For FR, FRLS cables , in addition to tests mentioned above, following additional tests are done<br />
Test Function Specification Specified Value<br />
Applicable For<br />
Critical Oxygen index To determine the<br />
percentage of oxygen<br />
required for supporting<br />
combustion of sheathing<br />
material at room temperature<br />
ASTM- D- 2863 Min 29<br />
FR and FRLS<br />
Temperature Index To determine at what<br />
temperature 21 % of Oxygen<br />
will support combustion of<br />
sheathing material<br />
ASTM- D- 2863 Min 250° C<br />
FR FR and FRLS<br />
Smoke Density<br />
To determine visibility (light<br />
transmission) under fire of<br />
sheath material<br />
ASTM- D- 2843 Max 60%<br />
FRLS<br />
Acid Gas generation To measure the amount of<br />
Hydrochloric gas evolved<br />
IEC- 754- I<br />
Max 20% by weight<br />
FRLS<br />
Flammability test<br />
from PVC sheath under<br />
construction<br />
1. To determine ignition 1. Swedish<br />
1. Min 300 mm<br />
FRLS<br />
on group of cables resistance and flame<br />
standard SS unburnt portion from<br />
propagation under specified 4241475<br />
top of 850 mm<br />
conditions<br />
class F3<br />
2. To determine ignition 2. IEC 332- I 2. min unburnt portion FR and FRLS<br />
Flammability<br />
test on group<br />
of cables<br />
Longer Packing Lengths<br />
resistance and flame<br />
propagation under specified<br />
conditions<br />
3. To determine ignition<br />
resistance and flame<br />
propagation especially for a<br />
bunch of cable under<br />
specified conditions<br />
To determine flame<br />
propagation in cable in<br />
installed conditions<br />
3. IEC 332- 3<br />
50 mm from the top of<br />
600+ 25 mm sample after<br />
specified duration<br />
3. min 2.5m unburnt<br />
above burner after<br />
specified duration in<br />
3.5 m sample<br />
FR and FRLS<br />
IEEE- 383 In total burning of 20<br />
minutes at 1500 F of 8 m<br />
cable samples, burning<br />
shall not go the top<br />
FR and FRLS<br />
Larger Take up capacities in <strong>Sterlite</strong> make it possible to give longer delivery lengths than those mentioned in the catalogue to minimize number of joints<br />
which are a major cause in failures.<br />
The dimensional details, weights and packing are mentioned in Tables 1 to 10.<br />