24.07.2013 Views

Xpelair XID Centrifugal metal inline fans - CMS

Xpelair XID Centrifugal metal inline fans - CMS

Xpelair XID Centrifugal metal inline fans - CMS

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Dimensions<br />

Controllers<br />

and Accessories<br />

Auto Changeover Switches<br />

MAC-M manual duty sharing controller with<br />

auto changeover on fan failure<br />

Allows manual selection of the ‘duty’ and ‘standby’<br />

<strong>fans</strong>. Automatic changeover occurs when one of the<br />

<strong>fans</strong> fails.<br />

The changeover panel incorporates a ‘power on’<br />

indicator, and ‘run’ and ‘fail’ lights indicating fan<br />

operational status.<br />

When ‘Fan 1’ is manually selected, the light<br />

sequence is:<br />

Amber power light ON<br />

Fan 1 green ‘run’ light ON<br />

Fan 1 red ‘fail’ light OFF<br />

Fan 2 green ‘run’ light OFF<br />

Fan 2 red ‘fail’ light OFF<br />

When ‘Fan 2’ is manually selected, the ‘Fan 1’ green<br />

‘run’ light is OFF and the ‘Fan 2’ green ‘run’ light is ON.<br />

When the automatic changeover panel switches to<br />

‘Fan 2’ due to ‘Fan 1’ failure, the light sequence is:<br />

Amber power light ON<br />

Fan 1 green ‘run’ light ON<br />

Fan 1 red ‘fail’ light ON<br />

Fan 2 green ‘run’ light ON<br />

Fan 2 red ‘fail’ light OFF<br />

dia<br />

When ‘Fan 1’ is operational due to ‘Fan 2’ failure,<br />

the ‘Fan 1’ red ‘fail’ light is OFF and the ‘Fan 2’ red<br />

‘fail’ light is ON.<br />

Fan ‘failure’ is via a very reliable airflow sensing flow<br />

switch device within the case. This gives automatic<br />

changeover and fan status indication on the<br />

control panel.<br />

MAC-M manual duty sharing controller with auto<br />

changeover should be switched from ‘Fan 1’ run to<br />

‘Fan 2’ run on a weekly cycle.<br />

MAC-A automatic duty sharing controller with<br />

auto changeover on fan failure<br />

Operates as MAC-M with the addition of automatic<br />

timed change of the ‘duty’ and ‘standby’ <strong>fans</strong> every<br />

12 hours.<br />

35<br />