26.03.2013 Views

Manual Motor Control Switches and Disconnects - Schneider Electric

Manual Motor Control Switches and Disconnects - Schneider Electric

Manual Motor Control Switches and Disconnects - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SELECT ONE OF EACH<br />

GS1 Fusible <strong>and</strong> LK3 Non-Fusible Disconnect <strong>Switches</strong><br />

Selection<br />

Selection<br />

1 SWITCH + 1 SHAFT + 1 HANDLE + 1 LUG KIT (IF REQUIRED)<br />

(see below) (see pages 31 & 32) (see pages 31 & 32) (see page 33)<br />

Compact 30A Switch Shaft 320mm Black H<strong>and</strong>le Lug Kit<br />

GS1DDU3 GS1AE2 GS1AH130 GS1AW403<br />

200A Switch<br />

GS1MU3<br />

800A Switch<br />

GS1TU3<br />

30A Side H<strong>and</strong>le<br />

GS1EERU30<br />

Fusible Disconnect <strong>Switches</strong><br />

Compact GS1 30 A<br />

Type Fuses Amps Nb<br />

Maximum Horse Power Rating<br />

Three Phase Test Function Catalog<br />

Number<br />

Poles 240 V 480 V 600 V<br />

Compact<br />

Fused<br />

CC 30 3 7.5 15 20 Yes* GS1DDU3<br />

Compact<br />

Fused<br />

J 30 3 7.5 15 20 Yes* GS1DU3<br />

* Test function is available as st<strong>and</strong>ard but can only be active with test h<strong>and</strong>le.<br />

GS1 30 to 400 A<br />

Type Fuses Amps Nb<br />

Maximum Horse Power Rating<br />

Three Phase Test Function Catalog<br />

Number<br />

Poles 240 V 480 V 600 V<br />

Fused CC 30 3 7.5 15 20 Yes* GS1EEU3<br />

Fused J 30 3 7.5 15 20 Yes* GS1EU3<br />

Fused J 60 3 15 30 50 Yes* GS1GU3<br />

Fused J 100 3 30 60 75 Yes* GS1JU3 s<br />

Fused J 200 3 60 125 150 Yes* GS1MU3 s<br />

Fused J 400 3 125 250 350 Yes* GS1QU3 s<br />

* Test function is available as st<strong>and</strong>ard but can only be active with test h<strong>and</strong>le.<br />

GS1 600 to 800 A<br />

Type Fuses Amps Nb<br />

Maximum Horse Power Rating<br />

Three Phase Test Function Catalog<br />

Number<br />

Poles 240 V 480 V 600 V<br />

Fused J 600 3 250 500 500 No GS1SU3 s<br />

Fused L 800 3 250 500 500 No GS1TU3 s<br />

For H<strong>and</strong>les <strong>and</strong> Shafts, see pages 31 & 32.<br />

s Terminal lugs must be ordered separately.<br />

With Direct Mount Side H<strong>and</strong>le<br />

Type Fuses Amps Nb Three Phase<br />

Maximum Horse Power Rating<br />

Test<br />

Function<br />

03/04 © 1999-2004 <strong>Schneider</strong> <strong>Electric</strong> All Rights Reserved<br />

Catalog<br />

Number<br />

Poles 240 V 480 V 600 V<br />

Fused CC 30 2 – – – No GS1EERU20<br />

Fused CC 30 3 7.5 15 20 No GS1EERU30<br />

29

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!