16<br />

7.2. typIcaL INStaLLatION Of <strong>EQUINOX</strong> - thIN-fILM<br />

MOdULES IN paraLLEL cONfIgUratION.<br />

fig. 8.<br />

Thin-film installation with EqUINOX of 5 kW.<br />

part list for inverter of 5kw<br />

Item part Q. description<br />

1 Inverter 1 Equinox 5kW AC, grid connection.<br />

2 DC switch 1 Included in Equinox: 2 poles, 125 Vdc, 100 A<br />

3 Combinator 1 Combinator circuit 5 string: Fuses (5 @ 20<br />

A, 125 Vdc)<br />

4 Bus N 4 cables 14 Negative bus module, 4 modules per cable<br />

5 Bus P 4 cables 14 Positive bus module, 4 modules per cable<br />

6 Photovol.<br />

module<br />

56<br />

Installation of particular cables<br />

cable section Q. cable connetor type Length<br />

A 5 6 mm 2 MC4 -/blank *TBD<br />

B 5 6 mm 2 MC4 +/blank *TBD<br />

C 2 16 mm 2 blank/blank *0,5 m<br />

* Current lenght are determined depending on the parts location .<br />

combinator<br />

circuit<br />

dc switches<br />

Inverter<br />

Install the peripherals adjacent<br />

to the inverter<br />