5.<br />

6.<br />

8<br />

Connect the left and right power cables from transformer to<br />

the studs in the rear side of electronic module. Connectors<br />

have a tactile mechanical locking. Connect the AC power cable<br />

to the rear side (bottom left) of electronic module.<br />

Note: avoid that cables touch the transformers.<br />

Connect the AC cables from grid to AC connector located at<br />

bottom-right side of transformer module.<br />

Put the left and right covers of transformer module. Connect<br />

the earth cables and fix the covers to transformer module by<br />

using the 2 supplied screws (it is only shown the left side - repeat<br />

the process for left side).<br />

fig. 5.<br />

Process of physical installation.<br />

4.3. cONNEctION.<br />

Wiring methods must be in accordance with local regulations.<br />

Appendix A includes a detailed electrical diagram for a typical<br />

EqUINOX <strong>LV</strong> system.<br />

photovoltaic modules (pV) have to be disconnected<br />

from wires that link the panel with the inverter before<br />

the installation. risk of electrocution.<br />

4.3.1. Of dc input.<br />

The following procedure describes the steps to connect the inverter<br />

to the photovoltaic panels.<br />

attention: a wrong connection can both damage<br />

the equipment and make injuries to the personnel.<br />

do no exceed the stated maximum dc voltage.<br />

1.<br />

2.<br />

3.<br />

4.<br />

5.<br />

6.<br />

7.<br />

Check that power supply cables from photovoltaic panels are<br />

disconnected or not alive.<br />

do not disconnect the cables from photovoltaic<br />

panels, risk of electrocution exists.<br />

Address the DC cables from panels to DC input cable glands of<br />

combinator module.<br />

Connect the negative cable to “PV Array Negative” terminal<br />

strip.<br />

Connect the positive cable to “PV Array Positive” terminal<br />

strip.<br />

Connect the photovoltaic panels to the wires of combinator<br />

module.<br />

Check the open circuit voltage of each circuit (positive cable<br />

of each circuit has to be isolated from DC bus) with a digital<br />

voltmeter. Check the voltage between each positive cable and<br />

negative of terminal strip first. Voltage can be a little bit different<br />

from the expected open circuit votlage due to the temperature<br />

of the module and/or the sunlight. Nevertheless, if<br />

panels are properly wired, each circuit should be at a few volts<br />

from the other ones.<br />

Leave DC switches in OFF position.<br />

4.3.2. Of ac output.<br />

The following procedure describes the steps to connect the inverter<br />

to the protection switchgear panel (interconnection point).<br />

1.<br />

2.<br />

3.<br />

attention: a wrong connection of the panel wiring<br />

can damage the unit and make personal injuries.<br />

Remove the panel of AC wiring.<br />

Connect the AC cable.<br />

Address cables to L1 and L2. Connect the earth cable to GND<br />

terminal.<br />

4.4. UNINStaLLatION.<br />

an error when disconnecting the cables of photovoltaic<br />

panels can cause risk of electrocution.<br />

USEr MaNUaL