<strong>Sterlite</strong> Power<br />

Cable Solutions


<strong>Sterlite</strong> Medium Voltage (MV) XLPE-insulated Power Cables<br />

Product Applications<br />

<strong>Sterlite</strong>(R) Medium Voltage (MV) power cables are crosslinked polyethylene (XLPE-insulated) cables that possess very good<br />

electrical, mechanical and thermal characteristics in medium voltage networks. This type of insulation offers excellent chemical<br />

resistant, is non-hygroscopic and is resistant to cold.<br />

Product Applications<br />

Crosslinked polyethylene (XLPE) has become the globally preferred insulation for power cables, both for distribution and<br />

transmission system applications.<br />

Product Benefits<br />

Higher current carrying capacity due to higher permissible continuous conductor temperature<br />

0<br />

Higher Short Circuit rating as it can withstand short circuit temperature up to 250 C<br />

0<br />

Higher temperature to withstand emergency overload up to 130 C<br />

Extremely low dielectric losses<br />

Light-weight<br />

Easier to join and terminate<br />

Smaller bending radius<br />

0<br />

Flexible up to -40 C<br />

Not prone to fatigue damage due to vibration or loading cycles<br />

Typical Product Specifications<br />

Conductor: Electrolytic grade Copper or Aluminum, round, multi-wire stranded, circular and compact in various sizes according to<br />

IS 8130/ IEC 60228.<br />

Conductor Shield: Conductors for cables rated over 3.3 KV are shielded by extruded semi conducting compound which is of<br />

bonded type.<br />

Insulation: Natural, chemically cross linked polyethylene. Thickness is according to relevant IS or IEC standards.<br />

Insulation Shield: Cables rated over 3.3 KV have a non-metallic semi conducting part in combination with a metallic part applied<br />

over the insulation. Non-metallic part is generally made of extruded semi conducting compound and is applied together with<br />

conductor shield. Insulation in one process (wherever required semi conducting tape/ water swellable tape is provided) can be<br />

applied directly over non-metallic insulation screen followed by helically applied bare annealed plain copper tape applied with an<br />

overlap.<br />

Core Identification: It can be provided by coloured strips applied on core or by printed numerals (1, 2&3) or printed strips.<br />

Laying–Up: For multi core cables, the cores are cabled with fillers in the interstices.<br />

Inner Sheath (Common Covering): The laid up cores are provided with a common covering either of tape or extrusion of thickness<br />

as per relevant standard.<br />

Armour: The armour can either be applied directly over core or inner sheath of single core cables and over inner sheath for multi<br />

core cables. Aluminium wire or strip constitutes the armour for single core cables where as GI wire or strip constitutes the armour<br />

for multi core cables.<br />

Outer Sheath: All cables are provided with an extruded inner sheath whose thickness is governed by relevant standard. The PVC of<br />

outer sheath conforms to type ST 2 of IS 5831, wherever required “FR”, “FRLS” or “LSOH” can be provided. The colour of outer<br />

sheath is generally black.<br />

Issued: June 2012 1


Manufacturing Process<br />

To ensure the accuracy and precision of the manufacturing process, <strong>Sterlite</strong> has a state of-the-art plant with top of the line<br />

machines enabling control of critical process and quality parameters. All <strong>Sterlite</strong> production lines are backed up with strong quality<br />

assurance systems. This is done by ensuring that all process and test equipments are periodically calibrated with defined<br />

benchmarks.<br />

Quality Tests<br />

The following tests are performed randomly to ensure a better quality:<br />

Degree of Cross linking for the Dielectric Void and contamination test involving microscopic inspection of imperfections of<br />

the insulation<br />

Bonding test of insulation screen with the insulation<br />

Online Diameter and eccentricity measurement and control by X-Ray unit, to ensure consistency and accuracy of Insulated<br />

core.<br />

Further, all Cables produced are subjected to the following routine tests as per IS 7098 (Part-2):1985:<br />

High Voltage test<br />

Conductor Resistance test<br />

Partial Discharge test<br />

Tests on conductors<br />

Tests on Armour<br />

Test for dimensions of insulation and sheath<br />

Physical tests for insulation<br />

Physical tests for outer sheath<br />

Partial Discharge<br />

Bending test followed by partial discharge<br />

Dielectric Power Factor test as a function of voltage<br />

Dielectric Power Factor test as a function of Temperature<br />

Insulation Resistance (Volume Resistivity test)<br />

Heating cycle test<br />

Impulse withstand test<br />

High Voltage test (4 hours)<br />

Flammability<br />

Issued: June 2012 2


For FR, FRLS cables , in addition to tests mentioned above, following additional tests are done<br />

Test Function Specification Specified Value<br />

Applicable For<br />

Critical Oxygen index To determine the<br />

percentage of oxygen<br />

required for supporting<br />

combustion of sheathing<br />

material at room temperature<br />

ASTM- D- 2863 Min 29<br />

FR and FRLS<br />

Temperature Index To determine at what<br />

temperature 21 % of Oxygen<br />

will support combustion of<br />

sheathing material<br />

ASTM- D- 2863 Min 250° C<br />

FR FR and FRLS<br />

Smoke Density<br />

To determine visibility (light<br />

transmission) under fire of<br />

sheath material<br />

ASTM- D- 2843 Max 60%<br />

FRLS<br />

Acid Gas generation To measure the amount of<br />

Hydrochloric gas evolved<br />

IEC- 754- I<br />

Max 20% by weight<br />

FRLS<br />

Flammability test<br />

from PVC sheath under<br />

construction<br />

1. To determine ignition 1. Swedish<br />

1. Min 300 mm<br />

FRLS<br />

on group of cables resistance and flame<br />

standard SS unburnt portion from<br />

propagation under specified 4241475<br />

top of 850 mm<br />

conditions<br />

class F3<br />

2. To determine ignition 2. IEC 332- I 2. min unburnt portion FR and FRLS<br />

Flammability<br />

test on group<br />

of cables<br />

Longer Packing Lengths<br />

resistance and flame<br />

propagation under specified<br />

conditions<br />

3. To determine ignition<br />

resistance and flame<br />

propagation especially for a<br />

bunch of cable under<br />

specified conditions<br />

To determine flame<br />

propagation in cable in<br />

installed conditions<br />

3. IEC 332- 3<br />

50 mm from the top of<br />

600+ 25 mm sample after<br />

specified duration<br />

3. min 2.5m unburnt<br />

above burner after<br />

specified duration in<br />

3.5 m sample<br />

FR and FRLS<br />

IEEE- 383 In total burning of 20<br />

minutes at 1500 F of 8 m<br />

cable samples, burning<br />

shall not go the top<br />

FR and FRLS<br />

Larger Take up capacities in <strong>Sterlite</strong> make it possible to give longer delivery lengths than those mentioned in the catalogue to minimize number of joints<br />

which are a major cause in failures.<br />

The dimensional details, weights and packing are mentioned in Tables 1 to 10.<br />

Issued: June 2012 3


Operating Conditions:<br />

Electrical Parameters of the cables mentioned in Tables 11 to 19 are based on the following operating conditions<br />

0<br />

Maximum permissible conductor : 90 C<br />

temperature for continuous operation<br />

0<br />

Ambient Air Temperature : 40 C<br />

0<br />

Ground Temperature : 30 C<br />

0<br />

Thermal Resistivity of Soil : 150 C cm/watt<br />

Depth of Laying : 90 cms for cables up to 11 KV<br />

: 105 cms for cables above 11 KV<br />

Three single core cables are laid in trefoil formation with screen/Armour bonded at both ends<br />

Multi core cables are laid singly<br />

Rating Factors:<br />

For installations other than standard conditions mentioned above, rating factors have to be applied and have been given in Tables 20 to 25.<br />

Issued: June 2012<br />

4


DIMENSION AND WEIGHT (Tables)<br />

Table 01<br />

Single-core 3.8/6.6 KV Cables<br />

Single wire Armoured cables with Aluminium conductors<br />

Single Core Aluminium Conductor Extruded Semiconducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, PVC type ST 2 inner sheathed, Aluminium wire Armoured, PVC type ST 2 outer sheathed<br />

3.8/6.6 KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code: A2XWaY<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

630<br />

800<br />

1000<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

3.0<br />

3.3<br />

3.5<br />

3.5<br />

3.6<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.3<br />

0.3<br />

0.3<br />

0.3<br />

0.3<br />

0.3<br />

0.4<br />

0.4<br />

0.4<br />

0.5<br />

0.5<br />

0.5<br />

Table 02<br />

Three-core 3.8/6.6 KV<br />

strip Armoured cables with Aluminium conductors<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

2.8<br />

3.0<br />

3.3<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.4<br />

0.4<br />

0.5<br />

0.5<br />

0.5<br />

0.6<br />

0.6<br />

0.6<br />

0.7<br />

0.7<br />

0.7<br />

Nominal<br />

diameter of<br />

armour<br />

mm<br />

1.6<br />

1.6<br />

1.6<br />

1.6<br />

1.6<br />

1.6<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.5<br />

2.5<br />

Nominal<br />

Dimension of<br />

armour<br />

mm<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.4<br />

1.4<br />

1.4<br />

1.4<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.72<br />

1.88<br />

2.04<br />

2.20<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.56<br />

1.72<br />

1.72<br />

1.88<br />

1.88<br />

2.04<br />

2.2<br />

2.2<br />

2.36<br />

2.52<br />

2.84<br />

Approx<br />

overall<br />

dia<br />

mm<br />

24.5<br />

26.0<br />

28.0<br />

29.0<br />

31.0<br />

35.5<br />

35.5<br />

37.7<br />

42.0<br />

49.0<br />

54.0<br />

59.0<br />

Approx<br />

overall<br />

dia<br />

mm<br />

36.0<br />

39.0<br />

42.0<br />

45.5<br />

49.5<br />

53.0<br />

56.5<br />

60.0<br />

65.5<br />

70.2<br />

79.5<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

760<br />

870<br />

1000<br />

1130<br />

1130<br />

1450<br />

1770<br />

2030<br />

2500<br />

3480<br />

4340<br />

5180<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

1650<br />

1900<br />

2190<br />

2610<br />

3040<br />

3510<br />

4000<br />

4575<br />

5465<br />

6390<br />

7950<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

Three Core Aluminium Conductor Extruded Semiconducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, Taped PVC type ST 2 inner sheathed, Steel strip Armoured, PVC type ST 2 outer sheathed<br />

3.8/6.6 KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code:A2XFY(T)<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

Issued: June 2012<br />

5


DIMENSION AND WEIGHT (Tables)<br />

Table 03<br />

Single-core 6.6/6.6 KV and 6.35/11 KV Cables<br />

Single wire Armoured cables with Aluminium conductors<br />

Single Core Aluminium Conductor Extruded Semiconducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, PVC type ST 2 inner sheathed, Aluminium wire Armoured, PVC type ST 2 outer sheathed<br />

6.35/11 KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code: A2XWaY<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

630<br />

800<br />

1000<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

3.6<br />

Minimum<br />

Thickness of<br />

iinner sheath<br />

mm<br />

0.3<br />

0.3<br />

0.3<br />

0.3<br />

0.3<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.5<br />

0.5<br />

0.6<br />

Table 04<br />

Three-core 6.6/6.6 KV or 6.35/11 KV<br />

strip Armoured cables with Aluminium conductors<br />

Three Core Aluminium Conductor Extruded Semiconducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, Taped PVC type ST 2 inner sheathed, Steel strip Armoured, PVC type ST 2 outer sheathed<br />

6.35/11 KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code:A2XFY(T)<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.4<br />

0.5<br />

0.5<br />

0.5<br />

0.6<br />

0.6<br />

0.6<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

Nominal<br />

diameter of<br />

armour<br />

mm<br />

1.6<br />

1.6<br />

1.6<br />

1.6<br />

1.6<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.5<br />

2.5<br />

Nominal<br />

Dimension<br />

outer sheath<br />

mm<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.4<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.72<br />

1.88<br />

2.04<br />

2.20<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.72<br />

1.72<br />

1.88<br />

1.88<br />

2.04<br />

2.20<br />

2.20<br />

2.36<br />

2.52<br />

2.68<br />

2.84<br />

Approx<br />

overall<br />

dia<br />

mm<br />

26.0<br />

27.5<br />

29.5<br />

31.0<br />

32.5<br />

35.0<br />

37.3<br />

39.0<br />

42.5<br />

49.5<br />

54.5<br />

59.0<br />

App<br />

overall<br />

diameter<br />

mm<br />

40.0<br />

42.5<br />

45.5<br />

49.0<br />

53.0<br />

56.5<br />

60.0<br />

64.0<br />

69.0<br />

73.5<br />

80.5<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

840<br />

960<br />

1100<br />

1250<br />

1380<br />

1630<br />

1880<br />

2110<br />

2570<br />

3500<br />

4370<br />

5200<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

1940<br />

2175<br />

2500<br />

2900<br />

3450<br />

3900<br />

4370<br />

5030<br />

5920<br />

6780<br />

8120<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

Standard<br />

packing length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

350<br />

300<br />

Issued: June 2012<br />

6


DIMENSION AND WEIGHT (Tables)<br />

Table 05<br />

Single-core 11/11 KV Cables<br />

Single wire Armoured cables with Aluminium conductors<br />

Single Core Aluminium Conductor Extruded Semi conducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, PVC type ST 2 inner sheathed, Aluminium wire Armoured, PVC type ST 2 outer sheathed 11/11<br />

KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code: A2XWaY<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

630<br />

800<br />

1000<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

5.5<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.3<br />

0.3<br />

0.3<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.5<br />

0.5<br />

0.6<br />

0.6<br />

Table 06<br />

Three-core 11/11 KV<br />

strip Armoured cables with Aluminium conductors<br />

Three Core Aluminium Conductor Extruded Semi conducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, Taped PVC type ST 2 inner sheathed, Steel strip Armoured, PVC type ST 2 outer sheathed 11/11<br />

KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code:A2XFY(T)<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.5<br />

0.6<br />

0.6<br />

0.6<br />

0.6<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

Nominal<br />

diameter of<br />

armour<br />

mm<br />

1.6<br />

1.6<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.5<br />

2.5<br />

2.5<br />

Nominal<br />

Dimension<br />

of Armour<br />

mm<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.72<br />

1.72<br />

1.88<br />

2.04<br />

2.20<br />

2.36<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.88<br />

2.04<br />

2.20<br />

2.20<br />

2.36<br />

2.36<br />

2.52<br />

2.68<br />

2.84<br />

3.00<br />

3.00<br />

Approx<br />

overall<br />

dia<br />

mm<br />

30.2<br />

31.7<br />

34.2<br />

35.5<br />

37.0<br />

38.8<br />

41.5<br />

43.0<br />

46.5<br />

54.5<br />

58.7<br />

63.0<br />

App<br />

overall<br />

diameter<br />

mm<br />

48.5<br />

51.5<br />

54.5<br />

58.0<br />

62.0<br />

65.5<br />

69.0<br />

73.0<br />

78.0<br />

82.0<br />

89.0<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

1070<br />

1200<br />

1420<br />

1550<br />

1700<br />

1840<br />

2200<br />

2420<br />

2880<br />

4030<br />

4800<br />

5600<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

2670<br />

3010<br />

3360<br />

3800<br />

4390<br />

4880<br />

5430<br />

6120<br />

7080<br />

7970<br />

9360<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

400<br />

350<br />

250<br />

200<br />

Issued: June 2012<br />

7


DIMENSION AND WEIGHT (Tables)<br />

Table 07<br />

Single-core 12.7/22 KV Cables<br />

Single wire Armoured cables with Aluminium conductors<br />

Single Core Aluminium Conductor Extruded Semi conducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, PVC type ST 2 inner sheathed, Aluminium wire Armoured, PVC type ST 2 outer sheathed<br />

12.7/22 KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code: A2XWaY<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

630<br />

800<br />

1000<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

6.0<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.3<br />

0.3<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.5<br />

0.5<br />

0.6<br />

0.6<br />

Table 08<br />

Three-core 12.7/22 KV<br />

strip Armoured cables with Aluminium conductors<br />

Three Core Aluminium Conductor Extruded Semi conducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, Taped PVC type ST 2 inner sheathed, Steel strip Armoured, PVC type ST 2 outer sheathed<br />

12.7/22 KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code:A2XFY(T)<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.5<br />

0.6<br />

0.6<br />

0.6<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

Nominal<br />

diameter of<br />

armour<br />

mm<br />

1.6<br />

1.6<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.5<br />

2.5<br />

2.5<br />

Nominal<br />

Dimension<br />

of Armour<br />

mm<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.56<br />

1.72<br />

1.72<br />

1.72<br />

1.88<br />

2.04<br />

2.20<br />

2.36<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

2.04<br />

2.04<br />

2.20<br />

2.36<br />

2.36<br />

2.52<br />

2.68<br />

2.68<br />

2.84<br />

3.0<br />

3.0<br />

Approx<br />

overall<br />

dia<br />

mm<br />

31.2<br />

32.6<br />

35.2<br />

36.6<br />

38.0<br />

40.2<br />

42.4<br />

44.0<br />

47.7<br />

55.6<br />

59.7<br />

64.0<br />

App<br />

overall<br />

diameter<br />

mm<br />

51.0<br />

53.5<br />

57.0<br />

60.5<br />

64.5<br />

68.0<br />

71.5<br />

75.0<br />

80.0<br />

84.0<br />

91.0<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

1140<br />

1280<br />

1500<br />

1650<br />

1800<br />

2030<br />

2300<br />

2550<br />

3000<br />

4160<br />

4970<br />

5800<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

2900<br />

3200<br />

3590<br />

4100<br />

4650<br />

5175<br />

5750<br />

6380<br />

7360<br />

8280<br />

9670<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

400<br />

350<br />

300<br />

250<br />

200<br />

Issued: June 2012<br />

8


DIMENSION AND WEIGHT (Tables)<br />

Table 09<br />

Single-core 19/33 KV Cables<br />

Single wire Armoured cables with Aluminium conductors<br />

Single Core Aluminium Conductor Extruded Semi conducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, PVC type ST 2 inner sheathed, Aluminium wire Armoured, PVC type ST 2 outer sheathed 19/33<br />

KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code: A2XWaY<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

630<br />

800<br />

1000<br />

Nominal area<br />

of conductor<br />

Sq.mm<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

Nominal<br />

Thickness of<br />

insulation<br />

mm<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

8.8<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.4<br />

0.5<br />

0.5<br />

0.5<br />

0.5<br />

0.6<br />

0.6<br />

0.7<br />

Table 10<br />

Three-core 19/33 KV<br />

strip Armoured cables with Aluminium conductors<br />

Three Core Aluminium Conductor Extruded Semi conducting compound screened, XLPE insulated, Semi conducting compound<br />

screened, helical copper tape wrapped, Taped PVC type ST 2 inner sheathed, Steel strip Armoured, PVC type ST 2 outer sheathed 19/33<br />

KV cable conforming to IS 7098 (Part-2):1985 with latest amendments. Code:A2XFY(T)<br />

Minimum<br />

Thickness of<br />

inner sheath<br />

mm<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

0.7<br />

Nominal<br />

diameter of<br />

armour<br />

mm<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.0<br />

2.5<br />

2.5<br />

2.5<br />

2.5<br />

3.15<br />

Nominal<br />

Dimension<br />

of Armour<br />

mm<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

4 x 0.8<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

1.56<br />

1.56<br />

1.72<br />

1.72<br />

1.72<br />

1.88<br />

1.88<br />

2.04<br />

2.04<br />

2.36<br />

2.36<br />

2.52<br />

Minimum<br />

Thickness of<br />

outer sheath<br />

mm<br />

2.52<br />

2.68<br />

2.84<br />

2.84<br />

3.00<br />

3.00<br />

3.00<br />

3.00<br />

3.00<br />

Approx<br />

overall<br />

dia<br />

mm<br />

36.5<br />

38.2<br />

40.2<br />

41.6<br />

43.0<br />

45.1<br />

47.3<br />

50.4<br />

53.7<br />

61.2<br />

64.6<br />

70.5<br />

App<br />

overall<br />

diameter<br />

mm<br />

69.5<br />

73.5<br />

77.5<br />

80.5<br />

84.0<br />

88.0<br />

92.5<br />

96.5<br />

103.0<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

1470<br />

1600<br />

1800<br />

1960<br />

2100<br />

2340<br />

2630<br />

3070<br />

3500<br />

4700<br />

5410<br />

6560<br />

Approx<br />

Cable<br />

Weight<br />

kg/km<br />

5050<br />

5660<br />

6310<br />

6840<br />

7480<br />

8190<br />

9190<br />

10080<br />

11600<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

500<br />

Standard<br />

packing<br />

length<br />

metres<br />

500<br />

500<br />

500<br />

500<br />

400<br />

350<br />

300<br />

250<br />

200<br />

Issued: June 2012<br />

9


ELECTRICAL PARAMETERS (Tables)<br />

Table 11<br />

PERMISSIBLE MAXIMUM SHORT CIRCUIT RATINGS FOR XLPE CABLES<br />

Conductor Area<br />

Sq.mm<br />

16<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

Short circuit rating for 1 second duration<br />

Copper Conductor Aluminium Conductor<br />

KA<br />

2.28<br />

3.57<br />

5.0<br />

7.15<br />

10.0<br />

13.58<br />

17.16<br />

21.45<br />

26.45<br />

34.32<br />

42.9<br />

57.2<br />

71.5<br />

90.0<br />

114.28<br />

142.85<br />

KA<br />

1.51<br />

2.36<br />

3.30<br />

4.72<br />

6.60<br />

8.96<br />

11.32<br />

14.16<br />

17.46<br />

22.65<br />

28.32<br />

37.76<br />

47.20<br />

59.47<br />

75.52<br />

94.40<br />

For duration other than 1 second, short circuit may be calculated from the following formula : Isc = I/t<br />

Isc=Short circuit current during time t in Amperes<br />

I = Short circuit during time of 1 second, as given in above table<br />

t = Short circuit current duration in seconds<br />

Note: For large currents , the force between the conductors must be considered specially when single core cables are used<br />

Table 12<br />

CAPACITANCE<br />

Conductor Area<br />

Sq.mm<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

CAPACITANCE<br />

3.8/6.6 KV<br />

6.6/6.6 KV &<br />

6.35/11 KV<br />

11/11 KV<br />

µF/Km<br />

µF/Km<br />

µF/Km<br />

0.22<br />

0.18<br />

0.135<br />

0.24<br />

0.20<br />

0.148<br />

0.27<br />

0.22<br />

0.165<br />

0.31<br />

0.25<br />

0.184<br />

0.35<br />

0.28<br />

0.205<br />

0.38<br />

0.31<br />

0.222<br />

0.42<br />

0.34<br />

0.239<br />

0.46<br />

0.37<br />

0.260<br />

0.51<br />

0.41<br />

0.286<br />

0.51<br />

0.44<br />

0.306<br />

0.53<br />

0.49<br />

0.343<br />

0.56<br />

0.55<br />

0.380<br />

0.63<br />

0.61<br />

0.421<br />

0.69<br />

0.67<br />

0.462<br />

0.75<br />

0.75<br />

0.508<br />

12.7/22 KV<br />

µF/Km<br />

0.128<br />

0.139<br />

0.155<br />

0.173<br />

0.192<br />

0.208<br />

0.224<br />

0.243<br />

0.266<br />

0.285<br />

0.319<br />

0.353<br />

0.391<br />

0.428<br />

0.471<br />

19/33 KV<br />

µF/Km<br />

-<br />

-<br />

0.121<br />

0.134<br />

0.147<br />

0.158<br />

0.169<br />

0.182<br />

0.199<br />

0.211<br />

0.235<br />

0.258<br />

0.284<br />

0.310<br />

0.339<br />

Issued: June 2012<br />

10


ELECTRICAL PARAMETERS (Tables)<br />

Table 13<br />

CURRENT RATING<br />

Cable<br />

size<br />

mm²<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

Cable<br />

size<br />

mm²<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

Ground<br />

96<br />

115<br />

135<br />

165<br />

195<br />

225<br />

250<br />

285<br />

330<br />

370<br />

420<br />

480<br />

540<br />

610<br />

680<br />

Ground<br />

98<br />

115<br />

140<br />

170<br />

200<br />

225<br />

250<br />

285<br />

325<br />

365<br />

410<br />

465<br />

520<br />

560<br />

600<br />

3.3 kV (E) & (UE)<br />

Duct<br />

86<br />

100<br />

120<br />

145<br />

175<br />

200<br />

220<br />

250<br />

285<br />

325<br />

370<br />

420<br />

470<br />

530<br />

580<br />

Table 14<br />

CURRENT RATING<br />

3.3 kV (E) & (UE)<br />

Duct<br />

87<br />

105<br />

120<br />

150<br />

175<br />

200<br />

220<br />

250<br />

285<br />

320<br />

360<br />

400<br />

445<br />

485<br />

510<br />

Single core XLPE Insulated Unarmoured Cables laid in trefoil formation (Solid Bonded)<br />

Aluminium (Amp) Copper (Amp)<br />

Air<br />

105<br />

125<br />

150<br />

190<br />

235<br />

275<br />

310<br />

360<br />

425<br />

495<br />

580<br />

690<br />

800<br />

930<br />

1060<br />

Air<br />

110<br />

135<br />

160<br />

200<br />

245<br />

285<br />

325<br />

375<br />

440<br />

500<br />

590<br />

680<br />

780<br />

880<br />

970<br />

6.6kV (E),11kV(E)<br />

& 11kV(UE)<br />

Ground<br />

97<br />

115<br />

135<br />

165<br />

200<br />

225<br />

250<br />

285<br />

330<br />

370<br />

425<br />

485<br />

550<br />

620<br />

690<br />

Ground<br />

99<br />

115<br />

140<br />

170<br />

200<br />

225<br />

250<br />

285<br />

325<br />

365<br />

410<br />

455<br />

510<br />

550<br />

590<br />

Duct<br />

86<br />

100<br />

120<br />

145<br />

175<br />

195<br />

220<br />

250<br />

285<br />

325<br />

375<br />

420<br />

475<br />

530<br />

590<br />

Duct<br />

87<br />

105<br />

120<br />

145<br />

175<br />

195<br />

220<br />

245<br />

280<br />

315<br />

355<br />

395<br />

435<br />

470<br />

500<br />

Air<br />

110<br />

135<br />

160<br />

200<br />

245<br />

285<br />

320<br />

370<br />

455<br />

510<br />

600<br />

700<br />

810<br />

940<br />

1070<br />

6.6kV (E),11kV(E)<br />

& 11kV(UE)<br />

Air<br />

115<br />

140<br />

165<br />

210<br />

255<br />

295<br />

330<br />

380<br />

450<br />

510<br />

590<br />

680<br />

780<br />

870<br />

960<br />

22kV(E) & 33kV (E) 3.3kV<br />

Ground<br />

-<br />

115<br />

135<br />

165<br />

195<br />

225<br />

250<br />

280<br />

325<br />

370<br />

420<br />

480<br />

550<br />

610<br />

680<br />

Ground<br />

-<br />

115<br />

135<br />

165<br />

195<br />

225<br />

250<br />

280<br />

320<br />

355<br />

400<br />

445<br />

495<br />

540<br />

570<br />

Duct<br />

-<br />

100<br />

120<br />

145<br />

170<br />

195<br />

215<br />

245<br />

280<br />

320<br />

360<br />

410<br />

470<br />

520<br />

580<br />

Duct<br />

-<br />

100<br />

120<br />

145<br />

170<br />

195<br />

215<br />

240<br />

275<br />

305<br />

345<br />

380<br />

420<br />

460<br />

490<br />

Air<br />

-<br />

140<br />

170<br />

210<br />

255<br />

295<br />

330<br />

380<br />

450<br />

520<br />

610<br />

710<br />

820<br />

950<br />

1080<br />

Single core XLPE Insulated Armoured Cables laid in trefoil formation (Solid Bonded)<br />

Aluminium (Amp) Copper (Amp)<br />

22kV(E) & 33kV (E) 3.3kV<br />

Air<br />

-<br />

145<br />

170<br />

215<br />

260<br />

300<br />

340<br />

385<br />

450<br />

510<br />

600<br />

680<br />

770<br />

870<br />

950<br />

Ground<br />

125<br />

150<br />

175<br />

215<br />

255<br />

290<br />

320<br />

365<br />

420<br />

470<br />

530<br />

600<br />

670<br />

740<br />

800<br />

Ground<br />

125<br />

150<br />

175<br />

215<br />

255<br />

290<br />

325<br />

360<br />

415<br />

460<br />

510<br />

560<br />

610<br />

660<br />

680<br />

Duct<br />

110<br />

130<br />

155<br />

190<br />

225<br />

255<br />

285<br />

320<br />

370<br />

410<br />

465<br />

520<br />

580<br />

640<br />

690<br />

Duct<br />

115<br />

135<br />

155<br />

190<br />

225<br />

255<br />

285<br />

315<br />

360<br />

400<br />

445<br />

485<br />

530<br />

570<br />

580<br />

Air<br />

130<br />

160<br />

195<br />

245<br />

300<br />

350<br />

400<br />

460<br />

550<br />

630<br />

740<br />

860<br />

980<br />

1120<br />

1250<br />

Air<br />

140<br />

170<br />

205<br />

260<br />

315<br />

365<br />

415<br />

475<br />

560<br />

640<br />

730<br />

840<br />

940<br />

1040<br />

1100<br />

Ground<br />

125<br />

150<br />

175<br />

215<br />

255<br />

290<br />

325<br />

365<br />

420<br />

475<br />

540<br />

610<br />

680<br />

750<br />

820<br />

Ground<br />

125<br />

150<br />

175<br />

215<br />

255<br />

290<br />

320<br />

360<br />

410<br />

455<br />

510<br />

550<br />

600<br />

640<br />

670<br />

6.6kV (E),11kV(E)<br />

& 11kV(UE)<br />

Duct<br />

110<br />

130<br />

155<br />

190<br />

225<br />

255<br />

285<br />

320<br />

370<br />

415<br />

465<br />

520<br />

590<br />

640<br />

700<br />

6.6kV (E),11kV(E)<br />

& 11kV(UE)<br />

Duct<br />

110<br />

130<br />

155<br />

190<br />

225<br />

250<br />

280<br />

315<br />

355<br />

395<br />

435<br />

475<br />

520<br />

540<br />

570<br />

Air<br />

140<br />

175<br />

205<br />

260<br />

315<br />

365<br />

415<br />

480<br />

560<br />

650<br />

760<br />

880<br />

1010<br />

1140<br />

700<br />

Air<br />

150<br />

180<br />

215<br />

270<br />

325<br />

375<br />

425<br />

485<br />

570<br />

640<br />

730<br />

830<br />

930<br />

1010<br />

1090<br />

22kV(E) & 33kV (E)<br />

Ground<br />

-<br />

150<br />

175<br />

210<br />

255<br />

290<br />

320<br />

360<br />

420<br />

470<br />

530<br />

600<br />

680<br />

750<br />

820<br />

22kV(E) & 33kV (E)<br />

Ground<br />

-<br />

150<br />

175<br />

215<br />

250<br />

285<br />

315<br />

355<br />

400<br />

445<br />

495<br />

540<br />

580<br />

630<br />

650<br />

Duct<br />

-<br />

130<br />

150<br />

185<br />

220<br />

250<br />

280<br />

315<br />

365<br />

410<br />

460<br />

520<br />

580<br />

640<br />

700<br />

Duct<br />

-<br />

130<br />

150<br />

185<br />

220<br />

245<br />

275<br />

305<br />

350<br />

380<br />

425<br />

460<br />

500<br />

530<br />

550<br />

Air<br />

-<br />

180<br />

215<br />

270<br />

330<br />

380<br />

430<br />

490<br />

580<br />

660<br />

770<br />

890<br />

1020<br />

1160<br />

1290<br />

Air<br />

-<br />

185<br />

220<br />

275<br />

335<br />

385<br />

430<br />

490<br />

570<br />

650<br />

740<br />

830<br />

920<br />

1020<br />

1080<br />

Issued: June 2012<br />

11


ELECTRICAL PARAMETERS (Tables)<br />

Table 15<br />

CURRENT RATING<br />

Cable<br />

size<br />

mm²<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Table 16<br />

REACTANCE OF SINGLE CORE XLPE CABLES<br />

Cable<br />

size<br />

mm²<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

Ground<br />

94<br />

115<br />

135<br />

165<br />

195<br />

220<br />

245<br />

280<br />

320<br />

360<br />

410<br />

3.3 kV (E) & (UE)<br />

Duct<br />

80<br />

94<br />

110<br />

140<br />

165<br />

185<br />

210<br />

235<br />

270<br />

305<br />

350<br />

UNARM<br />

0.113<br />

0.105<br />

0.100<br />

0.097<br />

0.095<br />

0.091<br />

0.089<br />

0.088<br />

0.086<br />

0.085<br />

0.082<br />

0.081<br />

0.080<br />

Three core XLPE Insulated Armoured Cables<br />

Aluminium (Amp) Copper (Amp)<br />

Air<br />

99<br />

120<br />

145<br />

185<br />

225<br />

255<br />

295<br />

340<br />

400<br />

460<br />

535<br />

3.8/ 6.6 KV<br />

ARM<br />

/Km /Km<br />

0.128<br />

0.119<br />

0.114<br />

0.111<br />

0.108<br />

0.105<br />

0.101<br />

0.097<br />

0.094<br />

0.091<br />

0.089<br />

0.088<br />

0.087<br />

6.6kV (E),11kV(E)<br />

& 11kV(UE)<br />

Ground<br />

95<br />

115<br />

130<br />

160<br />

190<br />

220<br />

245<br />

275<br />

315<br />

355<br />

400<br />

Duct<br />

82<br />

97<br />

115<br />

140<br />

165<br />

190<br />

210<br />

240<br />

275<br />

310<br />

350<br />

APP REACTANCE AT 50Hz assuming cables in trefoil touching<br />

UNARM<br />

0.117<br />

0.109<br />

0.104<br />

0.101<br />

0.098<br />

0.096<br />

0.092<br />

0.090<br />

0.087<br />

0.085<br />

0.082<br />

0.081<br />

0.080<br />

Air<br />

105<br />

125<br />

150<br />

190<br />

230<br />

260<br />

295<br />

335<br />

395<br />

450<br />

520<br />

6.6/ 6.6KV &<br />

6.35/ 11 KV<br />

ARM<br />

/Km /Km<br />

22kV(E) & 33kV (E) 3.3 kV (E) & (UE)<br />

Ground<br />

-<br />

110<br />

130<br />

160<br />

190<br />

215<br />

240<br />

270<br />

310<br />

350<br />

395<br />

0.128<br />

0.119<br />

0.114<br />

0.111<br />

0.107<br />

0.105<br />

0.101<br />

0.099<br />

0.095<br />

0.092<br />

0.089<br />

0.088<br />

0.087<br />

Duct<br />

-<br />

98<br />

115<br />

140<br />

170<br />

190<br />

215<br />

240<br />

275<br />

310<br />

355<br />

Air<br />

-<br />

130<br />

155<br />

190<br />

230<br />

265<br />

300<br />

340<br />

400<br />

455<br />

530<br />

UNARM<br />

11/ 11 KV<br />

ARM<br />

/Km /Km<br />

0.127<br />

0.118<br />

0.113<br />

0.110<br />

0.107<br />

0.103<br />

0.099<br />

0.097<br />

0.093<br />

0.091<br />

0.088<br />

0.086<br />

0.084<br />

Ground<br />

120<br />

145<br />

170<br />

210<br />

250<br />

285<br />

315<br />

355<br />

410<br />

460<br />

520<br />

Duct<br />

100<br />

120<br />

145<br />

175<br />

210<br />

240<br />

270<br />

300<br />

350<br />

390<br />

440<br />

0.137<br />

0.128<br />

0.124<br />

0.120<br />

0.116<br />

0.111<br />

0.108<br />

0.106<br />

0.101<br />

0.098<br />

0.095<br />

0.093<br />

0.091<br />

Air<br />

125<br />

155<br />

190<br />

235<br />

290<br />

330<br />

375<br />

435<br />

510<br />

590<br />

670<br />

UNARM<br />

12.7/ 22 KV<br />

ARM<br />

/Km /Km<br />

0.130<br />

0.121<br />

0.116<br />

0.112<br />

0.109<br />

0.105<br />

0.101<br />

0.099<br />

0.095<br />

0.093<br />

0.089<br />

0.087<br />

0.085<br />

Ground<br />

120<br />

145<br />

170<br />

210<br />

250<br />

280<br />

310<br />

350<br />

400<br />

445<br />

500<br />

6.6kV (E),11kV(E)<br />

& 11kV(UE)<br />

Duct<br />

105<br />

125<br />

150<br />

180<br />

215<br />

240<br />

270<br />

305<br />

350<br />

390<br />

440<br />

0.139<br />

0.130<br />

0.125<br />

0.121<br />

0.117<br />

0.113<br />

0.109<br />

0.106<br />

0.102<br />

0.100<br />

0.097<br />

0.094<br />

0.092<br />

Air<br />

135<br />

165<br />

195<br />

240<br />

295<br />

335<br />

380<br />

430<br />

500<br />

570<br />

650<br />

UNARM<br />

19/ 33 KV<br />

ARM<br />

/Km /Km<br />

0.143<br />

0.134<br />

0.128<br />

0.124<br />

0.120<br />

0.116<br />

0.111<br />

0.109<br />

0.104<br />

0.100<br />

0.097<br />

0.095<br />

0.092<br />

22kV(E) & 33kV (E)<br />

Ground<br />

-<br />

145<br />

170<br />

205<br />

245<br />

275<br />

305<br />

345<br />

395<br />

440<br />

495<br />

Duct<br />

-<br />

125<br />

150<br />

180<br />

215<br />

245<br />

275<br />

305<br />

350<br />

390<br />

440<br />

Air<br />

-<br />

0.149<br />

0.139<br />

0.134<br />

0.129<br />

0.125<br />

0.121<br />

0.116<br />

0.115<br />

0.109<br />

0.107<br />

0.103<br />

0.099<br />

0.098<br />

165<br />

200<br />

245<br />

300<br />

340<br />

385<br />

435<br />

510<br />

580<br />

660<br />

Issued: June 2012<br />

12


ELECTRICAL PARAMETERS (Tables)<br />

Table 17<br />

REACTANCE OF 3 CORE CABLES<br />

Conductor<br />

Area<br />

mm²<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

Table 18<br />

DIELECTRIC LOSSES<br />

Conductor<br />

Area<br />

mm²<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

REACTANCE OF 3 CORE CABLES<br />

3.8/ 6.6 KV<br />

6.6/ 6.6KV &<br />

6.35/ 11 KV<br />

11/ 11 KV 12.7/ 22 KV 19/ 33 KV<br />

/Km /Km /Km /Km /Km<br />

0.101<br />

0.108<br />

0.123<br />

0.126<br />

0.143<br />

0.097<br />

0.104<br />

0.118<br />

0.121<br />

0.137<br />

0.093<br />

0.099<br />

0.112<br />

0.115<br />

0.130<br />

0.087<br />

0.093<br />

0.104<br />

0.107<br />

0.121<br />

0.084<br />

0.089<br />

0.100<br />

0.103<br />

0.116<br />

0.082<br />

0.087<br />

0.097<br />

0.100<br />

0.112<br />

0.080<br />

0.085<br />

0.094<br />

0.097<br />

0.108<br />

0.078<br />

0.082<br />

0.091<br />

0.093<br />

0.104<br />

0.076<br />

0.080<br />

0.088<br />

0.090<br />

0.101<br />

0.076<br />

0.078<br />

0.086<br />

0.088<br />

0.098<br />

0.075<br />

0.076<br />

0.083<br />

0.085<br />

0.094<br />

3.8/ 6.6 KV<br />

6.6/ 6.6KV &<br />

6.35/ 11 KV<br />

DIELECTRIC LOSSES<br />

11/ 11 KV 12.7/ 22 KV 19/ 33 KV<br />

w/ pH/Km w/ pH/Km w/ pH/Km w/ pH/Km w/ pH/Km<br />

3.943<br />

9.883<br />

20.561<br />

25.923<br />

46.097<br />

4.367<br />

10.892<br />

22.450<br />

28.250<br />

49.810<br />

4.959<br />

12.293<br />

25.063<br />

31.464<br />

54.909<br />

5.632<br />

13.884<br />

28.016<br />

35.094<br />

60.634<br />

6.344<br />

15.566<br />

31.127<br />

38.913<br />

66.628<br />

6.929<br />

16.946<br />

33.673<br />

42.038<br />

71.514<br />

7.555<br />

18.422<br />

36.390<br />

45.369<br />

76.709<br />

8.264<br />

20.091<br />

39.457<br />

49.129<br />

82.556<br />

9.180<br />

22.246<br />

43.413<br />

53.976<br />

90.075<br />

9.299<br />

23.910<br />

46.461<br />

57.709<br />

95.855<br />

9.680<br />

27.036<br />

52.184<br />

64.715<br />

106.680<br />

10.219<br />

30.061<br />

57.714<br />

71.484<br />

117.115<br />

11.382<br />

33.474<br />

63.946<br />

79.108<br />

128.852<br />

12.545<br />

36.883<br />

70.168<br />

86.720<br />

140.552<br />

13.518<br />

40.777<br />

77.270<br />

95.407<br />

153.891<br />

Issued: June 2012<br />

13


ELECTRICAL PARAMETERS (Tables)<br />

Table 19<br />

RESISTANCES<br />

Conductor<br />

Area<br />

mm²<br />

25<br />

35<br />

50<br />

70<br />

95<br />

120<br />

150<br />

185<br />

240<br />

300<br />

400<br />

500<br />

630<br />

800<br />

1000<br />

D C RESISTANCE AT 20° C A C RESISTANCE AT 90° C<br />

ALUMINIUM COPPER ALUMINIUM COPPER<br />

1.20<br />

0.868<br />

0.641<br />

0.443<br />

0.320<br />

0.253<br />

0.206<br />

0.164<br />

0.125<br />

0.100<br />

0.0778<br />

0.0605<br />

0.0469<br />

0.0367<br />

0.0291<br />

0.727<br />

0.524<br />

0.387<br />

0.268<br />

0.193<br />

0.153<br />

0.124<br />

0.0991<br />

0.0754<br />

0.0601<br />

0.0470<br />

0.0366<br />

0.0283<br />

0.0221<br />

0.0176<br />

1.53<br />

1.11<br />

0.818<br />

0.565<br />

0.409<br />

0.323<br />

0.264<br />

0.210<br />

0.161<br />

0.129<br />

0.102<br />

0.082<br />

0.065<br />

0.931<br />

0.671<br />

0.496<br />

0.344<br />

0.248<br />

0.197<br />

0.160<br />

0.129<br />

0.099<br />

0.080<br />

0.064<br />

0.052<br />

0.042<br />

Issued: June 2012<br />

14


RATING FACTORS<br />

Table 20<br />

RATING FACTORS FOR DEPTH OF LAYING<br />

(For cables laid directly in ground)<br />

Depth of laying<br />

(mm)<br />

500- 750<br />

750- 900<br />

900- 1050<br />

1050- 1200<br />

1200- 1500<br />

1500- 1800<br />

1.1 KV<br />

Cables<br />

1.00<br />

0.98<br />

0.96<br />

0.94<br />

0.92<br />

0.90<br />

3.3, 6.6,11 KV<br />

Cables<br />

-<br />

1.00<br />

0.99<br />

0.98<br />

0.96<br />

0.95<br />

22 & 33 KV<br />

Cables<br />

-<br />

-<br />

1.00<br />

0.99<br />

0.98<br />

0.96<br />

Table 21<br />

GROUP RATING FACTORS FOR MULTI CORE CABLES OR GROUPS OF SINGLE CORE CABLES IN HORIZONTAL FORMATION<br />

(For cables laid directly in ground)<br />

Number of cables or group of single core<br />

cables in same trench<br />

Spacing between cables or groups touching<br />

70 mm<br />

250 mm<br />

2 3<br />

4 5<br />

6<br />

0.79<br />

0.85<br />

0.87<br />

0.69<br />

0.75<br />

0.79<br />

Table 22<br />

GROUP RATING FACTORS FOR MULTI CORE CABLES OR GROUPS OF SINGLE CORE CABLES IN AIR ON LADDER SUPPORTS, METAL TRAYS , WALLS<br />

etc WITH MAINTAINED SPACING BETWEEN CABLES OR GROUPS<br />

Number of cables or group of single core cables<br />

Vertically<br />

1<br />

2<br />

3<br />

0.93<br />

0.83<br />

0.76<br />

0.63<br />

0.68<br />

0.75<br />

0.58<br />

0.64<br />

0.72<br />

0.55<br />

0.60<br />

0.69<br />

1 2<br />

Horizontally<br />

3 4<br />

5<br />

1.00<br />

0.89<br />

0.80<br />

0.87<br />

0.79<br />

0.72<br />

0.84<br />

0.76<br />

0.70<br />

0.83<br />

0.75<br />

0.69<br />

4 0.77 0.72 0.68 0.67 0.66<br />

Table 23<br />

RATING FACTORS FOR VARIATION IN GROUND TEMPERATURE<br />

(For cables laid directly in ground)<br />

GROUND TEMPERATURE ° C<br />

RATING FACTOR<br />

15<br />

1.12<br />

20<br />

1.08<br />

Table 24<br />

RATING FACTORS FOR VARIATION IN AMBIENT AIR TEMPERATURE<br />

AIR TEMPERATURE ° C<br />

RATING FACTOR<br />

20<br />

1.18<br />

25<br />

1.14<br />

Table 25<br />

RATING FACTORS FOR VARIATION IN THERMAL RESISTIVITY OF SOIL<br />

Voltage rating of cables<br />

1.1 & 3.3 KV<br />

6.6, 11 & 22 KV<br />

33 KV<br />

25<br />

1.04<br />

30<br />

1.10<br />

30<br />

1.0<br />

35<br />

1.05<br />

35<br />

0.96<br />

40<br />

1.0<br />

40<br />

0.91<br />

45<br />

0.95<br />

45<br />

0.87<br />

50<br />

0.89<br />

Thermal resistivity of soil (° C cm/W)<br />

100<br />

1.18<br />

120<br />

1.08<br />

150<br />

1.0<br />

200<br />

0.88<br />

250<br />

0.81<br />

0.16 1.08 1.0<br />

0.90 0.83<br />

0.12 1.07 1.0<br />

0.90 0.83<br />

50<br />

0.82<br />

55<br />

0.84<br />

300<br />

0.74<br />

0.76<br />

0.78<br />

6<br />

0.82<br />

0.74<br />

0.68<br />

0.65<br />

Issued: June 2012<br />

15


PROCESS FLOW CHART: XLPE INSULATED POWER CABLES (upto 33 kV GRADE)<br />

RAW MATERIALS<br />

ALUMINIIUM/ COPPER<br />

WIRE DRAWING<br />

A<br />

CONDUCTOR STRANDING<br />

XLPE COMPOUND<br />

SEMICONDUCTING COMPOUND XLPE TRUE TRIPLE EXTRUSION<br />

COPPER TAPE<br />

COL. IDENTIFICATION TAPE<br />

FILLERS<br />

PVC TAPE/<br />

PVC COMPOUND<br />

GALVANISED STEEL<br />

FLAT STRIPS/<br />

ROUND WIRES<br />

(A-I QUALITY CHECKPOINTS)<br />

3 CORE<br />

B<br />

C<br />

COPPER TAPING<br />

D<br />

LAYING UP OF CORES<br />

E<br />

INNER SHEATHING<br />

(TAPED/ EXTRUDED)<br />

F<br />

ARMOURING<br />

G<br />

1 CORE<br />

PACKING<br />

OUTER SHEATHING H<br />

I<br />

Issued: June 2012<br />

16


sterlitetechnologies.com<br />

China<br />

Denmark<br />

India<br />

Netherlands<br />

Russia<br />

South Africa<br />

Taiwan<br />

Turkey<br />

United Arab Emirates<br />

United Kingdom<br />

United States of America<br />

About <strong>Sterlite</strong><br />

<strong>Sterlite</strong> Technologies Limited is a leading global<br />

provider of connectivity solutions for the<br />

telecom & power industries.<br />

Equipped with a suite that includes power<br />

conductors, power cables, optical fibers, fiber<br />

cables, data cables and a comprehensive<br />

telecom solutions portfolio, <strong>Sterlite</strong>'s vision is to<br />

'Connect every home on the planet'. <strong>Sterlite</strong> is<br />

also executing multi-million dollar power<br />

transmission system projects, pan-India.<br />