<strong>28.1</strong><br />

Product Selection<br />

When Ordering Specify<br />

● Catalog number<br />

<strong>NEMA</strong> <strong>Contactors</strong> <strong>and</strong> <strong>Starters</strong><br />

Freedom Series<br />

● Heater pack number (see selection table, Pages 281–283) or full load current<br />

BN16DM0AB<br />

Wiring Diagrams<br />

Type BN16 <strong>NEMA</strong>—Manual or Automatic Reset Overload Relay<br />

<strong>NEMA</strong><br />

Size<br />

Notes<br />

For separate 120V control circuit. For maximum hp at listed motor voltages, use the rating of other starters of same size.<br />

Single-Phase Applications (Factory Wired)<br />

1<br />

M<br />

OL<br />

1<br />

L1<br />

Maximum Horsepower Magnet Coil Voltage<br />

Open Type Two-Pole<br />

Motor Voltage Single-Phase (60 Hz)<br />

Catalog Number<br />

00 115 1/3 120 BN16AN0AC<br />

230 1 240 BN16AN0BC<br />

0 115 1 120 BN16BN0AC<br />

230 2 240 BN16BN0BC<br />

1 115 2 120 BN16DN0AB<br />

230 3 240 BN16DN0BB<br />

1P 115 3 120 BN16PN0AB<br />

230 5 240 BN16PN0BB<br />

2 115 3 120 BN16GN0AB<br />

230 7-1/2 240 BN16GN0BB<br />

3 115 7-1/2 120 BN16KN0A<br />

230 15 240 BN16KN0B<br />

Starter catalog numbers do not include heater packs. Select one carton of three heater packs. Heater pack selection, Pages 281–283.<br />

AC Lines<br />

A1 A2<br />

2/T1 4/T2 6/T3<br />

T1<br />

2<br />

T2<br />

4<br />

3<br />

L2<br />

Front View of Panel<br />

2/13<br />

3/14<br />

98<br />

“C”<br />

97<br />

96<br />

Reset<br />

95<br />

Separate Control<br />

Remove Wire “C” if supplied <strong>and</strong> connect separate control<br />

lines to the Number 1 Terminal on the remote pilot device<br />

<strong>and</strong> to the Number 96 Terminal on the overload relay.<br />

Two-Wire Control<br />

When more than<br />

one pushbutton<br />

station is used,<br />

omit Connector “A”<br />

<strong>and</strong> connect per<br />

sketch at right.<br />

T1 T2<br />

Single-Phase Motor<br />

3/14<br />

START<br />

1 3/14<br />

Not for Use with<br />

Auto Reset OL Relays<br />

STOP<br />

2/13<br />

1<br />

Three-Wire Control<br />

START “A”<br />

STOP<br />

256 Volume 5—Motor Control <strong>and</strong> Protection CA08100006E—December 2010 www.eaton.com<br />

For Immediate Delivery or Tech Support call KM<strong>Parts</strong>.com at (866) 595-9616<br />

START<br />

STOP<br />

3/14<br />

2/13<br />

1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!