All internal resistances have been<br />

deducted from the total static pressure of the blower.<br />

4.<br />

“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.<br />

5. W = Watts<br />

44 Unitary Products Group