19.08.2013 Views

Joints - Sterlite

Joints - Sterlite

Joints - Sterlite

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

RATING FACTORS<br />

Table 20<br />

RATING FACTORS FOR DEPTH OF LAYING<br />

(For cables laid directly in ground)<br />

Depth of laying<br />

(mm)<br />

500- 750<br />

750- 900<br />

900- 1050<br />

1050- 1200<br />

1200- 1500<br />

1500- 1800<br />

1.1 KV<br />

Cables<br />

1.00<br />

0.98<br />

0.96<br />

0.94<br />

0.92<br />

0.90<br />

3.3, 6.6,11 KV<br />

Cables<br />

-<br />

1.00<br />

0.99<br />

0.98<br />

0.96<br />

0.95<br />

22 & 33 KV<br />

Cables<br />

-<br />

-<br />

1.00<br />

0.99<br />

0.98<br />

0.96<br />

Table 21<br />

GROUP RATING FACTORS FOR MULTI CORE CABLES OR GROUPS OF SINGLE CORE CABLES IN HORIZONTAL FORMATION<br />

(For cables laid directly in ground)<br />

Number of cables or group of single core<br />

cables in same trench<br />

Spacing between cables or groups touching<br />

70 mm<br />

250 mm<br />

2 3<br />

4 5<br />

6<br />

0.79<br />

0.85<br />

0.87<br />

0.69<br />

0.75<br />

0.79<br />

Table 22<br />

GROUP RATING FACTORS FOR MULTI CORE CABLES OR GROUPS OF SINGLE CORE CABLES IN AIR ON LADDER SUPPORTS, METAL TRAYS , WALLS<br />

etc WITH MAINTAINED SPACING BETWEEN CABLES OR GROUPS<br />

Number of cables or group of single core cables<br />

Vertically<br />

1<br />

2<br />

3<br />

0.93<br />

0.83<br />

0.76<br />

0.63<br />

0.68<br />

0.75<br />

0.58<br />

0.64<br />

0.72<br />

0.55<br />

0.60<br />

0.69<br />

1 2<br />

Horizontally<br />

3 4<br />

5<br />

1.00<br />

0.89<br />

0.80<br />

0.87<br />

0.79<br />

0.72<br />

0.84<br />

0.76<br />

0.70<br />

0.83<br />

0.75<br />

0.69<br />

4 0.77 0.72 0.68 0.67 0.66<br />

Table 23<br />

RATING FACTORS FOR VARIATION IN GROUND TEMPERATURE<br />

(For cables laid directly in ground)<br />

GROUND TEMPERATURE ° C<br />

RATING FACTOR<br />

15<br />

1.12<br />

20<br />

1.08<br />

Table 24<br />

RATING FACTORS FOR VARIATION IN AMBIENT AIR TEMPERATURE<br />

AIR TEMPERATURE ° C<br />

RATING FACTOR<br />

20<br />

1.18<br />

25<br />

1.14<br />

Table 25<br />

RATING FACTORS FOR VARIATION IN THERMAL RESISTIVITY OF SOIL<br />

Voltage rating of cables<br />

1.1 & 3.3 KV<br />

6.6, 11 & 22 KV<br />

33 KV<br />

25<br />

1.04<br />

30<br />

1.10<br />

30<br />

1.0<br />

35<br />

1.05<br />

35<br />

0.96<br />

40<br />

1.0<br />

40<br />

0.91<br />

45<br />

0.95<br />

45<br />

0.87<br />

50<br />

0.89<br />

Thermal resistivity of soil (° C cm/W)<br />

100<br />

1.18<br />

120<br />

1.08<br />

150<br />

1.0<br />

200<br />

0.88<br />

250<br />

0.81<br />

0.16 1.08 1.0<br />

0.90 0.83<br />

0.12 1.07 1.0<br />

0.90 0.83<br />

50<br />

0.82<br />

55<br />

0.84<br />

300<br />

0.74<br />

0.76<br />

0.78<br />

6<br />

0.82<br />

0.74<br />

0.68<br />

0.65<br />

Issued: June 2012<br />

15

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!